A1-User's Manual
31.19
Stall deceleration time
Range: 0.1 ~ 10.0 Sec in 0.1 Sec
Initial value: 1.0 Sec
Program the deceleration time for rate when the VFD detects the overload
02.01 (Final frequency reference)
31.22
RS485 Modbus time out check enable
0: Always Running ----- Initial value
1: Only during VFD is Running
Select a time out detection mode.
31.23
RS485 Modbus time out time
0: Disable
Range: 0 ~ 60 Sec in 1 Sec
Initial value: 0 Sec
Select a time out detection period when communication discontinues. If no
communication event occurs during this time period, a communication fault will occur.
Output Currnt (A)
31.18 (Stall current limit)
0
Frequency (Hz)
Related Parameters:
'31.23'
31.19 (Stall deceleration time)
142