A1-User's Manual
Set 3: Output Power
The highest analog value is the 200% of rated VFD power out. The indicator accuracy
after the adjustment is about +/- 10%.
Set 4: Output Torque
The highest analog value is the 200% of rated VFD output torque. The indicator accuracy
after the adjustment is about +/- 10%.
Set 5: Modbus communication
Special addresses 0x1004, 0x1005 can be used to control AO1 (FM) and AO2 (AMI).
For how to use communication frame, refer to 50. RS-485 (Modbus) parameter.
example)
01 06 1004 2710 CRC: AO1 (FM) 50% (5V) output
01 06 1005 2710 CRC: AO2 (AMI) 50% (12mA) output
Set 6: DC link Voltage
The 400Vac class outputs 0 ~ 820Vdc and the 200Vac class outputs 0 ~ 410Vdc as 0 ~ 10V.
The indicator accuracy after adjustment is about +/- 10%.
12.04
AO1 (FM) forced value
Range: 0.00 ~ 100.0 % in 0.01 %
Initial value: 0.0 %
Allows the data value of a forced analog output to be changed from 0.0 to 100.0
It is only possible to forced an input that has been selected in parameter
'12.01' (AO forced selection)
12.05
AO1 (FM) filter time
Range: 0 ~ 30000 ms in 1 ms
Initial value: 100 ms
Defines the filter time constant for analog input AO1
The filter time is that VFD is realized 63% of 100%
100
63
Address
function
0x1004
AO1 (FM) value
Output
0x1005
AO2 (AMI) value
output
%
Unfiltered signal
Filtered signal
T
T: Filter time constant
Explanation
0 to 10000
(0.1 scale, 0 to 10V, 0 to 100%)
0 to 10000
(0.1 scale, 4 ~ 20mA, 0 ~ 100%)
t