ETC Installation Guide
D1 & D2 Series Drivers
Note:
Note:
to NEC 700.10(B).
Emergency drivers and luminaires require two branch circuit connections. These inputs have the
following functions:
1. Normal branch circuit to sense failure of the normal supply. Connect to Sense Input
connector.
2. Normal/Emergency branch circuit providing power to the luminaire in both conditions.
Connect to Maintained Input connector.
Sense detects when power is lost and forces the luminaire to a full-on state, powered by the
emergency supply through the Constant Power input. Control of the luminaire will not be available
until the sense input has been restored.
WARNING:
feeds.
AVERTISSEMENT :
les alimentations de détection et de secours.
WARNING:
have the same phase. The diagram below shows the recommended installation.
AVERTISSEMENT :
(normal/secours) doivent être sur la même phase. Le schéma ci-dessous présente
l'installation recommandée.
Typical Installation
The typical installation shown below is suitable for all ArcSystem Pro emergency drivers and
ArcSystem Pro multi-cell emergency luminaires.
normal
normal/emergency
from UL1008
ATS by others
D1 & D2 Series Drivers
Installation must follow all national and local codes for electrical equipment.
Normal and emergency wiring cannot be contained in the same conduit according
Do not mix 120 V and 277 V between the sense and emergency
Ne pas inverser les alimentations à 120 V et 277 V entre
Sense (normal) and Maintained (normal/emergency) feeds must
Les alimentations de détection (normale) et d'entretien
normal
breaker
used to sense normal power failure
panel
normal/emergency branch circuit
emergency
breaker
panel
normal branch circuit
Sense
Maintained
Page 6 of 25
ArcSystem Pro
multi-cell emergency
luminaire or
ArcSystem Pro
One-Cell luminaire
with ArcSystem Pro
series emergency
driver
ETC
Need help?
Do you have a question about the ArcSystem Pro D1 Series and is the answer not in the manual?
Questions and answers