Figure 22
3.7

Removing the Terminal Board Enclosure

The sealing of cables and conduit entries should be carried out in accordance with the
relevant national standards or the regulatory authorities that certified the actuators. This is
especially true for units that are certified for use in hazardous areas, where the method of
sealing must be to an approved standard and cable glands, reducers, plugs, and adapters
must be approved and separately certified.
Standard cable entries (housing)
1" NPT, Qty 2
1-1/2" NPT, Qty 1
Optional: 3/4" NPT, up to Qty 2
On request, certified conduit entry adapters may be added
(Metric, Pg, Rc, ASA, etc.)
Remove the conduit entry plugs.
NOTICE
All accessories (including cable glands) must comply with approved specifications for the
site requirements and be certified according to the standard directive.
To guarantee a weather-proof and explosion-proof fit, screw the cable glands tightly
(at least 5 turns) and coat them with a thread sealant. The use of a thread sealant is
necessary in explosion-proof and weather-proof applications.
Installation
Section 3: Installation
October 2019
19