Instructions For Proper Installation; Marking - Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual

Electric actuator
Table of Contents

Advertisement

Appendix
October 2019
B.2

Instructions for Proper Installation

WARNING
Before installation, it is mandatory to check if the nameplate associated with the
extension for additional entry specifies the appropriate degree of protection and ambient
temperature limits as requested by the rules applicable to the plant/location where the
XTE3000 is installed.
Safety warnings and warranty will be invalidated if the XTE3000 is installed in explosive
atmospheres not covered by the appropriate grade of protection, and/or in environments
where temperatures exceed the maximum temperature specified on the product label.
B.2.1

Marking

Figure B-4
IECEx INE YY.NNNNX
INERIS YY ATEX NNNNX
0080
II
2
G
D
IP66/68
Table B-1.
Hazardous zone
Gas, mists, or vapors
Gas, mists, or vapors
Gas, mists, or vapors
Dust
Dust
Dust
126
Template of the label for XTE3000 / XTE3000AD / XTE3000LP
=
=
=
=
=
=
=
=
Categories according to 2014/34/EU Directive
Zone 0
Zone 1
Zone 2
Zone 20
Zone 21
Zone 22
Installation, Operation and Maintenance Manual
IECEx reference certificate (CoC)
ATEX reference certificate
Notified body for ATEX quality assurance (INERIS)
Group II (surface industries)
Category 2 apparatus
Explosive atmospheres caused by gas, mists, or vapors
Explosive atmospheres caused by gas dusts
Degree of protection
1G
2G or 1G
3G or 2G or 1G
1D
2D or 1D
3D or 2D or 1D
MAN-02-04-97-0713-EN Rev. 1
Appendix

Hide quick links:

Advertisement

Table of Contents
loading