Figure 4-30 Grounding Of Signal Cable Shields Using The Grounding Bracket; Figure 4-31 Connecting The Motor Cable To A Terminal Block In The Enclosure; Figure 4-32 Connecting The Motor Cable To An Isolator / Disconnect Switch - Emerson Affinity User Manual

Building automation hvac/r drive
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
If the control wiring is to exit the enclosure, it must be shielded and the
shield(s) clamped to the drive using the grounding bracket as shown in
Figure 4-30. Remove the outer insulating cover of the cable to ensure
the shield(s) make contact with the bracket, but keep the shield(s) intact
until as close as possible to the terminals
Alternatively, wiring may be passed through a ferrite ring, part no. 3225-
1004.
Figure 4-30 Grounding of signal cable shields using the
grounding bracket
4.11.6
Variations in the EMC wiring
Interruptions to the motor cable
The motor cable should ideally be a single length of shielded or armored
cable having no interruptions. In some situations it may be necessary to
interrupt the cable, as in the following examples:
Connecting the motor cable to a terminal block in the drive enclosure
Installing a motor isolator / disconnect switch for safety when work is
done on the motor
In these cases the following guidelines should be followed.
Terminal block in the enclosure
The motor cable shields should be bonded to the back-plate using
uninsulated metal cable-clamps which should be positioned as close as
possible to the terminal block. Keep the length of power conductors to a
minimum and ensure that all sensitive equipment and circuits are at
least 0.3m (12 in) away from the terminal block.
86
Electrical
Getting
Basic
Running
Installation
Started
parameters
the motor
www.controltechniques.com
SMARTCARD
Optimization
PC tools
operation
Figure 4-31 Connecting the motor cable to a terminal block in the
enclosure
Using a motor isolator / disconnect-switch
The motor cable shields should be connected by a very short conductor
having a low inductance. The use of a flat metal coupling-bar is
recommended; conventional wire is not suitable.
The shields should be bonded directly to the coupling-bar using
uninsulated metal cable-clamps. Keep the length of the exposed power
conductors to a minimum and ensure that all sensitive equipment and
circuits are at least 0.3m (12 in) away.
The coupling-bar may be grounded to a known low-impedance ground
nearby, for example a large metallic structure which is connected closely
to the drive ground.
Figure 4-32 Connecting the motor cable to an isolator /
disconnect switch
From the
Drive
Coupling bar
Surge immunity of control circuits - long cables and
connections outside a building
The input/output ports for the control circuits are designed for general
use within machines and small systems without any special precautions.
These circuits meet the requirements of EN 61000-6-2:2005 (1kV surge)
provided the 0V connection is not grounded.
In applications where they may be exposed to high-energy voltage
surges, some special measures may be required to prevent malfunction
or damage. Surges may be caused by lightning or severe power faults in
association with grounding arrangements which permit high transient
voltages between nominally grounded points. This is a particular risk
where the circuits extend outside the protection of a building.
Advanced
Technical
Diagnostics
parameters
Data
From the Drive
Back-plate
Enclosure
To the motor
Isolator
To the
motor
(If required)
Affinity User Guide
Issue Number: 5
UL Listing
Information

Advertisement

Table of Contents
loading

Table of Contents