Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual page 71

Electric actuator
Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
Figure 61
Example A
100%
Example C
100%
Configuration procedure
Set-Up Routines
Position request %
Configured values:
% min = 0%
% max = 100%
Polarity : 4 mA = CL
0%
Input signal
4
20
Position request %
Configured values:
% min = 0%
% max = 100%
Polarity : 4 mA = OP
0%
Input signal
4
20
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see entering the set-up mode). When the message displayed is "SET-UP MODE
OK?" press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "FAIL SAFE".
Press YES if the configured ACTION is correct (open, close, stay-put, go to position
xxx%, off). If not, press NO to change it and then press YES.
Press YES if the configured value of the DELAY is correct (from 0 to 255 seconds).
If not, press NO to change it and then press YES.
Section 9: Set-Up Routines
Example B
Position request %
100%
0%
mA
4
8
Example D
Position request %
100%
0%
mA
4
8
October 2019
Configured values:
% min = 25%
% max = 75%
Polarity : 4 mA = CL
Input signal
16 20
mA
Configured values:
% min = 25%
% max = 75%
Polarity : 4 mA = OP
Input signal
16 20
mA
63