Section 6: Local Controls
October 2019
6.2

Configuration Options

The XTE3000 actuator can be completely configured via the local interface by means of
a series of menus that can be selected from the alphanumeric display. The operator can
navigate through the different displays by answering YES or NO to the appropriate
prompt (change? OK?, view?, next?, etc.) in the right corner of the lower row of the
alphanumeric display.
To access the menus: set the local selector in OFF and then simultaneously press
OPEN/YES and STOP. The alphanumeric display will now show the present language.
Press YES if the language is correct; if not, press NO to scroll through the list of available
languages and then press YES to when the menu reaches the desired language.
After choosing the language, the next step is the selection between view and set-up mode.
Use "View" mode to see the actuator configuration, and use "Set-up" mode to change
the present configuration. Unauthorized access to the set-up mode is prevented by a
4-character alphanumeric password. The actuator is supplied by Emerson with the default
password "0 0 0 0".
Once the correct password has been entered, the actuator parameters can be configured.
The current password can also be modified by the "set password" routine in the
Maintenance menu. After entering the new password the old one becomes invalid, so it is
important to record the new password in a secure location for future retrieval.
The configuration functions (view and set-up mode) are grouped in 4 main menus:
Actuator set-up, Nameplate, Valve data, and Maintenance.
Actuator set-up
This menu includes the routines that allow the actuator to be configured according to the
requested control mode and to the valve it is mounted on.
The routines with * are only available if the relevant modules are present. If the bus
interface is LonWorks, the "BUS" routine changes to "FDI control".
44
stroke limits
torque set-up
ESD set-up
remote controls
local controls
output relays
positioner *
fail safe *
out 4-20 mA *
interlock
2-speed timer
bus *
miscellaneous