The amount of data to be viewed is large and the local display can only display one datum
at a time. To use this function, it is recommended to utilize the features of DCMlink via a
PDA or PC. Figure 67 below shows an example of a graph available on the PDA or PC screen,
showing the reference opening torque curve and the latest opening torque curve.
View Procedure
10.4.4

Operation Log

The operation log consists of different counters and routines that provide information
to assist in the maintenance program. The data are grouped into 2 families: general and
recent data. The general data log collects data from "test date" to "present date".
The test date is set in-house and can be viewed in the "Nameplate" menu, but cannot be
changed. The recent data log collects data from the last "clear recent data log" date to
"present date".
Command "clear recent data log" is available in the SET-UP MENU, maintenance, Section 7.
This command clears the content of the recent data log and resets the counters to 0. The
old data are lost.
The main differences between "general" and "recent" data log are the following:
View Routines
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see "Entering the view mode").
When the message displayed is "VIEW MODE OK?" press YES. Press NO to
scroll through the list of available menus and press YES to select the
"Maintenance" menu.
Press NO to scroll through the list of routines and press YES to select torque curve.
Press NO to scroll through the list of available curves (from 100 to 1 and
reference). Curve 100 is the latest and curve 1 is the oldest. Press YES to select.
Press YES to select the opening or closing curve. Press NO to exit.
Press YES to scroll through the list of values. Press NO to exit.
The general data log gives information relevant to the full life of the actuator,
starting from the manufacturing date.
In the recent data log the same data are collected starting from a date set by the
user. The date may be viewed in the MAINTENANCE DATE Section.