The Motor Is Very Hot And Does Not Start; The Motor Runs But The Actuator Does Not Move The Valve - Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual

Electric actuator
Table of Contents

Advertisement

Section 12: Troubleshooting
October 2019
12.4

The Motor is Very Hot and does not Start

12.5
The Motor Runs but the Actuator does not
Move the Valve
If the valve position indicators do not change on the local display:
Figure 83
Figure 84
96
Check that no alarm other than motor overheating is present.
Wait until the motor cools down and the normally closed (NC) contact of the
thermal switch automatically resets before trying to operate the actuator again.
Check that the number of operations per hour and their duration is suitable for the
actuator service (refer to the nameplate menu).
Check that the valve operating torque is within the range of the unit's designed
operating torque.
Always check for causes of abnormal operation.
Check that the manual de-clutch lever is not stuck in the manual operation position.
Rotate the handwheel a few degrees to remove any possible sticking between the
handwheel and the drive sleeve.
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
Troubleshooting