16. Priority of settings

The system can always be set with Grundfos GO Remote to
operate at maximum speed or to stop.
If two or more functions are enabled at the same time, the system
will operate according to the function with the highest priority.
Example: If the system has been set to maximum speed via the
digital input, the pump control panel or Grundfos GO Remote can
only set the system to "Manual" or "Stop".
The priority of the settings is listed in the table below:
Priority
Start/stop button
1
2
3
4
5
6
7
8
9
10
11
12
13
14
* If the bus communication is interrupted, the system will resume its previous operating mode, for example "Stop", selected on the
control panel of the pump running as master or with Grundfos GO Remote.
Control panel on pump or
Grundfos GO Remote
Stop
Stop*
Manual
Max. speed*
Min. speed
Start
Digital input
Bus communication
Stop
Stop
Max. speed
Min. speed
Start
Max. speed
Min. speed
Start