12.9 Proportional pressure

It is possible to control the system in proportional pressure
control, see section
12.3 Control
system automatically adjusts the setpoint to the actual flow rate to
compensate for flow-dependent dynamic losses. This will also
gain considerable energy savings and increase the comfort for
the users.
To use this function, the system calculates the flow based on the
head of the system (outlet-inlet pressure).
The outlet pressure is always known as the system is always
fitted with an outlet pressure sensor. The inlet sensor depends on
the system design. If not present, it can be retrofitted, see section
15.1.3 Inlet pressure
sensor.
If there is no inlet pressure available or if it is very constant, it is
also possible to set a fixed inlet pressure.
Set the flow calculation
Connect Grundfos GO to each pump in the system (one at the
time) then select "Setting the proportional pressure" in the
settings.
Type in the pump data if not already done by factory (it can be
read on the pump nameplate).
rated flow (Q)
rated head (H)
maximum head (H
).
max
The individual pump will now calculate its own flow, and the
system will sum up the system flow.
Set the proportional pressure control
Connect to one of the master pumps with Grundfos GO Remote
or via the HMI 300 control interface to set the proportional
pressure control:
Set the System setpoint which will be the maximum pressure
setpoint.
Go to "Settings" and select "Setting the proportional pressure":
Choose the control curve function ("Linear" or "Quadratic"),
see fig. 37.
Set the zero flow head (the minimum setpoint in the system).
Set the Q
(the flow point where the system reaches the
max
maximum setpoint)
Activate or deactivate the "Fixed inlet pressure" (depending on
inlet pressure measurement)
Type in the fixed inlet pressure (if activated).
H
C
B
A
Fig. 37 Proportional pressure
A: The zero head
B: Q
in cascade
max
C: The maximum pressure (standard setpoint).
Pump in constant-curve control mode
In constant-curve control mode, the pump performance will
operate between the maximum and minimum curve of the pump.
See fig. 38.
22
mode. With this function, the
Q
Max.
Min.
Fig. 38 Pump in constant-curve control mode

12.10 "Pump changeover"

The function ensures that the pumps run for the same number of
operating hours. In certain applications, the requirement remains
constant for long periods and does not require all pumps to run.
In such situations, pump changeover does not take place
naturally, thus forced pump changeover may be required. Once
every 24 hours, the system will force a changeover to the pump
with the lowest operating hours. The interval can be set from 1 to
25 hours and the timer starts when the system is powered on.

12.11 "Undo"

This menu is only available in Grundfos GO Remote.
This display allows you to undo all settings that have been made
with Grundfos GO Remote in the current session. Once you undo
any setting, you cannot revert to them.

12.12 "Pump name"

This display allows you to name a system which makes it easy to
identify it when connecting to Grundfos GO Remote.

12.13 "Unit configuration"

This menu allows you to choose between SI and US units. You
can set either unit system as the default for the entire system, or
select the preferred unit for each parameter.
Factory setting
See section
29. Factory
settings.