13.6 "Analog output"
The analog output enables the reading of certain operating data
to external control systems.
To set the analog output, make the settings below.
Output signal
•
"0-10 V"
•
"0-20 mA"
•
"4-20 mA".
Function of analog output
•
"Actual speed"
Signal range
[V, mA]
0
"0-10 V"
0 V
"0-20 mA"
0 mA
"4-20 mA"
4 mA
The reading is a percentage of the rated speed.
•
"Actual value"
Signal range
[V, mA]
Sensor
"0-10 V"
"0-20 mA"
"4-20 mA"
The reading is a percentage of the range between the minimum
and maximum value.
•
"Resulting setpoint"
Signal range
[V, mA]
"0-10 V"
"0-20 mA"
"4-20 mA"
The reading is a percentage of the external setpoint range.
•
"Motor load"
Signal range
[V, mA]
"0-10 V"
"0-20 mA"
"4-20 mA"
The reading is a percentage of the range between 0 and 200 % of
the maximum permissible load at the actual speed.
•
"Motor current"
Signal range
[V, mA]
0
"0-10 V"
0 V
"0-20 mA"
0 mA
"4-20 mA"
4 mA
The reading is a percentage of the range between 0 and 200 % of
the rated current.
26
"Actual speed"
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
"Actual value"
Sensor
min
max
0 V
10 V
0 mA
20 mA
4 mA
20 mA
"Resulting setpoint"
[%]
0
100
0 V
10 V
0 mA
20 mA
4 mA
20 mA
"Motor load"
[%]
0
100
0 V
10 V
0 mA
20 mA
4 mA
20 mA
"Motor current"
[%]
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA
•
"Limit 1 exceeded" and "Limit 2 exceeded"
Signal range
Output not
[V, mA]
"0-10 V"
"0-20 mA"
"4-20 mA"
This function is typically used for monitoring secondary
parameters in the system. If the limit is exceeded, an output, a
warning, or an alarm is activated.
•
"Flow rate"
Signal range
[V, mA]
"0-10 V"
0 V
"0-20 mA"
0 mA
"4-20 mA"
4 mA
The reading is a percentage of the range between 0 and 200 % of
the nominal flow.
Factory setting
See section
29. Factory
settings.
"Limit-exceeded function"
Output active
active
0 V
10 V
0 mA
20 mA
4 mA
20 mA
"Flow rate"
[%]
0
100
200
5 V
10 V
10 mA
20 mA
12 mA
20 mA