Priority Of Settings - Grundfos MAGNA3 50-40 F N Installation And Operating Instructions Manual

Hide thumbs Also See for MAGNA3 50-40 F N:
Table of Contents

Advertisement

4.6 Priority of settings

The external forced-control signals will influence the settings
available on the pump control panel or with the Grundfos GO
Remote. However, the pump can always be set to max. curve
duty or to stop on the pump control panel or with the
Grundfos GO Remote.
If two or more functions are enabled at the same time, the pump
will operate according to the setting with the highest priority.
The priority of the settings is as shown in the table below.
Example: If the pump has been forced to stop via an external
signal, the pump control panel or the Grundfos GO Remote can
only set the pump to max. curve.
Pump control
Priority
panel or
Grundfos GO
Remote
1
Stop
2
Max. curve
3
4
5
6
7
8
9
Min. curve
10
11
Start
As illustrated in the table, the pump does not react to external
signals (max. curve and min. curve) when it is controlled via bus.
For further details, please contact Grundfos.
Possible settings
External
Bus signal
signals
Stop
Stop
Max. curve
Min. curve
Start
Max. curve
Min. curve
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Magna3 65-40 f nMagna3 80-40 f nMagna3 100-40 f nMagna3 50-60 f nMagna3 65-60 f nMagna3 80-60 f n ... Show all

Table of Contents