10.1 HMI200

The HMI200 is standard control interface on non-system control
motors (slave motors).
Fig. 22 HMI200
Pos.
Symbol
Description
Grundfos Eye
Shows the operating status of individuals
1
pump.
See section
information.
2
-
Light fields for indication of setpoint.
Changes the setpoint and resets alarms
3
and warnings.
Enables radio communication with
4
Grundfos GO Remote and other products
of the same type.
Makes the pump ready for operation or
starts and stops the pump.
Start:
If the button is pressed when the pump is
stopped, the pump will only start if no
other functions with higher priority have
been enabled. See section
5
settings.
Stop:
If the button is pressed when the pump is
running, the pump will always be stopped.
When the pump is stopped by this button,
the "Stop" text next to the button will
illuminate.
14
1
2
3
4
Stop
5
17. Grundfos Eye
for further
16. Priority of
10.1.1 Setpoint setting
Set the desired setpoint by pressing
be set on any of the pumps in the system and applies to the
complete pump system.
The light fields on the control panel will indicate the specified
setpoint.
Pump in constant-pressure control mode
Hydro Multi-E systems are set up from factory as pressure
boosting systems, but can be set up to other control modes. See
CRE installation and operating instructions. The following
example applies to a pump in an application where a pressure
sensor gives a feedback to the pump. If the sensor is retrofitted to
the pump, it must be set manually as the pump does not
automatically register a connected sensor.
Figure
23
shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 43.5 psi (3 bar) with a sensor
measuring range from 0 to 87.0 psi (0 to 6 bar). The setting range
is equal to the sensor measuring range.
bar
6
3
0
Fig. 23 Setpoint set to 43.5 psi (3 bar), constant-pressure
control mode
H
Fig. 24 Constant pressure curve
Setting to maximum curve:
Press
continuously to change over to the maximum curve
of the pump (top light field flashes). When the top light field is
on, press and hold for
for 3 seconds until the light field
starts flashing.
To change back, press
continuously until the desired
setpoint is indicated.
or
. The setpoint can
Q

Advertisement