Messages and diagnostics
7.3 Structure of the slave diagnostics
Error type
Channel
error type
F7
0x1021
F4
0x1022
0x1046
2)
F4
0x1024
0x1046
2)
F1
0x1025
0x1046
2)
F6
0x1026
0x1046
2)
F7
0x1027
F16
0x1033
F7
0x1040
F8
0x1041
F7
0x1042
F8
0x1043
F24
0x1046
F24
0x1057
0x1046
2)
F9
0x1080
F9
0x1081
0x1046
2)
F9
0x1082
0x1046
2)
F5
0x1083
0x1046
2)
F17
0x1084
0x1046
2)
94
Error
Asymmetry
Therm. motor model
overload
Temperature sensor
overload
Temperature sensor short
circuit
Temperature sensor wire
break
Ground fault
No start-up data received
Threshold I exceeded
Threshold I undershot
Threshold P exceeded
Threshold P undershot
Actuator disconnection
Number of starting
operations exceeded
Device error
Bypass defective
Power semiconductor
defective
Switching element overload
Electronics supply voltage
too low
Cause
A limit value for asymmetry has been exceeded.
Asymmetry can cause an overload.
Loss of phase.
Fault in the motor windings.
The motor feeder has been overloaded.
The motor temperature rise has exceeded a
limit.
The temperature of the motor is too high.
A short circuit has occurred in the temperature
sensor cable.
A wire has broken in the sensor cable of the
temperature sensor.
The ground-fault monitoring has responded. An
impermissibly high residual current is flowing.
Data necessary for device start-up are missing.
The current has exceeded a limit.
The current has undershot a limit.
The active power of the motor has exceeded a
limit value.
The active power of the motor has undershot a
limit value.
The module has disconnected the actuator. An
additional diagnostic message will be displayed to
provide you with more detailed information about
the cause.
The permissible number of starting operations in
the monitoring period has been exceeded.
Irrecoverable error detected following
self-diagnostics (self-test, contactor contacts,
switching element, etc.).
Bypass defective
The error can also be generated by
successive, brief interruptions of the control
supply voltage.
Power semiconductor defective
The fault is also generated if the defective
switching element (bypass or power
semiconductor) cannot be accurately
identified.
Switching element (switching contact, power
semiconductor) too hot.
The supply voltage is below the permissible
value.
SIRIUS 3RW5 PROFIBUS communication module
Equipment Manual, 02/2020, A5E35633549002A/RS-AC/003
Byte.Bit
1)
14.0
12.3
12.0
12.2
12.1
16.0
18.4
14.2
14.3
83.4
83.5
12.4
3)
14.1
3)
14.4
3)
83.6
3)
71.1
19.2
29.3
10.4
29.5
29.6
29.7
10.3
16.7