Configuring
6.1 Configuring the 3RW5 Soft Starter in the PROFIBUS DP system
Procedure
1. Configure the 3RW5 soft starter in the PROFIBUS DP system.
The following procedures are possible, for example:
– Configuring 3RW5 soft starters without help from a 3RW5 HMI (Page 61)
– Configuring 3RW5 soft starters with the aid of a 3RW5 HMI (Page 63)
Note the information in chapter Configuring the 3RW5 Soft Starter (Page 61).
2. Parameterize the 3RW5 soft starter. In particular, note the information in chapter
Operation on failure of the bus connection to the controller (Page 70). You will find more
information on parameterization in the Equipment Manual of the 3RW5 soft starter.
Depending on the selection and equipment of the 3RW5 soft starter, you can
parameterize the 3RW5 soft starter in different ways via the
3RW5 communication module:
– SIRIUS Soft Starter ES (TIA Portal) Premium / Professional on PC with
– Configuration software of the controller on PC or programming device with
– User program via data sets (Page 125)
Note
During parameterization of the 3RW5 soft starter, it is possible to select impossible
combinations of interdependent values. The diagnosis "Invalid parameter value" is then
indicated in data set 92 of the 3RW5 soft starter (slot 2) (Page 135). You will find the
dependencies of the parameters in the Equipment Manual of the 3RW5 soft starter.
Result
The 3RW5 soft starter is linked into the PROFIBUS DP system as a DP slave and
parameterized. You can program the controller and commission the 3RW5 soft starter in the
PROFIBUS DP system.
60
PROFIBUS DP connection
PROFIBUS DP connection
Note
With the GSD file, you can set only values for parameter set 1 (PS 1) and parameters
(e.g. input action) that are independent of the parameter set. For PS 2 and PS 3, the
default values are used.
SIRIUS 3RW5 PROFIBUS communication module
Equipment Manual, 02/2020, A5E35633549002A/RS-AC/003