Description
3.5 Operating modes and master control function
Parameter
Parameter
Control via digital input
Additional information
For more information, see Chapter Operating modes (Page 26).
Further information on the 3RW5 soft starters can be found in the Equipment Manual of the
respective 3RW5 soft starter.
36
Description
Manual activation
On failure of the bus connection or a CPU stop the 3RW5 soft starter remains in
the "Automatic" mode or the 3RW5 soft starter switches to the "Automatic" mode.
Permanent activation
A switch to the "Automatic" mode and operating mode "manual - bus" is not
possible. If the 3RW5 soft starter is in the "Automatic" or "manual - bus" mode,
the 3RW5 soft starter switches to the "Manual operation local - input controlled"
mode. Control by means of a higher-level control (e.g. PLC) is not possible.
Activate on bus error (factory setting)
On failure of the bus connection or a CPU stop, the 3RW5 soft starter switches
from the "Automatic" mode to the "Manual operation local - input controlled" mode
or the 3RW5 soft starter remains in the operating mode "manual - local" mode.
No change on bus error
On failure of the bus connection or a CPU stop the master control function does
not switch, but the 3RW5 soft starter remains in the current mode.
SIRIUS 3RW5 PROFIBUS communication module
Equipment Manual, 02/2020, A5E35633549002A/RS-AC/003