3.1
P
ower connections
RECOMMENDED WIRE GAUGES
Table 6
CURRENT LEVEL
GTF
25A
40A
50A
60A
75A
90A
120A
-
150A
200A
250A
-
Note:
Cables must be copper "Stranded Wire" or "Compact-Stranded Wire" type with maximum operating temperature 60/75°
80960G_MHW_GTF_05-2019_ENG
3 • ELECTRICAL CONNECTIONS
TERMINAL
CABLE WIRE
4 mm²
1/L1, 2/T1, PE
10 AWG
10 mm²
1/L1, 2/T1, PE
7 AWG
10 mm²
1/L1, 2/T1, PE
7 AWG
16 mm²
1/L1, 2/T1, PE
5 AWG
25 mm²
1/L1, 2/T1, PE
3 AWG
35 mm²
1/L1, 2/T1, PE
2 AWG
50 mm²
1/L1, 2/T1, PE
1/0 AWG
0.25 ...2.5 mm²
3/L2 (Ref. Vline)
23...14 AWG
70 mm
1/L1, 2/T1
2/0 AWG
95 mm
1/L1, 2/T1
4/0 AWG
120 mm
1/L1, 2/T1
250 AWG
0.25 ...2.5 mm
3/L2 (Ref. Vline)
23...14 AWG
WIRE TERMINAL
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
Wire terminal / Eye
D. 6mm
wire terminal tip
Wire stripped for 25 mm or
²
with crimped pre-insulated
terminal tube CEMBRE
PKC70022
Wire stripped for 25 mm or
²
with crimped pre-insulated
terminal tube CEMBRE
PKC95025
²
Wire stripped for 25 mm
²
Wire stripped for 8 mm
or with tag terminal
TIGHTENING TORQUE /
TOOL
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
2.5 Nm / Phillips screwdriver
PH2 - PH3
0.5 ...0.6 Nm / Screwdriver blade
0.6 x 3.5 mm
6 Nm / No. 6 hex head wrench
6 Nm / No. 6 hex head wrench
6 Nm / No. 6 hex head wrench
0.5 ...0.6 Nm / Flat-head screwdriver
tip 0,6 x 3.5 mm