Figure 3-2. Schematic Illustration of the Rosemount 5600 Transmitter Connection
Primary Out
Non-IS
3.3

Cables

Depending on local requirements, cable glands, or explosion proof conduits must be used for
connection to the non-intrinsically safe junction box (EEx e). For the connection to the instrinsically safe
junction box (EEx i) use cable glands with integral shield connection for cable diameter 6-12 mm or
conduit.
Use shielded instrument cable 0.5 mm
min. 0.5 mm
3.4

Power supply

You can use either DC or AC as the built in power supply has a wide input range. The following
specification is valid for the power supply:
24-240 V
DC/AC 0-60 Hz
10 W
15 VA
There is no voltage selector in the electronics compartment since the transmitter power supply unit
automatically adapts to the available voltage within specified limits.
Electrical Installation
®
HART
interface
1
Junction
2
box X1
3
4
X1
7 8 9
4 5 6
1 2 3
2
cable for power supply.
Junction
Box X2
Optional EEx e
2
(AWG 20) for analog outputs and serial communication. Use
Electrical Installation
March 2020
Level
X2
Secondary
6.767
m
output
7
6
5
4
3
2
1
Primary
output IS
7 8 9
4 5 6
1 2 3
Secondary
X2
output
4
3
1 and 2 Not used
2
1
57