Reference Manual
00809-0100-4024, Rev CA
2. Make a small recess in the flange hole.
Figure 2-32. Recess Hole
0.24-1.18
3. Put the O-ring on the flange and insert the flange ball into the hole. Make sure the pin on the side of
the flange ball fits into the corresponding recess on the flange.
Figure 2-33. Put the O-ring on the Flange
4. Tighten the nut. Make sure the flange ball fits tightly to the flange.
5. Secure the nut by tightening the locking screw.
Figure 2-34. Secure the Nut
Mechanical Installation
(6-30)
Recess
R3
3.78
(96)
1.97
50
(50)
Flange ball
O-ring
Nut
Locking screw
Mechanical Installation
March 2020
41