Wiring Schematic - Danfoss VLT AQUA Drive FC 202 Operating Instructions Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Electrical Installation

4.4 Wiring Schematic

4
4
Figure 4.1 Basic Wiring Schematic
A=Analog, D=Digital
*Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the VLT
Converters - Safe Torque Off Operating Instructions.
**Do not connect cable screen.
NOTICE!
Actual configurations vary with unit types and optional equipment.
16
3-phase
91 (L1)
power
92 (L2)
input
93 (L3)
95
PE
DC bus
88 (-)
89 (+)
50 (+10 V OUT)
+10 V DC
S201
0/-10 V DC-
53 (A IN)
+10 V DC
0/4–20 mA
S202
0/-10 V DC-
54 (A IN)
+10 V DC
0/4–20 mA
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
19 (D IN)
(COM D IN)
20
(D IN/OUT)
27
(D IN/OUT)
29
32 (D IN)
33 (D IN)
*
37 (D IN)
Danfoss A/S © 01/2015 All rights reserved.
®
VLT
AQUA Drive FC 202
Switch Mode
Power Supply
10 V DC
24 V DC
15 mA
130/200 mA
+
-
+
-
ON=0/4–20 mA
OFF=0/-10 V DC -
+10 V DC
P 5-00
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
S801
24 V
0 V
24 V (NPN)
0 V (PNP)
24 V
0 V
RS-485
Interface
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
(U) 96
(V) 97
(W) 98
(PE) 99
Brake
(R+) 82
resistor
(R-) 81
relay1
03
240 V AC, 2 A
02
01
relay2
06
240 V AC, 2 A
05
400 V AC, 2 A
04
Analog Output
(COM A OUT) 39
0/4–20 mA
(A OUT) 42
ON=Terminated
OFF=Open
5 V
S801
0 V
(N RS-485) 69
(P RS-485) 68
**
(COM RS-485) 61
Motor
RS-485
: Chassis
: Ground
®
Frequency
MG20MC22

Advertisement

Table of Contents
loading

Table of Contents