Danfoss VLT AQUA Drive FC 202 Operating Instructions Manual page 69

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
Type designation
1)
High/normal overload
Typical shaft output at 550 V [kW]
Typical shaft output at 550 V [hp]
Typical shaft output at 690 V [kW]
Typical shaft output at 690 V [hp]
IP20/Chassis
IP21/Type 1
IP55/Type 12/Type 3R
Output current
Continuous (3x525–550 V) [A]
Intermittent (60 s overload) (3x525–550 V) [A]
Continuous (3x551–690 V) [A]
Intermittent (60 s overload) (3x551–690 V) [A]
Continuous kVA at 550 V [kVA]
Continuous kVA at 690 V [kVA]
Maximum input current
Continuous at 550 V [A]
Intermittent (60 s overload) at 550 V [A]
Continuous at 690 V [A]
Intermittent (60 s overload) at 690 V [A]
Additional specifications
Maximum cable cross-section for mains and
2
motor [mm
] ([AWG])
Maximum cable cross-section for brake and
2
load sharing [mm
] ([AWG])
2)
Maximum cable cross-section
for mains
2
disconnect [mm
] ([AWG])
3)
Estimated power loss
at rated maximum load [W]
4)
Efficiency
5)
Table 8.17 B4, C2, C3 Enclosure, Mains Supply 3x525–690 V AC IP20/IP21/IP55 – Chassis/NEMA1/NEMA 12, P30K–P75K
For fuse ratings see chapter 8.8 Fuses and Circuit Breakers.
1) High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2) The 3 values for the maximum cable cross-section are for single core, flexible wire and flexible wire with sleeve, respectively.
3) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598–2, refer to
www.danfoss.com/vltenergyefficiency.
4) Efficiency measured at nominal current. For energy efficiency class see chapter 8.4.1 Ambient Conditions. For part load losses see
www.danfoss.com/vltenergyefficiency.
5) Measured using 5 m screened motor cables at rated load and rated frequency.
6) Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit in the
design guide.
7) Enclosure sizes B3+B4 and C3+C4 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit
in the design guide.
8) Enclosure sizes for N75K, N90K are D3h for IP20/Chassis, and D5h for IP54/Type 12.
9) Two wires are required.
10) Variant not available in IP21.
11) Type 3R is not available in A4 enclosures.
MG20MC22
Operating Instructions
P37K
P45K
HO
NO
HO
NO
22
30
30
37
30
40
40
50
30
37
37
45
40
50
50
60
B4
C3
C2
C2
36.0
43.0
43.0
54.0
54.0
47.3
64.5
59.4
34.0
41.0
41.0
52.0
51.0
45.1
61.5
57.2
34.3
41.0
41.0
51.4
40.6
49.0
49.0
62.1
36.0
49.0
49.0
59.0
54.0
53.9
72.0
64.9
36.0
48.0
48.0
58.0
54.0
52.8
72.0
63.8
95 (3/0)
600
740
740
900
0.98
0.98
Danfoss A/S © 01/2015 All rights reserved.
8)
P55K
P75K/N75K
HO
NO
HO
NO
37
45
45
55
50
60
60
75
45
55
55
75
60
75
75
100
C3
D3h
C2
C2
54.0
65.0
65.0
87.0
81.0
71.5
97.5
95.7
52.0
62.0
62.0
83.0
78.0
68.2
93.0
91.3
51.4
61.9
61.9
82.9
62.1
74.1
74.1
99.2
59.0
71.0
71.0
87.0
87.0
78.1
105.0
95.7
58.0
70.0
70.0
86.0
87.0
77.0
105
94.6
150 (300 MCM)
95 (3/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
900
1100
1100
1500
0.98
0.98
8)
P90K/N90K
HO
NO
55
75
75
100
75
90
199
125
D3h
C2
87.0
105
130.5
115.5
83.0
100
124.5
110
82.9
100
99.2
119.5
87.0
99.0
8
8
129
108.9
1500
1800
0.98
67

Advertisement

Table of Contents
loading

Table of Contents