Specifications
525–600 V, Enclosure Sizes A, B, and C
Enclosure
A2
A3
A5
B1
B2
B3
B4
8
8
C1
C2
C3
C4
Table 8.21 525–600 V, Enclosure Sizes A, B, and C
76
Power [kW]
Recommended
fuse size
1.1–4.0
gG-10
5.5–7.5
gG-10 (5.5)
gG-16 (7.5)
1.1–7.5
gG-10 (0.75-5.5)
gG-16 (7.5)
11–18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
22–30
gG-50 (22)
gG-63 (30)
11–18.5
gG-25 (11)
gG-32 (15)
22–37
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
37–55
gG-63 (37)
gG-100 (45)
aR-160 (55)
75–90
aR-200 (75)
45–55
gG-63 (37)
gG-100 (45)
75–90
aR-160 (55)
aR-200 (75)
Danfoss A/S © 01/2015 All rights reserved.
®
VLT
AQUA Drive FC 202
Recommended
maximum fuse
gG-25
gG-32
gG-32
gG-80
gG-100
gG-63
gG-125
gG-160 (37-45)
aR-250 (55)
aR-250
gG-150
aR-250
Recommended circuit
Maximum trip level
breaker
Moeller
PKZM0-25
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
[A]
25
25
25
63
100
50
100
160
250
150
250
MG20MC22

Advertisement

Table of Contents
loading