Specifications
3x525–690 V, Enclosure Sizes B and C
Power
Maximum
[kW]
pre-fuse
11–15
22
30
37
45
55
75
90
Table 8.30 3x525–690 V, Enclosure Sizes B and C
8
8
82
Bussmann
Bussmann
E52273
E4273
[A]
RK1/JDDZ
J/JDDZ
30
KTS-R-30
JKS-30
45
KTS-R-45
JKS-45
60
KTS-R-60
JKS-60
80
KTS-R-80
JKS-80
90
KTS-R-90
JKS-90
100
KTS-R-100
JKS-100
125
KTS-R-125
JKS-125
150
KTS-R-150
JKS-150
Danfoss A/S © 01/2015 All rights reserved.
®
VLT
AQUA Drive FC 202
Recommended maximum fuse
Bussmann
SIBA
E4273
E180276
T/JDDZ
RK1/JDDZ
JJS-30
5017906-030
JJS-45
5014006-050
JJS-60
5014006-063
JJS-80
5014006-080
JJS-90
5014006-100
JJS-100
5014006-100
JJS-125
2028220-125
JJS-150
2028220-150
LittelFuse
Ferraz-
E81895
Shawmut
RK1/JDDZ
E163267/E2137
RK1/JDDZ
KLS-R-030
A6K-30-R
KLS-R-045
A6K-45-R
KLS-R-060
A6K-60-R
KLS-R-075
A6K-80-R
KLS-R-090
A6K-90-R
KLS-R-100
A6K-100-R
KLS-150
A6K-125-R
KLS-175
A6K-150-R
Ferraz-
Shawmut
E2137
J/HSJ
HST-30
HST-45
HST-60
HST-80
HST-90
HST-100
HST-125
HST-150
MG20MC22