Danfoss VLT AQUA Drive FC 202 Operating Instructions Manual page 73

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse inputs
Programmable pulse inputs
Terminal number pulse
Maximum frequency at terminal 29, 33
Maximum frequency at terminal 29, 33
Minimum frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
i
Pulse input accuracy (0.1–1 kHz)
Control card, 24 V DC output
Terminal number
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Relay 02 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
MG20MC22
Operating Instructions
1)
on 1-3 (NC), 1-2 (NO) (resistive load)
(inductive load @ cosφ 0.4)
1)
1)
on 1-2 (NO), 1-3 (NC) (resistive load)
1)
(inductive load)
1)
2) 3)
on 4-5 (NO) (resistive load)
on 4-5 (NO) (inductive load @ cosφ 0.4)
1)
1)
on 4-5 (NO) (resistive load)
1)
on 4-5 (NO) (inductive load)
1)
on 4-6 (NC) (resistive load)
on 4-6 (NC) (inductive load @ cosφ 0.4)
1)
Danfoss A/S © 01/2015 All rights reserved.
>10 V DC
>19 V DC
<14 V DC
28 V DC
approximately 4 kΩ
27, 29
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
maximum error 0.1% of full scale
12 bit
29, 33
110 kHz (push-pull driven)
5 kHz (open collector)
4 Hz
see Digital inputs
28 V DC
approx. 4 kΩ
maximum error 0.1% of full scale
12, 13
200 mA
1-3 (break), 1-2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
60 V DC, 1 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
80 V DC, 2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
2
1)
8
8
2
2
71