COMMISSIONING AND MAINTENANCE
3.3

Error List

When a display has a technical fault, a numeric error code ap-
pears that will enable the maintenance operator to identify the
possible cause.
There are 3 categories of errors:
1
Permanent: errors that require a manual reset
2
Temporary: errors that are automatically reset once the
cause that generated them is removed or stopped
3
Notices: simple warnings that do not block the appliance's
operation
3.3.1

Permanent Errors

Nr.
Error
E2PROM_READ_ER-
0
ROR
1
IGNIT_ERROR
2
GV_RELAY_ERROR
SAFETY_RELAY_ER-
3
ROR
BLOCKING_TOO_
4
LONG
FAN_ERROR_NOT_
5
RUNNING
FAN_ERROR_TOO_
6
SLOW
FAN_ERROR_TOO_
7
FAST
8
RAM_ERROR
WRONG_EEPROM_
9
SIGNATURE
10
E2PROM_ERROR
11
STATE_ERROR
12
ROM_ERROR
15
MAX_TEMP_ERROR
16
FLUE_GAS_ERROR
17
STACK_ERROR
18
INSTRUCTION_ERROR
19
ION_CHECK_FAILED
FLAME_OUT_TOO_
20
LATE
FLAME_BEFORE_IG-
21
NIT
CORRUPTED_ER-
23
ROR_NR
29
PSM_ERROR
30
REGISTER_ERROR
Description
Internal software error
Three unsuccessful ignition at-
tempts in a row
Failure detected in the GV relay
Failure detected in safety relay
Control had a blocking error for
more than 20 hours
Fan is not running for more than
60 seconds
Fan runs too slow for more than 60
seconds
Fan runs too fast for more than 60
seconds
Internal software error
Contents of Eeprom is not up to
date
Wrong safety parameters in Ee-
prom
Internal software error
Internal software error
The external overheat protection
is enabled or the T_Supply sensor
measures a temperature of over
100°C (212°F)
Flue temperature exceeded the
maximum flue temperature
Internal software error
Internal software error
Internal software error
Flame still present 10 seconds after
closing the gas valve
Flame is detected before ignition
Error code RAM byte was corrupted
to an unknown error code
Internal software error
Internal software error
3.3.2

Temporary Errors

Nr.
Error
100
WD_ERROR_RAM
101
WD_ERROR_ROM
102
WD_ERROR_STACK
WD_ERROR_REG-
103
ISTER
REFHI_TOO_HIGH /
106
REFHI_TOO_LOW
REFHI_TOO_HIGH /
107
REFHI_TOO_LOW
REFHI_TOO_HIGH /
108
REFHI_TOO_LOW
REFHI_TOO_HIGH /
109
REFHI_TOO_LOW
REFHI_TOO_HIGH /
110
REFHI_TOO_LOW
REFHI_TOO_HIGH /
111
REFHI_TOO_LOW
REFHI_TOO_HIGH /
112
REFHI_TOO_LOW
REFHI_TOO_HIGH /
113
REFHI_TOO_LOW
114
FALSE_FLAME
LOW_WATER_PRES-
115
SURE_ERROR
118
WD_COMM_ERROR
119
RETURN_OPEN
120
SUPPLY_OPEN
122
DHW_OPEN
123
FLUE_OPEN
126
RETURN_SHORTED
127
SUPPLY_SHORTED
129
DHW_SHORTED
130
FLUE_SHORTED
133
Net Freq Error
RESET_BUTTON_ER-
134
ROR
163
T_SELECTION1_OPEN Heat exchanger's flow rate too low
3.3.3

Warnings

Nr.
Error
CC_LOSS_COMMUNI-
200
CATION
CC_LOSS_COMMUNI-
201
CATION
202
OUTDOOR_WRONG
203
T_SYSTEM_WRONG
204
T_CASCADE_WRONG
76
Description
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Internal software error
Flame is detected in a state in
which no flame is allowed to be
seen.
Low water pressure error
Watchdog communication error
Return sensor open
Supply sensor open
DHW sensor open
Flue sensor open
Return sensor shorted
Supply sensor shorted
DHW sensor shorted
Flue sensor shorted
Net. freq. error detected by the
watchdog
Too many resets in a short time
period
Description
Cascade system: the burner of the
managing module has lost the
signal of one of the depending
thermal module burner
Cascade system: the managing
module has lost the signal of one
of the depending thermal module
Outdoor sensor is open of shorted
T_System sensor is open of short-
ed
T_Cascade sensor is open of
shorted