Parameters Specific To Cascade Systems - Riello Steel Pro Power 114-2 P Installation, Technical Assistance Service And System Management Manual

Table of Contents

Advertisement

CASCADE CONNECTION
4.7

Parameters specific to cascade systems

Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Nr. dis-
Par.
Menu
played
No.
Display
Permit
Managing and the primary circuit's probe is
M2
72
Emergency
lost. In this event, if Par. 72 is set to "Yes", the
Mode
cascade is initiated, working to the fixed set-
Emergency
M2
74
Set-point
Delay
Per Start
M2
75
Next
Mod.
Delay Per
M2
76
Stop Next
Mod.
Delay
Defines the stand-by time in seconds to re-
Quick
M2
142
start the next cascade module in quick start
Start
Next
Delay
M2
143
Quick
Stop Next
Defines by how many degrees the tempera-
Hyst.
ture measured by the primary circuit's probe
Down
M2
77
must fall below the set-point in order for the
Start
subsequent module to be started after the
Module
Defines by how many degrees the tempera-
Hyst.
ture measured by the primary circuit's probe
M2
78
Up Stop
must go above the set-point in order for the
Module
subsequent module to be switched off after
Defines by how many degrees the tempera-
Hyst.
ture measured by the primary circuit's probe
Down
M2
144
Quick
the subsequent module to be started after
Start
the time interval set by Par. 142 (quick-start
Defines by how many degrees the tempera-
ture measured by the primary circuit's probe
Hyst. Up
must go above the set-point in order for the
M2
145
Quick
subsequent module to be switched off after
Stop
Defines by how many degrees the tempera-
ture measured by the primary circuit's probe
Hyst. Up
M2
146
must go above the set-point in order for all
Stop All
"On" modules to be switched off at the same
Number
Defines the number of modules of which the
M2
147
of Units
Description
Activates the emergency mode. This mode
comes on when communication between
point determined by Par. 74.
Set-point active in emergency mode.
Defines the stand-by time in seconds to
restart the subsequent cascade module in
normal start mode.
Defines the stand-by time in seconds to
switch off the last cascade module on in
normal Off mode.
mode.
Defines the stand-by time in seconds to
switch off the last cascade module on in
Quick Stop mode.
time interval set by Par. 75.
the time interval set by Par. 76.
must go below the set-point in order for
mode).
the time interval set by Par. 143 (quick stop
mode).
time.
cascade consists.
Access type
U
End user
I
Installer
O
Manufacturer
Range
Yes/No
20...65
5...255
5...255
5...255
5...255
0...40
0...40
0...40
0...40
0...40
1...16
90
Factory
Access
UM
setting
type
Yes
U
70
°C
I
120
Sec.
I
30
Sec.
I
60
Sec.
I
15
Sec.
I
5
°C
I
4
°C
I
20
°C
I
6
°C
I
8
°C
I
8
I
Category
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade
Cascade