EEPROM CONTROL
The burner controller automatically checks for errors in the mi-
crocontroller EEPROM and enters lockout if an error is detect-
ed. An error is indicated by the LED flashing (see the "Fault diag-
nosis - lockouts" section on page 49).
3.4

Error List

When a technical anomaly occurs, the control interface display
shows a text message (small digit) and a number (large digit),
which indicate the type and level of the detected error.
There are 3 error levels:
1
Permanent: heating and/or DHW requests are suspended
and burner and circulator are switched off. For the error to
disappear, keep the key ENTER/RESET on the control inter-
face pressed for 3 seconds or reset the power supply by
using the main switch.
2
Temporary: heating and/or DHW requests are suspend-
ed and burner and circulator are switched off. The error
disappears automatically when the cause which generated
it is solved.
3
Alert: the thermal unit is not locked out, but its functions
may be limited according to the signalled alert code.
The log of the last ten errors occurred can be viewed through
the error log (menu 9000 - installer level) (from Par. 9001 to Par.
9010).
3.4.1

Permanent Errors

Message
Error No.
Description
Loc
E010
Ignition failure
Loc
E020
Safety thermostat tripped
Low water pressure - Load the
Loc
E040
system
Pressure transducer not connected
Loc
E042
or read value outside of the permit-
ted range
3.4.2

Temporary Errors

Message
Error No.
Err
E046
Err
E060
Err
E070
Err
E080
Err
E099
Err
E100
Err
E101
Err
E102
Err
E104
Err
E105
Err
E106
Err
E108
Err
E109
Err
E110
3.4.3

Warnings

Message
Error No.
Atte
E041
Air
E043
Atte
E044
53
COMMISSIONING AND MAINTENANCE
Description
Pressure decreasing alarm (<0.8)
(temporary)
Domestic hot water probe in short
circuit or disconnected.
Delivery probe in short circuit or
disconnected. Delivery probe fault /
delivery probe overtemperature
Return probe fault / return probe
overtemperature
Too many resets from remote con-
trol. NO MORE RESETS
Communication lost in zone 1 (tem-
porary)
Zone 1 limit thermostat triggering
(temporary)
Zone 1 delivery probe (temporary)
Communication lost in zone 2 (tem-
porary)
Zone 2 limit thermostat triggering
(temporary)
Zone 2 delivery probe (temporary)
Communication lost in zone 3 (tem-
porary)
Zone 3 limit thermostat triggering
(temporary)
Zone 3 delivery probe (temporary)
Description
Primary circuit pressure insuffi-
cient (temporary)
Venting cycle in progress (tem-
porary)
Primary circuit pressure too high
(temporary)