Riello Steel Pro Power 114-2 P Installation, Technical Assistance Service And System Management Manual page 67

Table of Contents

Advertisement

The parameters regulating such temperature are:
Par.
Description
No.
Sets the desired flow temperature with heating mode.
3
Active for the heating mode Par. 1 = 0 o 3
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Delivery Temp.
(°C)
Par. 24
Par. 03
Par. 23
Mode 1
(Climatic functioning with room/heat demand thermostat, vari-
able set point according to the outdoor temperature)
In this case the thermal module operates with a variable set-
point depending on outdoor temperature based on a climatic
curve defined by the following parameters:
Par.
Description
No.
Defines the value of the set point calculated on climat-
109
ic mode (Par. 1 = 1).
Establishes the max. set-point at the minimum out-
19
door temperature for climatic regulation
Establishes the minimum outdoor temperature to
20
which the maximum set-point can be associated for
climatic regulation
Establishes the minimum set-point at the maximum
21
outdoor temperature for climatic regulation
Establishes the maximum minimum outdoor tempera-
22
ture to which the minimum set-point can be associat-
ed for climatic regulation
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Defines the temperature at which climatic regulation is
25
switched off
The demand is activated when the room/heat demand thermo-
Tset max (°C)
stat's contact is closed provided that outdoor temperature does
not exceed the value set by the parameter 25.
Setpoint
if the outdoor temperature is higher than the one set on param-
eter 25 , the burner is stopped even if there is a heat demand.
The climatic curve can also be adjusted in a simpler, more us-
Tset min (°C)
er-friendly way.
Enter the "CH" menu. The following display will appear:
Outdoor Temp. (°C)
Press the ● key to confirm and enter the climatic curve screen.
"Design Supply Temp." and "Design Outdoor Temp." will be dis-
played. To change their value, press the ● key.
1
2
3
Repeat steps 1 from 3 to make other changes.
After setting the parameters, press the ESC key to exit the menu.
9
67
COMMISSIONING AND MAINTENANCE
Delivery Temp.
(°C)
Par. 24
Par. 19
Par. 21
Par. 23
Par. 20
Central Heating (CH)
"
"
Outdoor reset
"
"
Outdoor reset
"
"
194
32
5
T Outside [°C]
"
"
Use the ▲ / ▼ keys to modify Design Supply Temp and the
◄ / ► keys to change Design Outdoor Temp.
Press ● to save changes
Use the ◄ / ► keys to select other values.
If the outdoor temperature sensor (accessory) is not detect-
ed (not installed or damaged) the system provides a warn-
ing: no. 202
The presence of the warning does not stop the thermal
module allowing a heat request to be carried out at the
maximum setpoint set on the climatic regulation.
Tset max (°C)
Par. 109
Tset min (°C)
Par. 22
Par. 25
Outdoor Temp. (°C)
Des. Supply T.
82.0
°C
"
"
"
"
Bas. Supply T.
40.0
°C
"
"
"
"
WW Shutdown
21.0
°C
"
"
"
"
Bas. Outd. T.
21.0
°C
95
"
"
"
"
Des. Outd. T.
-4.0
°C
"
"
"
"

Hide quick links:

Advertisement