Nr. dis-
Par.
Menu
played
No.
Display
Prog
M1
118
The value of this parameter is defined by Par. 97.
Input 3.
Prog
M1
120
The value of this parameter is defined by Par. 97.
Input 5.
Prog
M1
121
The value of this parameter is defined by Par. 97.
Input 6.
Prog
M1
122
The value of this parameter is defined by Par. 97.
Input 7.
Prog
M1
123
The value of this parameter is defined by Par. 97.
Input 8.
Prog.
M1
124
Input
The value of this parameter is defined by Par. 97.
RT.
Prog.
M1
125
The value of this parameter is defined by Par. 97.
Output 1.
Prog.
M1
126
Output
The value of this parameter is defined by Par. 97.
2.
Prog.
M1
127
Output
The value of this parameter is defined by Par. 97.
3.
Prog.
M1
128
Output
The value of this parameter is defined by Par. 97.
4.
Description
61
Default

Range

setting
0 Disabled 1
Drain switch 2
Defined
Gas pressure
by Par. 97
switch
0 Disabled 1
Defined
T_Return sensor
by Par. 97
2 Extern switch
0 Disabled 1
T_Flue sensor 2
Defined
Flue switch 3 APS
by Par. 97
switch
0 Disabled 1
T_Flue_2 sensor
2 T_Flue_2 + Bl.
Defined
Flue 3 T_System
by Par. 97
sensor 4 Blocked
Flue switch 5
Cascade Sensor
0 Disabled 1
T_DCW sensor 2
Defined
Water pressure
by Par. 97
switch
0 Disabled 1
Defined
Enabled
by Par. 97
0 Disabled 1
General Pump 2
CH Pump 3 DHW
Pump 4 System
Pump 5 Cascade
Pump 6 Alarm
Relay 7 Filling
Defined
Valve 8 LPG Tank
by Par. 97
9 External Igniter
10 Air Damper 14
Alarm Burner CC
15 Status Burner
CC 17 Antile-
gionella pump
0 Disabled 1
General Pump 2
CH Pump 3 DHW
Pump 4 System
Pump 5 Cascade
Pump 6 Alarm
Relay 7 Filling
Defined
Valve 8 LPG Tank
by Par. 97
9 External Igniter
10 Air Damper 14
Alarm Burner CC
15 Status Burner
CC 17 Antile-
gionella pump
0 Disabled 1
General Pump
10 Air Damper 11
Defined
External Igniter
by Par. 97
12 Modulating
Pump
0 Disabled 1
General Pump 2
CH Pump 3 DHW
Pump 4 System
Defined
Pump 5 Cascade
by Par. 97
Pump 6 Alarm
Relay 7 Filling
Valve 8 LPG Tank
INSTALLATION
Access
Catego-
UM
type
ry
I
General
I
General
I
General
I
General
I
General
I
General
I
General
I
General
I
General
I
General