4.
Please log in as an Administrator. For the Administrator password, please contact Delta
service personnel. After login, ensure that you are in the Administrator login
5.
Click SETUP → Mode Setting → On-Line.
6.
Single Input: Switch OFF the bypass breaker, input breaker and output breaker.
Dual Input: Switch OFF the bypass breaker, input breaker and output breaker.
7.
The UPS will discharge DC bus voltage, and the tri-color LED indicator will illuminate yellow.
After discharging is completed, the UPS will shut down, and the touch panel and the tri-color
LED indicator will be off.
8.
Switch OFF every external battery cabinet's breaker.
6.3.6 Frequency Conversion Mode Turn-off Procedures
WARNING:
1.
For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
2.
For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact Delta service personnel.
Ultron HPH Series
(Figure 6-36: Select On-Line Mode)
73
status.