Delta Amplon RT Series User Manual

Delta Amplon RT Series User Manual

Hide thumbs Also See for Amplon RT Series:

Advertisement

The power behind competitiveness
Delta UPS - Amplon Family
RT Series, Single Phase
1/ 2/ 3 kVA
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta Amplon RT Series

  • Page 1 The power behind competitiveness Delta UPS - Amplon Family RT Series, Single Phase 1/ 2/ 3 kVA User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2015 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    2.5.5 Flow Chart of the 7-Segment Display -----------------------------23 Rear Panel -------------------------------------------------------25 Chapter 3 : Installation ----------------------------------------------------31 Installation Data -------------------------------------------------31 Rack Mounting Procedures for the UPS and the Delta External Battery Pack (Optional) ---------------------------32 Tower Mounting Procedures for the UPS and the Delta External Battery Pack (Optional) ---------------------------34...
  • Page 4 Chapter 8 : Internal Battery Replacement --------------------------52 Chapter 9 : Optional Accessories -------------------------------------56 Chapter 10 : Maintenance ------------------------------------------------57 10.1 UPS ----------------------------------------------------------------57 10.2 Batteries ----------------------------------------------------------57 10.3 Fan -----------------------------------------------------------------58 Chapter 11 : Troubleshooting -------------------------------------------59 Appendi 1 : Technical Speci cations-------------------------------62 Appendix 2 : Warranty ----------------------------------------------------65 Amplon RT Series...
  • Page 5: Chapter 1 : Important Safety Instructions

    3. The UPS is available in 1kVA, 2 kVA and 3 kVA. Each kVA model has internal batteries and each model can connect the Delta external battery pack (optional). The nominal rating voltage of internal batteries is 24V, 48V and 72V for 1kVA, 2 kVA and 3 kVA respectively.
  • Page 6 Keep the UPS upright at all times and handle it with care. Do not stack the units. Do not place any objects on the UPS, the Delta external battery pack (optional) or any other accessory associated with the UPS. Install the UPS and the Delta external battery pack (optional) on a level and even surface.
  • Page 7 Chapter 1 Important Safety Instructions 4. Maintenance service must be performed by qualified service personnel. panels to be opened and/or removed. charges or unsafe electrical conditions. 6. Do not use extension cords to connect the UPS to an AC outlet. 7.
  • Page 8 UPS needs to be stored for an extended period of time. Whenever you recharge the batteries (internal and external), please fully charge them until the Battery Level Bar Graph shown on the UPS’s LCD is fully on. Amplon RT Series...
  • Page 9 2. For proper disposal of the UPS and batteries, contact your local recycling/ reuse or hazardous waste center. WARNING: events occur: 1. Liquid is poured or splashed on the UPS or the Delta external battery pack (optional). 2. The UPS does not run normally after this User Manual is carefully observed.
  • Page 10 This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions manual, may cause harmful interference to Amplon RT Series...
  • Page 11: Standard Compliance

    Chapter 1 Important Safety Instructions radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his/ her own expense. 1.2 Standard Compliance CB Report (by TUV) EN 62040-1 EMC EN62040-2 C1...
  • Page 12: Chapter 2 : Introduction

    It supports personal computers, networks, servers, telecommunica- tion equipment and a variety of other facilities. Each model has internal batteries and can connect to the Delta external battery pack (optional). The unit provides output power factor up to 0.9, produces greater smoothly at all times.
  • Page 13 Chapter 2 Introduction For Models: 1 kVA : UPS102R2RT0B035/ UPS102R2RT0B1B1/ UPS102R2RT0B0B6 2 kVA : UPS202R2RT0B035/ UPS202R2RT0B1B1/ UPS202R2RT0B0B6 3 kVA : UPS302R2RT0B035/ UPS302R2RT0B1B1/ UPS302R2RT0B0B6 × × × × × No. Item Q’ty 1 kVA 2/ 3 kVA 1 PC Rail Kit 1 Set USB Cable 1 PC...
  • Page 14 2/ 3 kVA 1 PC Rail Kit 1 Set Bracket Ear 1 Set Input Cable 10A 1 PC Input Cable 16A 1 PC Software CD-UPSentry 2012 1 PC User’s Manual CD 1 PC Quick Guide 1 PC Amplon RT Series...
  • Page 15 Chapter 2 Introduction For Models: 1 kVA : UPS102R2RT0B0B2 2 kVA : UPS202R2RT0B0B2 3 kVA : UPS302R2RT0B0B2 × × × × × No. Item Q’ty 1 kVA 2/ 3 kVA 1 PC Rail Kit 1 Set Bracket Ear 1 Set Input Cable 10A 1 PC Input Cable 16A...
  • Page 16: Functions & Features

    Input circuit breaker protection Generator compatible Hot swappable internal batteries Hot swappable Delta external battery pack (optional) Battery deep discharging protection Intelligent monitoring software connectivity through RS-232 port or USB port Provides the following functions via configuration of UPSentry 2012 software...
  • Page 17: Exterior & Dimensions

    Chapter 2 Introduction 2.4 Exterior & Dimensions 89mm 89mm...
  • Page 18: Operation Panel

    89mm 2.5 Operation Panel 2.5.1 LED Indicators LOAD 1 LOAD 2 RUN TIME 2.5.3 LCD Display (inclduing SET TEST BATT LOAD 2.5.4 7-Segment Display) °C SETUP 2.5.2 Multi-function Buttons Amplon RT Series...
  • Page 19: Led Indicators

    Chapter 2 Introduction 2.5.1 LED Indicators No. LED Description Indicates the output status. 1. ON (green): There is output 2. OFF: There is no output 1. ON (red): The UPS detects an internal fault or an environmental fault. You could refer to for more information.
  • Page 20 UPS, it is advised to unplug the input power cord. In battery mode, press and hold the button for 3 seconds, re- lease it after you hear one beep and the UPS will turn off its output. Amplon RT Series...
  • Page 21: Lcd Display

    Chapter 2 Introduction Multi- Description function Button 2. Fault Clear: When the UPS has a fault condition, press and hold the button for 3 seconds, release it after you hear one beep and the UPS will clear the fault condition and return to standby mode. Be- sides, the LCD will show the relevant error code.
  • Page 22 Mode Graph tery mode. Bypass Illuminates when the UPS is operating in by- LOAD 1 LOAD 2 Mode Graph pass mode. ECO Mode Illuminates when the UPS is operating in ECO LOAD 1 LOAD 2 Graph mode. Amplon RT Series...
  • Page 23 Chapter 2 Introduction Icon Naming Description ECO Icon Illuminates when the UPS is in ECO mode. 1. ON: ECO function is enabled and the conn- ected loads are feed by the utility AC power. 2. Flashing: ECO function is enabled and the connected loads are feed by the double conversion.
  • Page 24 The bar graph illuminates according to the remaining battery capacity * 2. Flashing: The bar graph flashes when a low-battery situation occurs. NOTE : means that: <10%: no segment will illuminate. 10%-29%: the 1 segment will illuminate. 90%-100%: all segments will illuminate. Amplon RT Series...
  • Page 25: 7-Segment Display

    Chapter 2 Introduction 2.5.4 7-Segment Display Column A LOAD 1 LOAD 2 RUN TIME SET TEST BATT LOAD °C 7-Segment Display Column B NOTE : You might need to read the word shown in together with that in to understand the display meaning. Icon Description 1.
  • Page 26 2. LOAD & KVA: When the above two words illuminate together, it means how much kVA the total load is. 3. LOAD & KW: When the above two words illuminate together, it means how much kW the total load is. Amplon RT Series...
  • Page 27: Flow Chart Of The 7-Segment Display

    Chapter 2 Introduction Icon Description LOAD 4. LOAD & % & When the above word (LOAD), unit (%) and icon together, it means that the UPS has an overload situation. Means ‘voltage’. Means ‘percentage’. Means ‘frequency’. Means ‘kVA’. Means ‘kW’. Means ‘minute’.
  • Page 28 0.1 second to view the next display. second to view the next display. Press the SETUP button Press the SETUP button for 0.1 second to for 0.1 second to view the next display. view the next display. Amplon RT Series...
  • Page 29: Rear Panel

    Chapter 2 Introduction 2.6 Rear Panel 1 kVA TOTAL OUTPUT Imax. 4.5A 250Vac INPUT BREAKER INPUT LOAD 1 LOAD 2 24V DC WARNING : CONNECT 24 VDC BATTERY SYSTEMS ONLY CONNECTING OTHER SYSTEMS WILL VOID WARRANTY SMART SLOT REPO RS-232 Rear Panel: UPS102R2RT0B035/ UPS102R2RT0B1B1/ UPS102R2RT0B0B6 250Vac INPUT...
  • Page 30 Output Connect to your loads. Receptacles Output Connect to your loads. Receptacles External Connects to the Delta external battery pack (optional). Battery Pack Please see Connector for detailed information. (24Vdc 40A) Smart Slot Accepts SNMP, Relay I/O or ModBus card (optional). Please for detailed information.
  • Page 31 Chapter 2 Introduction 2 kVA TOTAL OUTPUT Imax. 9A 250Vac SMART SLOT INPUT BREAKER LOAD 1 LOAD 2 48V DC WARNING : CONNECT 48 VDC BATTERY SYSTEMS ONLY CONNECTING OTHER SYSTEMS WILL VOID WARRANTY REPO RS-232 INPUT OUTPUT Imax. 9A Rear Panel: UPS202R2RT0B035/ UPS202R2RT0B1B1/ UPS202R2RT0B0B6 250Vac SMART SLOT...
  • Page 32 Output Connect to your loads. Receptacles Output Connect to your load. Receptacles External Connects to the Delta external battery pack (optional). Battery Pack Please see Connector for detailed information. (48Vdc 40A) AC Input Connects the UPS to the mains.
  • Page 33 Chapter 2 Introduction 3 kVA TOTAL OUTPUT Imax. 13.5A 250Vac SMART SLOT INPUT BREAKER LOAD 1 LOAD 2 72V DC WARNING : CONNECT 72 VDC BATTERY SYSTEMS ONLY CONNECTING OTHER SYSTEMS WILL VOID WARRANTY REPO RS-232 INPUT OUTPUT Imax. 13.5A Rear Panel: UPS302R2RT0B035/ UPS302R2RT0B1B1/ UPS302R2RT0B0B6 250Vac SMART SLOT...
  • Page 34 Output Connect to your loads. Receptacles Output Connect to your load. Receptacles External Connects to the Delta external battery pack (optional). Battery Pack Please see Connector for detailed information. (72Vdc 40A) AC Input Connects the UPS to the mains.
  • Page 35: Chapter 3 : Installation

    Chapter 3 : Installation NOTE : 1. Before installation, please read thoroughly. 2. Each model has internal batteries and each model can connect the Delta external battery pack (optional). UPS and the Delta external battery pack (optional) by yourself, installation 3.1 Installation Data No.
  • Page 36: Rack Mounting Procedures For The Ups And The Delta External Battery Pack (Optional)

    Delta External Battery Pack (Optional) You can rack-mount the UPS and the Delta external battery pack (optional) in a four-post frame. The UPS and the Delta external battery pack (optional) use identical mounting kits and their mounting procedures are the same.
  • Page 37 Chapter 3 Installation Use the provided eight screws and eight washers to attach the rails to your rack. See Insert the UPS into the rack and tighten the provided four screws. See . Please note that there will be extra four screws left after installation.
  • Page 38: Tower Mounting Procedures For The Ups And The Delta External Battery Pack (Optional)

    3.3 Tower Mounting Procedures for the UPS and the Delta External Battery Pack (Optional) You can mount the UPS and the Delta external battery pack (optional) in an upright position by following the procedures below. The UPS and the Delta external battery pack (optional) use identical mounting kits and their mount- ing procedures are the same.
  • Page 39 Chapter 3 Installation Operation Panel Cable Rotate the operation panel 90° clockwise and re-install it back into the front plastic panel . Replace the front plastic panel and make sure the . See Assemble the tower stands (optional) by inserting the tenons into the grooves according to the size of the UPS.
  • Page 40 Carefully lift the UPS upright (at least two people are required) with the Delta logo shown on the operation panel facing up. See Place the UPS inside the tower stands (at least two people are required). Amplon RT Series...
  • Page 41: Chapter 4 : Connections

    NOTE : 1. Please read before connection. 2. Before connecting the Delta external battery pack (optional) to the UPS, check whether the rating voltage of the battery pack is suitable for the UPS. (optional). There are three different ratings, 24Vdc, 48Vdc and 72Vdc. Please select...
  • Page 42 Remove the cover of the external battery pack connector located on the rear side of the UPS. Connect the battery cable attached to the Delta external battery pack (optional) to the UPS’s battery pack connector. Make sure the battery cable’s iron strip shown in the figure below is tightly screwed.
  • Page 43: Communication Interface Connection

    For convenient removal of the battery power cord in an emergent situation, please arrange and organize each cable/ wire connecting to the UPS and the Delta external battery pack (optional) well. 4.3 Communication Interface Connection The RT 1~3kVA series UPS’s communication interfaces include an RS-232 port, a USB port, a smart slot and an REPO port.
  • Page 44: Utility Power Connection

    1. The diagram shown above is for reference only. Actual display depends on the operation of the UPS. 2. The UPS will charge its internal batteries and the optional Delta external battery pack (if connected and its DC breaker is turned on) whenever the UPS is connected to the AC source.
  • Page 45: Chapter 5 : Operation Modes

    Chapter 5 Operation Modes Chapter 5 : Operation Modes NOTE : 1. Please refer to to learn how to operate the operation panel and understand the display meaning. 2. Each of the display diagrams shown in this chapter is for reference only. Actual display depends on the operation of the UPS.
  • Page 46: Eco Mode

    For setup procedures, please refer to the following: 1. Press the scrolling button for more than 3 seconds to enter into the setup SETUP mode. 2. Press the scrolling button for 0.1 second to change the parameter. SETUP Amplon RT Series...
  • Page 47 Chapter 5 Operation Modes at the same time, the LCD will go to the next setup item. 4. You can skip to the next setup item by pressing the cancel button for 0.1 second. 5. In setup mode, press the scrolling button for more than 3 seconds, the LCD SETUP will go back to the original display.
  • Page 48 Bypass Range Setup SETUP T>3 seconds SETUP T=0.1S T>0.1S T>0.1S ECO Setup SETUP T>3 seconds SETUP T=0.1S T>0.1S T>0.1S Buzzer Setup SETUP T>3 seconds SETUP T=0.1S T>0.1S T>0.1S Overload Alarm Setup SETUP T>3 seconds SETUP T=0.1S T>0.1S Amplon RT Series...
  • Page 49: Chapter 6 : Operation

    Chapter 6 Operation Chapter 6 : Operation NOTE : 1. Please refer to to learn how to operate the operation panel and understand the display meaning. 2. Please refer to to understand how to use the UPS interfaces. 6.1 Start-up Procedures After the UPS is connected to the AC utility, the AC utility supplies power to the UPS.
  • Page 50: Battery Test

    UPS to switch off the alarm automatically. If, after a period of time, the audible alarm still exists, the user must manually initiate a battery test (press and hold the button for 3 seconds and release it after you hear one beep) to clear the alarm. Amplon RT Series...
  • Page 51: Rating Power

    Chapter 6 Operation 6.7 De-rating Power When the input voltage range is between 100Vac and 160Vac, the UPS’s load capacity will decrease. This function provides a wider operating power voltage range. 6.8 Online Mode/ Battery Mode Overload Cut-off 1. When the UPS is 105% ~125% overloaded either in online mode or in battery mode, the Load Level Bar Graph the UPS will completely shut down within 1 minute.
  • Page 52: Generator Compatible

    UPS or its connected loads. It is highly recommended that personnel carefully inspect the UPS, its connected loads and the surrounding environment. 6.10 Generator Compatible The UPS can operate with most of the generators available in the market. Amplon RT Series...
  • Page 53: Chapter 7 : Communication Interfaces

    Chapter 7 Communication Interfaces Chapter 7 : Communication Interfaces NOTE : The UPS can still function properly without making the connections below. The UPS’s communication interfaces include an RS-232 port, a USB port, a smart slot and an REPO port. Please refer to for their locations.
  • Page 54 ModBus Card Lets the UPS have ModBus communication. NOTE : For more detailed information about optional cards, please contact service personnel. If you need to purchase any optional card, please contact your local dealer or customer service. Amplon RT Series...
  • Page 55 Chapter 7 Communication Interfaces REPO Port The REPO port allows the user to shut down the UPS in online mode or in battery mode when an emergency occurs. Use a RJ11 cable (not provided) to connect the REPO port and a user-supplied switch. If the user-supplied switch is a normally-closed one, please short pin 3, pin 4 and pin 5 for approximately 1 second to shut down the UPS.
  • Page 56: Chapter 8 : Internal Battery Replacement

    7. Please read stated in before replacing batteries. The 1kVA, 2kVA and 3kVA UPSs contain two, four, and six internal batteries respectively. Below, we take 1kVA model as an example to describe the internal battery replacement procedures. Amplon RT Series...
  • Page 57 Chapter 8 Internal Battery Replacement Remove the UPS’s front plastic panel (there are four screws). From the back of the front panel, carefully push the backside of the operation panel until it slides out of the front plastic panel. Please handle with care to avoid damaging the cable connecting the operation panel and the UPS’s internal connector.
  • Page 58 Put the front plastic panel aside. Disconnect the battery cables. Battery Cables Amplon RT Series...
  • Page 59 Chapter 8 Internal Battery Replacement Pull out the tab carefully to take out the internal batteries. Insert the new batteries and reverse the procedures mentioned above to complete battery replacement.
  • Page 60: Chapter 9 : Optional Accessories

    Quick Guide, User Guide, or Installation & Operation Guide included in the package of the relevant optional accessory. 2. If you want to buy any accessory mentioned above, please contact your local dealer or customer service. Amplon RT Series...
  • Page 61: Chapter 10 : Maintenance

    Chapter 10 Maintenance Chapter 10 : Maintenance 10.1 UPS UPS Cleaning Regularly clean the UPS, especially the slits and openings, to ensure that the to clean the slits and openings to prevent any object from blocking or covering these areas. UPS Regular Inspection Regularly check the UPS every half year and inspect: 1.
  • Page 62: Fan

    UPS. If not, contact service personnel. NOTE : Please ask your local dealer or customer service for more maintenance information. Do not perform maintenance if you are not trained for it. Amplon RT Series...
  • Page 63: Chapter 11 : Troubleshooting

    1. When a problem occur, please check if the following situation exists before contacting Delta service personnel: Is the main input voltage present? 2. Please have the following information ready if you would like to contact the Delta service personnel: Unit information including model, serial number, etc.
  • Page 64 When the total load is Contact service personnel. Save’ Shut- too small or when there down is no load connected to the UPS, ‘Battery Save’ shutdown will be enabled after the UPS has run in battery mode for 30 minutes. Amplon RT Series...
  • Page 65 Chapter 11 Troubleshooting Error Meaning Possible Cause Solution Code Battery The UPS transfers to 1. Check the main AC source run in battery mode and the main power cord’s Low Shut- due to AC utility abnor- status. down mality; however, the 2.
  • Page 66: Appendi 1 : Technical Speci Cations

    , 220, 230, 240 Vac Voltage ± 2% (linear load) Regulation Frequency 50/60 Hz ± 0.05 Hz Output vTHD < 3% (linear load) < 105%: Continuous Overload 105% ~ 125%: 1 minute; Capability 125% ~ 150%: 15 seconds Cress Factor Amplon RT Series...
  • Page 67 Appendix 1 Technical Speci cations Model RT-1K RT-2K RT-3K Connection IEC C13x3x2, IEC C13x3x2, IEC C13x3x2 IEC C19x1 IEC C19x1 Connection Brazil Brazil Brazil Output socket x3 socket x4 socket x4 Connection Argentina Argentina Argentina socket x3 socket x4 socket x4 Online Mode Up to 94% Ef ciency...
  • Page 68 Delta External Battery Pack (Optional) 440 x 335 x 440 x 432 x 440 x 610 x Dimension (W x D x H) 89 mm 89 mm 89 mm Weight 15 Kg 27 Kg 44 Kg Nominal Voltage 24Vdc 48Vdc...
  • Page 69: Appendix 2 : Warranty

    Appendix 2 Warranty Appendix 2 : Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation.