Appendix 1: Technical Specifications - Delta Ultron HPH Series User Manual

Hide thumbs Also See for Ultron HPH Series:
Table of Contents

Advertisement

Model
Power Rating
Waveform
Nominal Voltage
Voltage Range
Frequency
Input
Frequency Range
Input Current
Power Factor
Voltage
Power Factor
Voltage Regulation
Voltage Harmonic
Distortion
Output
Overload Capability
Output Frequency
Crest Factor
Online Mode
Efficiency
ECO Mode
Type
Battery Voltage
Battery &
Maximum Charge
Charger
Current
Charge Voltage
Audible Noise
Ultron HPH Series

Appendix 1: Technical Specifications

HPH-20K
20kVA/20kW
220/380 Vac; 230/400 Vac; 240/415 Vac
176 ~ 276/ 305 ~ 478 Vac(100% Load)
132 ~ 276/ 228 ~ 478Vac(70% ~ 100% Load)
46A
> 0.99 (full load)
220/380 Vac; 230/400 Vac; 240/415 Vac
< 1.5% (linear load)
≤ 105%: continuous; 105% ~ ≤ 110%: 60 minutes;
110% ~ ≤ 125%: 10 minutes;
126% ~ ≤ 150%: 1 minute; > 150%: 1 second
50/60 Hz ± 0.05 Hz
SMF/ VRLA
15A
Float charge 272 ± 2 Vdc
Equalized charge 280 ± 2 Vdc
< 55 dBA
127
HPH-30K
30kVA/30kW
Sine Wave
50/60 Hz
40 ~ 70 Hz
61A
1
±1%
3:1
Up to 96%
Up to 99%
± 240 Vdc
15A
< 60 dBA
HPH-40K
40kVA/40kW
78A
15A
< 60 dBA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ultron hph-20kUltron hph-30kUltron hph-40k

Table of Contents