5.1 Precautions Prior to Installation and Wiring

Due to different installation environments, it is highly recommended that you read this user
manual before installation. Only authorized Delta engineers or service personnel can perform
installation and maintenance. If you want to install the UPS by yourself, installation must be
under the supervision of authorized Delta engineers or service personnel. If you use a forklift or
other equipment to move the UPS, please make sure its load bearing is sufficient. For the weight
of the UPS, please refer to Appendix 1: Technical Specifications.

5.2 Installation Environment

Install the UPS indoors. Do not place it outdoors.
Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and installation
area can accommodate the UPS, other equipment and forklifts. And make sure that
transportation routes and installation area can bear the weight of the UPS, other equipment
and forklifts. Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and
installation area can accommodate and bear the weight of the UPS, external battery
cabinets, other equipment that will be installed nearby and forklifts. For the weight of the UPS,
please refer to Appendix 1: Technical Specifications.
The installation place must be kept clean and tidy at all times.
Ensure that the installation area is large enough for maintenance and ventilation. Since
the UPS adopts the design of air inlet at the front and air outlet at the rear, it is recommended
that you place the external battery cabinet next to the UPS. we suggest that you:
1.
Keep a distance of 100cm from the front of the UPS for maintenance and ventilation.
2.
Keep a distance of 50cm from the back of the UPS for maintenance and ventilation.
3.
Keep a distance of 50cm from the both sides of the UPS for maintenance.
Keep the installation area's temperature around 0°C~40°C and humidity under 95%
condensing
. The normal operating altitude is under 1000 meters above sea level.
WARNING:
Do not use air conditioners or similar equipment to blow into the rear side of the UPS
and hinder ventilation.