Delta UPS - Ultron Family
HPH Series, Three Phase
160/ 200 kVA
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Ultron HPH Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Delta Ultron HPH Series

  • Page 1 The power behind competitiveness Delta UPS - Ultron Family HPH Series, Three Phase 160/ 200 kVA User Manual www.deltapowersolutions.com...
  • Page 2 Copyright © 2018 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Important Safety Instructions ---------------------------------------------- 1-1 Installation Warnings ---------------------------------------------------------------------- 1-2 Connection Warnings --------------------------------------------------------------------- 1-2 Usage Warnings --------------------------------------------------------------------------- 1-3 Storage Warnings ------------------------------------------------------------------------- 1-5 Standard Compliance -------------------------------------------------------------------- 1-5 Introduction ---------------------------------------------------------------------- 2-1 General Overview ------------------------------------------------------------------------- 2-2 Package Inspection ----------------------------------------------------------------------- 2-2 Functions &...
  • Page 4 REPO Dry Contacts ------------------------------------------------------------ 4-4 4.1.3 External Battery Temperature Dry Contacts ------------------------------ 4-5 4.1.4 External Switch/ Breaker Status Dry Contacts -------------------------- 4-6 4.1.5 Output Dry Contacts ------------------------------------------------------------ 4-7 4.1.6 Input Dry Contacts -------------------------------------------------------------4-10 4.1.7 Parallel Communication Card ----------------------------------------------- 4-11 Ultron HPH Series...
  • Page 5 Table of Contents 4.1.8 Parallel Ports --------------------------------------------------------------------4-12 4.1.9 SMART Slot ---------------------------------------------------------------------4-13 4.1.10 USB Port & RS-232 Port -----------------------------------------------------4-13 4.1.11 Auxiliary Power Cards --------------------------------------------------------4-13 4.1.12 Battery Start Buttons ----------------------------------------------------------4-14 Communication Interfaces at the Rear of the Touch Panel --------------------4-14 Installation and Wiring ------------------------------------------------------- 5-1 Before Installation and Wiring ---------------------------------------------------------- 5-2 Installation Environment ---------------------------------------------------------------- 5-2 UPS Transportation ---------------------------------------------------------------------- 5-4...
  • Page 6 Power Flow & Summary & System Status -----------------------------------------7-17 Check System Readings ---------------------------------------------------------------7-19 7.9.1 Main Input ------------------------------------------------------------------------7-19 7.9.2 Bypass Input --------------------------------------------------------------------7-20 7.9.3 Inverter Output ------------------------------------------------------------------7-20 7.9.4 Power Module Summary -----------------------------------------------------7-21 7.9.5 UPS Output ----------------------------------------------------------------------7-21 7.9.6 Battery Status -------------------------------------------------------------------7-22 Ultron HPH Series...
  • Page 7 Table of Contents 7.10 UPS Settings ------------------------------------------------------------------------------7-23 7.10.1 Bypass Setting ------------------------------------------------------------------7-23 7.10.2 Mode Setting --------------------------------------------------------------------7-24 7.10.3 Output Setting -------------------------------------------------------------------7-25 7.10.4 Battery & Charging Setting --------------------------------------------------7-26 7.10.5 Parallel Setting ------------------------------------------------------------------7-28 7.10.6 Dry Contact Setting -----------------------------------------------------------7-29 7.10.7 General Setting -----------------------------------------------------------------7-31 7.10.8 IP Setting -------------------------------------------------------------------------7-33 7.10.9 Control ----------------------------------------------------------------------------7-34 7.11 System Maintenance --------------------------------------------------------------------7-35 7.11.1...
  • Page 9: Important Safety Instructions

    Important Safety Instructions Important Safety Instructions 1.1 Installation Warnings 1.2 Connection Warnings 1.3 Usage Warnings 1.4 Storage Warnings 1.5 Standard Compliance...
  • Page 10: Installation Warnings

    Leave adequate space around all sides of the UPS for proper ventilation and mainte- nance. Please refer to 5.2 Installation Environment. Only authorized Delta engineers or service personnel can perform installation and maintenance. If you want to install the UPS by yourself, please install it under the su- pervision of authorized Delta engineers or service personnel.
  • Page 11: Usage Warnings

    (that have serious surge current) to the UPS, it needs to be de-rated according to on-site applications. For such special applications, please contact Delta service personnel for the accurate UPS sizing. The UPS is not suitable for connecting with any asymmetrical loads.
  • Page 12 Do not open or remove the covers or panels of the UPS to avoid high voltage electric shock. Only authorized Delta engineers or service personnel can do so for installation or maintenance. If you want to open or remove the covers or panels, do it only under the supervision of authorized Delta engineers or service personnel.
  • Page 13: Storage Warnings

    Important Safety Instructions Storage Warnings Use the original packing material to pack the UPS to prevent any possible damage from rodents. If the UPS needs to be stored prior to installation, it should be placed in a dry indoor area. The allowable storage temperature is below 70°C and relative humidity is below 95%.
  • Page 15: Introduction

    Introduction Introduction General Overview Package Inspection Functions & Features Exterior and Dimensions Front View Internal View Rear View Tri-color LED Indicator & Buzzer...
  • Page 16: General Overview

    Internal 1. Check the rating label attached to the UPS and make sure the device No. and capacity match what you ordered. 2. Examine if any parts are loose or damaged. Ultron HPH Series...
  • Page 17 Introduction 3. The UPS package contains the following items. Please check if any items are missing. The power behind competitiveness Delta UPS - Ultron Family HPH Series, Three Phase 160/ 200 kVA User Manual www.deltapowersolutions.com ×18 ×2 ×2 Item Q'ty...
  • Page 18: Functions & Features

    ±15% & frequency ±3Hz). If yes, the UPS will stop supplying power to the critical loads to protect your electronic equipment. Supports ECO mode: when input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, the UPS will transfer to bypass mode; other- Ultron HPH Series...
  • Page 19 Introduction Both auxiliary power and control circuit adopt redundancy design, which doubly en- hances UPS reliability. Suitable for top and bottom wiring. Suitable for top and front maintenance for power modules and system components. Generator compatible Single input and dual input functions. Supports external switch/ breaker status detection.
  • Page 20: Exterior And Dimensions

    Moreover, fan failure detection circuit is established. State-of-the-art microprocessor technology performs self-detection and monitors fan speed in real time, which provides complete and detailed operating status of the UPS. Exterior and Dimensions 1600 1100 (Figure 2-1: Exterior & Dimensions) Ultron HPH Series...
  • Page 21: Front View

    Introduction Front View 10” Color Tri-color Touch Screen LED Indicator Door Switch Casters Leveling Feet (Figure 2-2: UPS Front View) On the front of the UPS, there are a 10” color touch screen, a tri-color LED indicator, a door switch, four casters and four leveling feet. Please see Figure 2-2. 1.
  • Page 22: Internal View

    (Figure 2-3: How to Open the UPS Front Door) Internal View WARNING: Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
  • Page 23 Introduction Internal View (Front View with Door Open) Communication Interfaces GND B A GND B A MODBUS BMS DISPLAY BATT. START EXT. BATT TEMP. EXT.SWITCH STATUS CONTACT O/P DRY CONTACT I/P DRY BT1 BT2 REPO BATT. START BT3 BT4 PARALLEL RS-232 Power Modules (160kVA: 3 Power Modules)
  • Page 24 Switch (Q2) Switch (Q3) (Figure 2-5: Location of the Four Switches) Figure 2-6. Turn on the Switch : Turn off the Switch : (ON) (OFF) (ON) (OFF) ON I ON I ON I ON I 90° 90° Ultron HPH Series 2-10...
  • Page 25: Rear View

    Introduction Rear View WARNING: Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
  • Page 26 Bypass Input (Figure 2-9: Wiring Terminals_ AC Input & Bypass Input ) (Rear View after Rear Panel Removal) Battery Input T T E IN P UPS Output (Figure 2-10: Wiring Terminals_ Battery Input & UPS Output) Ultron HPH Series 2-12...
  • Page 27: Tri-Color Led Indicator & Buzzer

    Introduction (Rear View after Rear Panel Removal) Grounding Terminals for Top Wiring & Grounding Terminals for Bottom Wiring & (Figure 2-11: Wiring Terminals_ Grounding ) Tri-color LED Indicator & Buzzer Please see Figure 2-12 for the location of the tri-color LED Indicator. For information about the tri-color LED indicator, please refer to Table 2-1.
  • Page 28 A GND GND B RESET MODBUS Buzzer IT C IT C IT C IT C (Figure 2-13: Buzzer Location ) Please refer to the table below for the status of the tri-color LED indicator and the buzzer. Ultron HPH Series 2-14...
  • Page 29 Introduction Table 2-1: Tri-color LED Indicator & Buzzer Tri-color Green Yellow Indicator Status ‘Bypass’ ‘On-Line’ ‘Battery’ Operation ‘ECO’ Mode & ‘Standby’ ‘Frequency Conversion’ Screen ‘Softstart’ ‘Green’ Display* ‘Energy Recycle’ Warning Minor Medium Major Level* The buzzer The buzzer beeps 0.5 Buzzer beeps 0.5 second for...
  • Page 31: Operation Modes

    Operation Modes Operation Modes 3.1 Single Input 3.2 Dual Input 3.3 Hot Standby Redundancy (Only For Dual Input & At Least Two UPSs) 3.4 Common Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s))
  • Page 32 2. Up to eight UPS units can be paralleled for redundancy and capacity expansion. Only UPSs with the same capacity, voltage and frequency can be paralleled. Please only use the provided parallel cable to parallel the UPS units. Otherwise, parallel functions will fail. Ultron HPH Series...
  • Page 33: Single Input

    Operation Modes Single Input 3.1.1 Online Mode_ Single Input_ Single Unit In online mode, the main AC source supplies AC power via the Input Switch (Q1) to the to the inverter. In the meantime, the rectifier provides charging power to the batteries. After receiving the DC power, the inverter converts it into clean and stable AC power to the connected critical loads via the Output Switch (Q4).
  • Page 34: Battery Mode_ Single Input_ Single Unit

    During bypass mode, the UPS’s tri-color LED illuminates yellow and the text ‘Bypass’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-3: Bypass Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
  • Page 35: Manual Bypass Mode_ Single Input_ Single Unit

    Operation Modes 3.1.4 Manual Bypass Mode_ Single Input_ Single Unit When the UPS needs maintenance, you can manually switch the UPS to manual bypass mode. To let the UPS run in manual bypass mode, please follow the procedures below: Press the LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’...
  • Page 36: Eco Mode_ Single Input_ Single Unit

    During ECO mode, the UPS’s tri-color LED illuminates green and the text ‘ECO’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-5: ECO Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
  • Page 37: Frequency Conversion Mode_ Single Input_ Single Unit

    Operation Modes 3.1.6 Frequency Conversion Mode_ Single Input_ Single Unit To activate frequency conversion mode, please refer to 6.2.6 Frequency Conversion Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. After the UPS is manually set in frequency conversion mode, the inverter will automatically the system will automatically disable the bypass function.
  • Page 38: Green Mode_ Single Input_ Single Unit

    UPS. For the green mode diagram, please see Figure 3-7. During green mode, the UPS’s tri-color LED illuminates green and the text ‘Green’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-7: Green Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
  • Page 39: Energy Recycle Mode_ Single Input_ Single Unit

    Operation Modes 3.1.8 Energy Recycle Mode_ Single Input_ Single Unit NOTE: Energy recycle mode is only applicable to single input and single unit application. Energy recycle mode is only applicable to UPS self-test only. Without connection of any critical loads, the UPS can execute current test under full load condition. Before you activate energy recycle mode, please make sure that the Manual Bypass Switch (Q3), Output Switch (Q4) and each external battery cabinet’s battery breaker (Q5) are in the OFF status.
  • Page 40: Online Mode_ Single Input_ Parallel Units

    UPS’s LCD shows the text ‘On-Line’ in the upper right corner. Please refer to Figure 3-9 for the path of electrical power through the parallel UPSs in online mode. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-9: Online Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-10...
  • Page 41: Battery Mode_ Single Input_ Parallel Units

    Operation Modes 3.1.10 Battery Mode_ Single Input_ Parallel Units If the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs, all parallel UPSs will automatically transfer from online mode to battery mode. During the conversion process, output voltage remains the same, and during battery mode, each UPS’s tri-color LED illuminates yellow and each UPS’s LCD shows the text ‘Battery’...
  • Page 42: Bypass Mode_ Single Input_ Parallel Units

    ‘Bypass’ in the upper right corner. Please refer to Figure 3-11 for the path of electrical power through the parallel UPSs in bypass mode. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-11: Bypass Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-12...
  • Page 43: Manual Bypass Mode_ Single Input_ Parallel Units

    Operation Modes 3.1.12 Manual Bypass Mode_ Single Input_ Parallel Units please follow the procedures below to manually switch each of the parallel UPSs to manual bypass mode. Press each LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’ screen will YES’.
  • Page 44 Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-12: Manual Bypass Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-14...
  • Page 45: Eco Mode_ Single Input_ Parallel Units

    Operation Modes 3.1.13 ECO Mode_ Single Input_ Parallel Units To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode (parallel), when each UPS’s bypass input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, each UPS works in bypass mode;...
  • Page 46: Frequency Conversion Mode_ Single Input_ Parallel Units

    During frequency conversion mode (parallel), once all of the UPSs’ inverters shut down, there is no bypass output. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-14: Frequency Conversion Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-16...
  • Page 47: Green Mode_ Single Input_ Parallel Units

    Operation Modes 3.1.15 Green Mode_ Single Input_ Parallel Units To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. each system will automatically detect its UPS’s output status (i.e. total load capacity %) to higher efficiency of the UPS.
  • Page 48: Dual Input

    During online mode, the UPS’s tri-color LED illuminates green and the text ‘On-Line’ appears in the upper right corner of the screen. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-16: Online Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-18...
  • Page 49: Battery Mode_ Dual Input_ Single Unit

    Operation Modes 3.2.2 Battery Mode_ Dual Input_ Single Unit The UPS transfers to battery mode automatically if the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs. In battery mode, the batteries provide DC power and the UPS converts it into AC power and supplies it to the connected critical loads via the Output Switch (Q4).
  • Page 50: Manual Bypass Mode_ Dual Input_ Single Unit

    Do not touch the wiring terminals and the Manual Bypass Switch (Q3) during UPS maintenance process to avoid electric shock. the connected critical loads are not protected. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-19: Manual Bypass Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-20...
  • Page 51: Eco Mode_ Dual Input_ Single Unit

    Operation Modes 3.2.5 ECO Mode_ Dual Input_ Single Unit To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode, when the bypass AC source’s input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, the UPS works in bypass mode;...
  • Page 52: Frequency Conversion Mode_ Dual Input_ Single Unit

    ‘Frequency Conversion’ appears in the upper right corner of the screen. NOTE: During frequency conversion mode, once the inverter shuts down, there is no bypass output. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-21: Frequency Conversion Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-22...
  • Page 53: Green Mode_ Dual Input_ Single Unit

    Operation Modes 3.2.7 Green Mode_ Dual Input_ Single Unit To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. Green mode is the same as online mode, but the difference is that the system will the UPS.
  • Page 54: Online Mode_ Dual Input_ Parallel Units

    UPSs in online mode. Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-23: Online Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-24...
  • Page 55: Battery Mode_ Dual Input_ Parallel Units

    Operation Modes 3.2.9 Battery Mode_ Dual Input_ Parallel Units If the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs, all parallel UPSs will automatically transfer from online mode to battery mode. During the conversion process, output voltage remains the same, and during battery mode, each UPS’s tri-color LED illuminates yellow and each UPS’s LCD shows the text ‘Battery’...
  • Page 56: Bypass Mode_ Dual Input_ Parallel Units

    ‘Bypass’ in the upper right corner. Please see Figure 3-25 for the path of electrical power through the parallel UPSs in bypass mode. Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-25: Bypass Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-26...
  • Page 57: Manual Bypass Mode_ Dual Input_ Parallel Units

    Operation Modes 3.2.11 Manual Bypass Mode_ Dual Input_ Parallel Units please follow the procedures below to manually switch each of the parallel UPSs to manual bypass mode. Press each LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’ screen will YES’.
  • Page 58 Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-26: Manual Bypass Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-28...
  • Page 59: Eco Mode_ Dual Input_ Parallel Units

    Operation Modes 3.2.12 ECO Mode_ Dual Input_ Parallel Units To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode (parallel), when each UPS’s bypass input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, each UPS works in bypass mode;...
  • Page 60: Frequency Conversion Mode_ Dual Input_ Parallel Units

    During frequency conversion mode (parallel), once all of the UPSs’ inverters shut down, there is no bypass output. Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-28: Frequency Conversion Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-30...
  • Page 61: Green Mode_ Dual Input_ Parallel Units

    Operation Modes 3.2.14 Green Mode_ Dual Input_ Parallel Units To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. each system will automatically detect its UPS’s output status (i.e. total load capacity %) to higher efficiency of the UPS.
  • Page 62: Hot Standby Redundancy (Only For Dual Input & At Least Two Upss)

    UPS 1 tri-color LED illuminates green and the UPS 2 tri-color LED illuminates yellow. Static Switch BYPA. Rectifier Inverter MAIN Batteries Static Switch BYPA. Rectifier Inverter LOAD MAIN Batteries (Figure 3-30: Hot Standby Redundancy Diagram (only for Dual Input & at Least Two UPSs)) Ultron HPH Series 3-32...
  • Page 63: Common Battery

    Operation Modes Common Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s)) To save on your costs and installation space, the parallel UPSs can share their connected external battery cabinet(s). For common battery application, please install an isolated switch between each parallel UPS and its connected external battery cabinet(s).
  • Page 64 Static Switch BYPA. Rectifier Inverter MAIN LOAD Static Switch BYPA. Batteries Rectifier Inverter MAIN (Figure 3-31: Common Battery Diagram_ only for Parallel UPSs Connecting to the Same External Battery Cabinet(s)) Ultron HPH Series 3-34...
  • Page 65: Communication Interfaces

    Communication Interfaces Communication Interfaces 4.1 Communication Interfaces on the Front of the UPS with Front Door Open 4.2 Communication Interfaces at the Rear of the Touch Panel...
  • Page 66: Communication Interfaces On The Front Of The Ups With Front Door Open

    START O/P DRY I/P DRY EXT. BATT EXT.SWITCH CONTACT CONTACT TEMP. STATUS BT1 BT2 REPO BATT. NC NO START BT3 BT4 PARALLEL RS-232 (Figure 4-2: Communication Interfaces_ on the Front of the UPS with Front Door Open) Ultron HPH Series...
  • Page 67: Display Port

    Power Contacts Contacts Contacts Card’s LED Card Card’s LED Indicator Indicator (Figure 4-3: Functions of Communication Interfaces) 4.1.1 Display Port Before shipment, the display port has been connected to the 10” touch panel with the designated cable in Delta factory.
  • Page 68: Repo Dry Contacts

    Screw x 2 DISPLAY BATT. START EXT. BATT EXT.SWITCH O/P DRY I/P DRY CONTACT CONTACT TEMP. STATUS BT1 BT2 REPO BATT. NC NO START BT3 BT4 PARALLEL RS-232 Dry Contact Card (Figure 4-5: Dry Contact Card Location) Ultron HPH Series...
  • Page 69: External Battery Temperature Dry Contacts

    Communication Interfaces Jump CNR3 Dry Contact Card (Figure 4-6: Jump CNR3 Location) 4.1.3 External Battery Temperature Dry Contacts You can use the external battery temperature dry contacts (BT1, BT2, BT3 and BT4) to detect at maximum four external battery cabinets’ temperature. You need to purchase the battery cabinet temperature sensor cable (optional).
  • Page 70: External Switch/ Breaker Status Dry Contacts

    Dry Contact_ S3 Normally closed (NC) device Dry Contact_ S4 Normally open (NO) device EXT.SWITCH STATUS Buffer 2mA. Max Buffer 2mA. Max 2mA. Max Buffer 2mA. Max Buffer (Figure 4-8: External Switch/ Breaker Status Dry Contacts Design) Ultron HPH Series...
  • Page 71: Output Dry Contacts

    Communication Interfaces Event Description External input switch or breaker Detect the external input switch or breaker’s detection. status (default: S1). External bypass switch or Detect the external bypass switch or breaker’s breaker detection. status (default: S2). External output switch or Detect the external output switch or breaker’s breaker detection.
  • Page 72 P4 (Max. 0.5A/12V) DRY 4 DRY C_NO P3 (Max. 0.5A/12V) +12VS P2 (Max. 0.5A/12V) P1 (Max. 0.5A/12V) COMM_C DRY 3 DRY B_NO +12VS COMM_B DRY 2 DRY A_NO +12VS COMM_A DRY 1 (Figure 4-9: Output Dry Contacts Design) Ultron HPH Series...
  • Page 73 Communication Interfaces Event Description None No set-up. Load On Inverter The UPS works in online mode. Load On Bypass The UPS works in bypass mode. When the main AC source fails, the batteries supply Load On Battery power to the critical loads. When the UPS runs in battery mode, battery voltage Battery Low is lower than the setup limit (default: 220Vdc).
  • Page 74: Input Dry Contacts

    I/P DRY CONTACT Dry-1 Buffer 2mA. Max Dry-2 Buffer 2mA. Max Dry-3 2mA. Max Buffer Dry-4 2mA. Max Buffer (Figure 4-10: Input Dry Contacts Design) Ultron HPH Series 4-10...
  • Page 75: Parallel Communication Card

    Communication Interfaces Event Description None No set-up. Generator Status Generator status detection. Battery Ground Fail Battery leakage detection. External Battery Breaker Status detection of the external battery cabinet’s Detection breaker or switch. 4.1.7 Parallel Communication Card The UPS has one parallel communication card and the card includes two parallel ports and one LED indicator.
  • Page 76: Parallel Ports

    Parallel Ports (Figure 4-14: Location of Parallel Ports) WARNING: The provided parallel cable is placed in the accessory package. Using other types of cables to connect the parallel UPSs may cause parallel failure, malfunctions and accidents. Ultron HPH Series 4-12...
  • Page 77: Smart Slot

    Communication Interfaces 4.1.9 SMART Slot You can install the optional Relay I/O card (for dry contact expansion) into the SMART slot shown in Figure 4-15. For relevant installation and application information, please contact Delta customer service. SMART Slot DISPLAY BATT.
  • Page 78: Battery Start Buttons

    R E S E T BM S A GND GND B RESET M OD BU MODBUS IT C IT C IT C IT C (Figure 4-18: Communication Interfaces _ at the Rear of the Touch Panel) Ultron HPH Series 4-14...
  • Page 79 (Built-in MODUBS card) 2. Connects to a user-supplied monitoring system. Connects to a user-supplied battery management system or Delta battery management system (optional). 1. Connects to the display port shown in Figure 4-3. 2. Before shipment, the display port has been connect- DISPLAY ed to the 10”...
  • Page 81: Installation And Wiring

    Installation and Wiring Installation and Wiring 5.1 Before Installation and Wiring 5.2 Installation Environment 5.3 UPS Transportation 5.4 Fixing the UPS 5.5 Wiring 5.6 External Battery Cabinet Connection Warnings 5.7 STS Module 5.8 Power Module...
  • Page 82: Before Installation And Wiring

    & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel. If you use a forklift or other equipment to move Table 5-1.
  • Page 83 Installation and Wiring The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Ensure that the installation area is big enough for maintenance and ventilation. Since the UPS adopts the design of air inlet at the front and air outlet at the rear, we suggest that you: 1.
  • Page 84: Ups Transportation

    UPS, one person hold the other lateral side of the UPS with their hands, and one person use their hands to push the UPS either from the front side or from the backside to move the unit to the installation area and avoid tipping the UPS. Ultron HPH Series...
  • Page 85: Fixing The Ups

    Installation and Wiring If you need to move the UPS over a long distance, please use appropriate equipment like a forklift. Do not use the UPS casters to move the unit over a long distance. Fixing the UPS Please follow the steps below: information, please refer to Table 5-1.
  • Page 86: Wiring

    1. Before wiring, please ensure that you have followed 5.4 Fixing the UPS 2. Before wiring, please read 5.5 Wiring thoroughly. 3. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
  • Page 87 Installation and Wiring Before wiring or making any electrical connection, make sure that the power supplied to The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Check that the size, diameter, phase, polarity are correct for each cable that needs con- necting to the UPS and external battery cabinet(s).
  • Page 88 VNG of the UPS should be zero, we suggest that you install an isolation transformer in front of the input side of the UPS, and connect the isolation trans- former’s secondary neutral (N) and the ground ( ) to the nearest place of the trans- former. Ultron HPH Series...
  • Page 89 UPS is powered on. WARNING: Only authorized Delta engineers or service personnel can modify single input/ dual input setup. The UPS default setting is single input. If you want to modify it into dual input, please follow the procedures below.
  • Page 90 (Figure 5-6: Rear Panel & Screw Location) (Rear View after Rear Panel Removal) IN P AC Input AC Input or Bypass Input IN P AC Input or Bypass Input (Figure 5-7: Wiring Terminals_ AC Input & Bypass Input ) Ultron HPH Series 5-10...
  • Page 91 Installation and Wiring Unscrew the six screw nuts and remove the three copper bars. Please refer to Figure 5-8. (Rear View after Rear Panel Removal) INPUT IN P Different Angle BYPASS INPUT IN P Three Three Copper Bars Screw Nuts Copper Bars Screw Nuts (Figure 5-8: Remove the Six Screw Nuts and Three Copper Bars )
  • Page 92: Single Unit Wiring

    5.5.3 Single Unit Wiring NOTE: 1. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
  • Page 93 Installation and Wiring Single Input (Single Unit) When there is only one AC power source, single unit wiring procedures are as follows. The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Remove the rear panel’s six screws (Figure 5-9 ~ Figure 5-10) to see the wiring terminals (Figure 5-11 ~ Figure 5-13).
  • Page 94 Bypass Input (Figure 5-11: Wiring Terminals_ AC Input & Bypass Input ) (Rear View after Rear Panel Removal) Battery Input T T E IN P UPS Output (Figure 5-12: Wiring Terminals_ Battery Input & UPS Output ) Ultron HPH Series 5-14...
  • Page 95 Installation and Wiring (Rear View after Rear Panel Removal) Grounding Terminals for Top Wiring & Grounding Terminals for Bottom Wiring & (Figure 5-13: Wiring Terminals_ Grounding ) For top wiring, please remove the top cover (there are 6 crews) shown in Figure 5-14. (Rear View after Rear Panel Removal) Top Cover...
  • Page 96 Battery Input Connect to the external battery Include +/ -/ N terminals. Terminals cabinet. Includes one grounding For the UPS’s protective earthing. terminal. Includes three For the external battery cabinet grounding terminals. and critical loads’ grounding. Ultron HPH Series 5-16...
  • Page 97 Installation and Wiring Make sure the Input Switch (Q1), Bypass Switch (Q2), Manual Bypass Switch (Q3) and Output Switch (Q4) are in the OFF position. Please see Figure 2-5 for switch location. Make sure each external battery cabinet’s breaker is in the OFF position. Follow Table 5-2 to select proper input, output and battery cables.
  • Page 98 Rear Panel Removal) IN P IN P For the External For the UPS’s Battery Cabinet Protective and Critical Earthing Connect the Loads’ grounding Main AC Source (Figure 5-18: Single Unit Single Input Bottom Wiring Diagram_ Step 1) Ultron HPH Series 5-18...
  • Page 99 Installation and Wiring Single Input_ Bottom Wiring_ Step 2 (Rear View after Rear Panel Removal) BA TT ER Y INP UT UP S OU TP UT R S T Connect the External Connect the Battery Cabinet Critical Loads (Figure 5-19: Single Unit Single Input Bottom Wiring Diagram_ Step 2) NOTE: The UPS will not work normally if the main AC source’s neutral (N) is not Follow Figure 5-20 to ground the UPS, external battery cabinet(s) and connected...
  • Page 100 Protective Connect the Connect the and Critical Earthing Bypass Source Main AC Source Loads’ grounding (Rear View after Rear Panel Removal) IN P IN P (Figure 5-21: Single Unit Dual Input Top Wiring Diagram_ Step 1) Ultron HPH Series 5-20...
  • Page 101 Installation and Wiring Dual Input_ Top Wiring_ Step 2 Connect the External Connect the Battery Cabinet Critical Loads (Rear View after Rear Panel Removal) R S T T T E IN P (Figure 5-22: Single Unit Dual Input Top Wiring Diagram_ Step 2) Dual Input_ Bottom Wiring_ Step 1 (Rear View after Rear Panel Removal)
  • Page 102 (Figure 5-24: Single Unit Dual Input Bottom Wiring Diagram_ Step 2) NOTE: The UPS will not work normally if the main AC source and bypass Input neutral (N). Follow Figure 5-20 to ground the UPS, external battery cabinet(s) and connected critical loads. Ultron HPH Series 5-22...
  • Page 103: Parallel Unit Wiring

    5.5.4 Parallel Unit Wiring NOTE: 1. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
  • Page 104 (At Maximum Four) External External External External Load Load Battery Battery Battery Battery Cabinet Cabinet Cabinet Cabinet Load Grounding Load Grounding UPS Grounding External Battery Cabinet Grounding Protective Earthing (Figure 5-26: Grounding Diagram_ Parallel Units ) Ultron HPH Series 5-24...
  • Page 105 Installation and Wiring WARNING: UPS’s ‘Parallel Group ID’ (1 or 2) and ‘Parallel ID’ (1~8) through the LCD. Otherwise, the parallel UPSs cannot be started. Please refer to 7.10.5 Parallel Setting. Dual Input (Parallel Units) When there are two AC power sources, parallel units’ wiring procedures are as follows. Follow to modify the UPS from single input to dual input.
  • Page 106: External Battery Cabinet Connection Warnings

    UPS is powered on, the UPS will automatically charge the batteries. WARNING: You can connect the critical loads to the UPS only after the batteries are power to the critical loads connected when a power failure occurs. Ultron HPH Series 5-26...
  • Page 107 Installation and Wiring Battery Parameters Item Description Float charge voltage: ±272Vdc (default) Charge Voltage Equalized charge voltage: ±280Vdc (default) Default: ±5A (per power module) Minimum: ±6A Charge Current Maximum: ±45A (160kVA)/ ±60A (200 kVA) (per power module’s Max. current: 15A) Low Battery Shutdown ±200~±220Vdc (default: 210Vdc) Voltage...
  • Page 108 Table 5-3: External Battery Cabinet’s Protective Device (Default Battery Q’ty: 40 PCS) Power Protective Module UPS Rating Device’s Protective Device’s Voltage Q’ty Current 160kVA/ 150kW 450A (1) 4-pole DC breaker (per pole (2) 3-pole DC breaker (per pole 200kVA/ 200kW 600A Ultron HPH Series 5-28...
  • Page 109 Please note that only authorized Delta engineers or service personnel can perform wir- ing or you can perform wiring only under the supervision of authorized Delta engineers or service personnel. To connect the external battery cabinet(s) to the UPS, please refer to:...
  • Page 110 (Figure 5-29: Installation of an Isolated Switch Connected in Series with a DC Fuse) 2. Option 2: A DC circuit breaker External Battery Cabinet 4-Pole DC Circuit Breaker (Figure 5-30: Installation of a 4-Pole DC Circuit Breaker) Ultron HPH Series 5-30...
  • Page 111 Installation and Wiring External Battery Cabinet 3-Pole DC Circuit Breaker (Figure 5-31: Installation of a 3-Pole DC Circuit Breaker) To save on your costs and installation space, parallel UPSs (at maximum 8 units) can share external battery cabinet(s). For relevant information, please refer to 3.4 Com- mon Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s)).
  • Page 112: Sts Module

    Long beep. Battery Life Time Expired Sounds 50ms every 3 seconds STS Module The hot swappable STS module has been installed inside the UPS in the Delta factory before shipment. Please see Figure 5-32 for its location. 160kVA 200kVA GND B...
  • Page 113: Sts Module Installation

    (Figure 5-33: STS Module) 5.7.1 STS Module Installation The hot swappable STS module has been installed inside the UPS in the Delta factory before shipment. If the STS module is removed for some reasons and you want to re-install it, please follow the steps below.
  • Page 114 IT C IT C (Figure 5-35: Insert the STS Module into the UPS) Re-install the four screws (removed during the STS module removal process) to IT C (Figure 5-36: Fix the STS Module on the UPS) Ultron HPH Series 5-34...
  • Page 115: Sts Module Removal

    Installation and Wiring Turn the STS module’s switch to the upper position ( (Figure 5-37: Turn the STS Module’s Switch to the Upper Position) 5.7.2 STS Module Removal NOTE: procedures. 2. The STS module is heavy (> 21kg). At least two people are required for handling.
  • Page 116 5-41) on the left side of the STS module in order to continuously pull out the mo- dule from the UPS cabinet. GND B A GND RESET MODBUS IT C IT C IT C IT C (Figure 5-40: Remove the STS Module) Ultron HPH Series 5-36...
  • Page 117: Sts Module's Led Indicator

    Installation and Wiring Press the Lock (Figure 5-41: Press the Lock of the STS Module) 5.7.3 STS Module’s LED Indicator LED Indicator (Figure 5-42: STS Module’s LED Indicator ) The STS module’s LED indicator shows its operation status. Please refer to the following table.
  • Page 118: Power Module

    M AN M AN L BY L BY IT CH IT CH (Figure 5-43: Power Module Location) For power module illustration, please refer to Figure 5-44. LED Indicator Handle Switch Fans Handle (Figure 5-44: Power Module ) Ultron HPH Series 5-38...
  • Page 119: Power Module Installation

    Installation and Wiring 5.8.1 Power Module Installation The power modules have been installed inside the UPS in the Delta factory before shipment. If any power module is removed for some reasons and you want to re-install it, please follow the steps below.
  • Page 120 RESET MODBUS IT C IT C IT C IT C (Figure 5-46: Insert the Power Module into the UPS) the UPS cabinet. Please refer to Figure 5-47. (Figure 5-47: Fix the Power Module on the UPS) Ultron HPH Series 5-40...
  • Page 121: Power Module Removal

    Installation and Wiring Turn the power module’s switch to the upper position ( (Figure 5-48: Turn the Power Module’s Switch to the Upper Position) 5.8.2 Power Module Removal NOTE: 1. Only after the UPS is manually set in the manual bypass mode, can the following power module removal procedures be executed.
  • Page 122 Figure 5-52) on the left side of the power module in order to continuously pull out the module from the UPS cabinet. GND B A GND RESET MODBUS IT C IT C IT C IT C (Figure 5-51: Remove the Power Module) Ultron HPH Series 5-42...
  • Page 123: Power Module's Led Indicator

    Installation and Wiring Press the Lock (Figure 5-52: Press the Lock of the Power Module) 5.8.3 Power Module’s LED Indicator LED Indicator (Figure 5-53: Power Module’s LED Indicator ) The power module’s LED indicator shows its operation status. Please refer to the following table.
  • Page 124 In online mode, if you turn the power module’s switch to the lower position ( the power module will shut down its output and discharge the DC BUS voltage until the voltage reaches to a safety level. After that, the power module's LED indicator Ultron HPH Series 5-44...
  • Page 125: Ups Operation

    UPS Operation UPS Operation 6.1 Pre Start-up & Pre Turn- and Parallel Units 6.2 Start-up Procedures...
  • Page 126 UPS’s requirements. 4. Check if all power modules are properly installed and every power module’s switch is in the upper position ( ). Please refer to 5.8 Power Module for more information. Ultron HPH Series...
  • Page 127 UPS Operation If you perform turn-off procedures for single unit, all power will be completely cut off. Please make sure the critical loads connected to the UPS have already been safely shut Parallel Units Pre Start-up Warnings for Parallel Units 1.
  • Page 128: Start-Up Procedures

    LED indicator will illuminate yellow. For more information, please refer to 4.1.7 Parallel Communication Card. For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. Ultron HPH Series...
  • Page 129 UPS Operation Auxiliary Auxiliary Power Power Card Card’s LED Indicator DISPLAY BATT. START O/P DRY I/P DRY EXT. BATT EXT.SWITCH CONTACT CONTACT TEMP. STATUS BT1 BT2 REPO BATT. NC NO START BT3 BT4 PARALLEL RS-232 Parallel Communication Parallel Auxiliary Auxiliary Power Card’s LED Indicator Communication Card Power Card...
  • Page 130 EVENT LOG Bypass Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-3: Main Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series...
  • Page 131 UPS Operation Press the ON/ OFF button ( ) once and the following screen will pop up to ask you if you want to power on the UPS’s inverter. Please select ‘YES’. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Standby Power Flow...
  • Page 132: Battery Mode Start-Up Procedures

    For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. The LCD initial screen (see Figure 6-6) will appear within 40 seconds after each auxiliary power card’s LED indicator illuminates green. Ultron HPH Series...
  • Page 133 UPS Operation (Figure 6-6: LCD Initial Screen) After 20 seconds of LCD initialization, the LCD will enter the Main Screen shown in Figure 6-7 and the tri-color LED indicator will illuminate yellow. For the location of the tri-color LED indicator, please refer to Figure 2-12. User Login 09:30 May 10,2018...
  • Page 134 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Battery Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-9: Battery Mode Screen) Ultron HPH Series 6-10...
  • Page 135: Bypass Mode Start-Up Procedures

    UPS Operation 6.2.3 Bypass Mode Start-up Procedures WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. Ensure that the Manual Bypass Switch (Q3) is in the OFF position. Switch ON every external battery cabinet’s breaker (Q5).
  • Page 136 WARNING Bypass Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins ( Figure 6-11: Main Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series 6-12...
  • Page 137 UPS Operation For parallel application, please check each parallel UPS’s parallel settings. Please input, output and battery settings must be the same. For parallel application, press the icon ( ) located in the upper left corner of the UPS-1.1 screen and check if the total number of the parallel UPSs is correct. The UPS with the Figure 6-12.
  • Page 138: Manual Bypass Mode Start-Up Procedures

    Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-14: Online Mode Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series 6-14...
  • Page 139 UPS Operation Check if the bypass voltage and STS module are normal or not. If normal, press the ON/ OFF button ( ) once and the following screen will pop 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow User...
  • Page 140 For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. The LCD initial screen (see Figure 6-17) will appear within 40 seconds after the Input Switch (Q1) and Bypass Switch (Q2) are turned on. Ultron HPH Series 6-16...
  • Page 141 UPS Operation (Figure 6-17: LCD Initial Screen) After 20 seconds of LCD initialization, the LCD will enter the Main Screen. For the Main Screen information, please refer to 7.6 Main Screen. Now, each power module keeps running and its LED indicator remains green. After each power module finishes establishing DC BUS voltage, the charger will start to charge the batteries.
  • Page 142 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-20: Online Mode Screen) Ultron HPH Series 6-18...
  • Page 143: Eco Mode Start-Up Procedures

    UPS Operation 6.2.5 ECO Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
  • Page 144 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-22: Main Screen_ User Login) Ultron HPH Series 6-20...
  • Page 145 UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-23). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
  • Page 146 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-26: ECO Mode Screen) Ultron HPH Series 6-22...
  • Page 147: Frequency Conversion Mode Start-Up Procedures

    UPS Operation 6.2.6 Frequency Conversion Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
  • Page 148 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-28: Main Screen_ User Login) Ultron HPH Series 6-24...
  • Page 149 UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-29). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
  • Page 150 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Conversion Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-32: Frequency Conversion Mode Screen) Ultron HPH Series 6-26...
  • Page 151: Green Mode Start-Up Procedures

    UPS Operation 6.2.7 Green Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
  • Page 152 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-34: Main Screen_ User Login) Ultron HPH Series 6-28...
  • Page 153 UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-35). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
  • Page 154 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Green Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-38: Green Mode Screen) Ultron HPH Series 6-30...
  • Page 155: Energy Recycle Mode Start-Up Procedures

    UPS Operation 6.2.8 Energy Recycle Mode Start-up Procedures WARNING: Energy recycle mode is only applicable to single input and single unit application. Ensure that the Manual Bypass Switch (Q3), Output Switch (Q4) and every external battery cabinet’s breaker (Q5) are in the OFF position. Switch ON the Input Switch (Q1) and Bypass Switch (Q2).
  • Page 156 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins ( Figure 6-40: Main Screen_ User Login) Ultron HPH Series 6-32...
  • Page 157 UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-41). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow...
  • Page 158 LED indicator location, please refer to Figure 2-12. 09:30 May 10,2018 Energy UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Recycle Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 0 mins (Figure 6-44: Energy Recycle Mode Screen) Ultron HPH Series 6-34...
  • Page 159 UPS Operation WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. In online mode, the LCD shows the following screen (Figure 6-45) and the tri-color LED indicator illuminates green.
  • Page 160 About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. Ultron HPH Series 6-36...
  • Page 161 UPS Operation In battery mode, the LCD shows the following screen (Figure 6-48) and the tri-color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Battery Power Flow...
  • Page 162 UPSs. parallel ones, please contact service personnel. In bypass mode, the LCD shows the following screen (Figure 6-51) and the tri-color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12. Ultron HPH Series 6-38...
  • Page 163 UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-51: Bypass Mode Screen) Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
  • Page 164 System Status 90 % 5 mins ( Figure 6-52: ECO Mode Screen & ON/ OFF Button Location) Press the ON/ OFF button ( ) once and the following screen will pop up to ask you YES’. Ultron HPH Series 6-40...
  • Page 165 UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Power Flow User POWER OFF ? Transfer to Bypass without Protection! After selection of ‘YES’, the UPS will shut down the inverter, terminate each power module’s output and let the bypass AC source supply power. If the bypass AC source is abnormal, there is a risk of output interruption and the connected critical loads won’t be protected.
  • Page 166 Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). Ultron HPH Series 6-42...
  • Page 167 UPS Operation WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. In frequency conversion mode, the LCD shows the following screen (Figure 6-57) and the tri-color LED indicator illuminates green. For the tri-color LED indicator location, please refer to Figure 2-12.
  • Page 168 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Standby Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins (Figure 6-59: Standby Mode Screen) Ultron HPH Series 6-44...
  • Page 169 UPS Operation Switch OFF the Output Switch (Q4) and log in as an Administrator. For the Admini- strator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-60). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT...
  • Page 170 System Status 90 % 5 mins ( Figure 6-62: Green Mode Screen & ON/ OFF Button Location) Press the ON/ OFF button ( ) once and the following screen will pop up to ask you YES’. Ultron HPH Series 6-46...
  • Page 171 UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Green Power Flow User POWER OFF ? Transfer to Bypass without Protection! After selection of ‘YES’, the UPS will shut down each power module’s output and let the bypass AC source supply power.
  • Page 172 Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). Ultron HPH Series 6-48...
  • Page 173 UPS Operation WARNING: Energy recycle mode is only applicable to single input and single unit application. In energy recycle mode, the LCD shows the following screen (Figure 6-67) and the tri- color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12.
  • Page 174 Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 0 mins (Figure 6-70: Bypass Mode Screen_ Administrator Login) Ultron HPH Series 6-50...
  • Page 175 UPS Operation Click SETUP Mode Setting On-Line. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Mode Setting Administrator MODE SETTING Select to change system mode Energy Frequency On-Line Green Recycle Conversion (Figure 6-71: Select Online Mode) Switch OFF the Input Switch (Q1) and Bypass Switch (Q2).
  • Page 177: Lcd Display & Settings

    LCD Display & Settings LCD Display & Settings 7.1 LCD Display Hierarchy 7.2 How to Turn on the LCD 7.3 ON/ OFF Button 7.4 Introduction of Touch Panel and Function Keys 7.5 Password Entry 7.6 Main Screen 7.7 Main Menu 7.8 Power Flow &...
  • Page 178: Lcd Display Hierarchy

    DHCP Client/ IP Address/ Subnet Mask/ Gateway IP/ DNS 1 IP/ DNS 2 IP/ Search Domain Host Name (Level 2) Control Buzzer Force Equalized Charge/ Force Bypass to Inverter/ Reset Module/ Reset System (Figure 7-1: LCD Display Hierarchy) Ultron HPH Series...
  • Page 179: How To Turn On The Lcd

    LCD Display & Settings NOTE: 1. * means that the ADMINISTRATOR password is needed. For password information, please refer to 7.5 Password Entry. 2. The information on the LCD screen presented in 7. LCD Display & Settings, including UPS operation mode, machine number, date, time, total number of alarms, load %, battery remaining time, user login or administrator login, are for reference only.
  • Page 180 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 7-4: Main Screen_ User Login) Ultron HPH Series...
  • Page 181: On/ Off Button

    LCD Display & Settings ON/ OFF Button After the touch panel is turned on in accordance with the steps stated in 7.2 How to Turn on the LCD, the main screen will appear in the User login status and the ON/ OFF Button ) shown in Figure 7-5 will appear.
  • Page 182: Introduction Of Touch Panel And Function Keys

    On-Line Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins 13 14 15 16 17 18 (Figure 7-8: Introduction of Touch Panel and Function Keys) Ultron HPH Series...
  • Page 183 LCD Display & Settings Button Text/ Symbol Function Digital Display No. Icon/ Text Description (Yes or Display (Yes or (Yes or No) Back to the main screen. The UPS-1.1 shown below the symbol indicates the group ID and parallel ID of the UPS. NOTE: For the parallel UPSs (at ma- ximum eight), if you press...
  • Page 184 Energy Recycle Bypass operation status). Battery Standby Softstart Press the button to check the operation mode and status of the UPS. For more information, please refer to 7.8 Power Power Flow Flow & Summary & System Status. Ultron HPH Series...
  • Page 185 LCD Display & Settings Button Text/ Symbol Function Digital Display No. Icon/ Text Description (Yes or Display (Yes or (Yes or No) Shortcut button for summary information. Press the button to check the input, output, and battery status of the UPS. For more information, please refer to 7.8 Summary Power Flow &...
  • Page 186 Other symbols which will appear during the operation of the touch panel are shown in the table below. Symbol Function Goes to the top page. Goes to the last page. Moves up. Moves down. Increases number. Decreases number. Indicates the page No. Deletes number/ word. Ultron HPH Series 7-10...
  • Page 187: Password Entry

    LCD Display & Settings Symbol Function Capital Space NOTE: the Main Screen. For information about the Main Screen, please refer to 7.6 Main Screen. 2. The sleep time for the back light can be adjusted. Please refer to 7.10.7 General Setting. 3.
  • Page 188: Main Screen

    POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in bypass mode and the inverter is not turned on. Ultron HPH Series 7-12...
  • Page 189 LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in online mode and the loads are supplied by the inverter.
  • Page 190 For energy recycle mode settings, please refer to 7.10.2 Mode Setting and 6.2.8 Energy Recycle Mode Start-up Procedures. Ultron HPH Series 7-14...
  • Page 191 LCD Display & Settings 09:30 May 10,2018 Frequency UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Conversion Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in frequency conversion mode and the bypass output is restricted.
  • Page 192: Main Menu

    2. Mode Setting 3. Output Setting 4. Battery & Charging Setting 5. Parallel Setting SETUP 6. Dry Contact Setting 7. General Setting 8. IP Setting 9. Control For more information, please refer to 7.10 UPS Settings. Ultron HPH Series 7-16...
  • Page 193: Power Flow & Summary & System Status

    LCD Display & Settings Main Menu Description Button Press the button to go to the Maintenance Menu. In the menu, you can (1) check the warning events/ historical events/ statistics/ relevant test, (3) clear the statistics/ historical event/ battery test result, and (4) In the Maintenance Menu, it includes the following items.
  • Page 194 -0 A 50.0 kW 50.0 kW 50.0 kW Press the button to check the status of the STS module, power modules, parallel System Status communication card, system control card and auxiliary power cards. Please refer to the Ultron HPH Series 7-18...
  • Page 195: Check System Readings

    LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line System Status Administrator SYSTEM STATUS Power Flow Summary System Status STS Module Status System Control Card Status Power Module Status Auxiliary Power Card Status Parallel Communication Card Status Check System Readings 7.9.1 Main Input...
  • Page 196: Bypass Input

    LOG IN EVENT LOG On-Line Inverter Output Administrator INVERTER OUTPUT Power Module 01 PM 01 PM 02 Phase Voltage(V) 220.0 220.0 220.0 PM 03 PM 04 Line Voltage(V) 380.0 380.0 380.0 Current(A) 25.0 25.0 25.0 Frequency(Hz) 50.0 Ultron HPH Series 7-20...
  • Page 197: Power Module Summary

    LCD Display & Settings 7.9.4 Power Module Summary Path: Power Module Summary MEASUREMENT After entering the POWER MODULE SUMMARY user can inquire about each power module’s Phase Voltage, Current, DC BUS Voltage, PM A/D and PM D/D readings. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
  • Page 198: Battery Status

    May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Battery Status Administrator PAGE PAGE BATTERY STATUS Power Module# Charge Voltage 272.0 272.0 272.0 272.0 of PM# 272.0 272.0 272.0 272.0 Charge Current of PM# Ultron HPH Series 7-22...
  • Page 199: Ups Settings

    After entering the BYPASS SETTING screen (shown in the figure below), the user can set up the Bypass Frequency Range, Bypass Voltage (Max.), Bypass Voltage (Min.) and ECO Voltage Range. If the range is exceeded, the system will issue an alarm. Only Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
  • Page 200: Mode Setting

    UPS system mode, of which there are 5 options: On-Line Mode, Green Mode, ECO Mode, Energy Recycle Mode and Frequency Conversion Mode. These settings must be performed by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
  • Page 201: Output Setting

    LCD Display & Settings 7.10.3 Output Setting Path: SETUP After entering the OUTPUT SETTING Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Output Setting Administrator OUTPUT SETTING Voltage Frequency...
  • Page 202: Battery & Charging Setting

    In the BATTERY & CHARGING SETTING screen (shown in the figure below), the user can set up the following items. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
  • Page 203 LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Battery & Charging Setting Administrator PAGE PAGE PAGE PAGE BATTERY & CHARGING SETTING Battery Test Fail Voltage Battery Test Duration Auto Battery Test Interal None 09:30 May 10,2018...
  • Page 204: Parallel Setting

    Set up the battery replacement date. 7.10.5 Parallel Setting Path: SETUP After entering the PARALLEL SETTING items can be set up. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
  • Page 205: Dry Contact Setting

    In the DRY CONTACT SETTING open) or NC (normally closed) for each of the input and output dry contacts can be set up. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance.
  • Page 206 13. Battery over temperature 14. Output voltage abnormal 15. Battery need replacement 16. Bypass over temperature 17. Bypass static switch fault 18. UPS over temperature 19. Battery breaker shunt trip 20. Backfeed protection 21. UPS general alarm Ultron HPH Series 7-30...
  • Page 207: General Setting

    LCD Display & Settings 7.10.7 General Setting Path: SETUP After entering the GENERAL SETTING items can be set up. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass General Setting Administrator GENERAL SETTING DATE/ DUST SCREEN USER TIME FILTER Date Format...
  • Page 208 Set up the LCD backlight sleep time (default: 1 Screen Sleep (after) minute). Language Set up the display language (default: English). USER MODBUS ID Set up the MODBUS ID. Admin Password Set up the administrator password (4 digits). Ultron HPH Series 7-32...
  • Page 209: Ip Setting

    Only when you select ‘Enable’ for ‘Dust Filter Installation’ can you set up the ‘Dust Filter Installation Date’. 7.10.8 IP Setting Path: SETUP After entering the IP SETTING Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE...
  • Page 210: Control

    Set up the DNS server 2 IP address. Search Domain Set up the search domain. Host Name Set up the host name. 7.10.9 Control Path: SETUP After entering the CONTROL Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG...
  • Page 211: System Maintenance

    LCD Display & Settings Item Description Reset the power modules or not. In bypass mode, when you press the ON/ OFF button ( ) to start up the UPS but the UPS does not respond, please select Reset Module ‘Reset’ to reset the power modules. After the power modules are reset, please press the ON/ OFF button ( ) to start up the UPS.
  • Page 212: Historical Event

    Mains Input Volt Out Range 08:10:06 2017-10-15 501F-01 UPS Soft Start 07:58:15 2017-10-15 5005-01 No Output 07:48:22 2017-10-15 480A-01 COM Card #2 Absent 07:35:10 2017-10-15 0100-01 Mains Input Volt Out Range 07:25:25 2017-10-15 3200-01 About Emergency PWR Off 07:15:02 Ultron HPH Series 7-36...
  • Page 213: Statistics

    LCD Display & Settings 7.11.3 Statistics Path: MAINTENANCE After entering the STATISTICS the following statistics. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Statistics Administrator STATISTICS In Battery Mode times Battery Mode Duration hours In Bypass Mode times Bypass Mode Duration hours...
  • Page 214: Test

    After entering the CLEAR statistics, historical event and battery test result. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Clear Administrator CLEAR Clear Statistics Clear Historical Event Clear Clear Clear Battery Test Result Clear Ultron HPH Series 7-38...
  • Page 215: Advanced Diagnosis

    LCD Display & Settings Item Description After selecting ‘Clear’ Clear Statistics all records of the statistics will be cleared. The clear action requires the Administrator password. After selecting ‘Clear’ and confirming clearance of historical Clear Historical event logs, all historical event logs will be cleared. The clear Event action requires the Administrator password.
  • Page 216: Version & S

    UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Version & S/N Administrator VERSION & S/N MAIN System Power Module 1 EA017700017W0 Power Module 2 EA017700018W0 Touch Panel Power Module 3 EA017700019W0 Power Module 4 EA017700020W0 Ultron HPH Series 7-40...
  • Page 217 LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Version & S/N Administrator VERSION & S/N MAIN FPGA COM #1 0H0017AR00.00.01 4A0000AD00.00.01 Choose File System 0H0033AD00.01.00 4A0002AD00.00.01 Touch Panel 00.92 UPGRADE 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
  • Page 218 Touch Panel _ MCU/ Check and update the touch panel’s MCU or FPGA Check and update the MCU or FPGA firmware PM #_ MCU/ FPGA Check and update the MCU or FPGA firmware PM #_ MCU/ FPGA Ultron HPH Series 7-42...
  • Page 219: Optional Accessories

    Optional Accessories Optional Accessories...
  • Page 220 Quick Guide, User Guide, or Installation & Operation Guide included in the package of the relevant optional accessory. 2. If you want to buy any accessory mentioned above, please contact your local dealer or customer service. Ultron HPH Series...
  • Page 221: Maintenance

    Maintenance Maintenance...
  • Page 222 UPS. If not, replace the fans. NOTE: Please ask your local dealer or customer service for more maintenance information. Do not perform maintenance if you are not trained for it. Ultron HPH Series...
  • Page 223: Troubleshooting

    Troubleshooting Troubleshooting 10-1...
  • Page 224 When you see the following alarm messages appear on the LCD, please follow the solutions shown below. If you see other alarm messages that are not listed in the table below, please contact Delta service personnel for assistance. Do not perform troubleshooting if you are not trained for it.
  • Page 225 Troubleshooting Alarm Possible Cause Solution Message Bypass Input Please check the wiring and phase sequence Volt Phase The wiring is incorrect. of the bypass AC source, and contact service Seq Abnormal personnel for assistance. The bypass AC source’s Bypass Volt Please check the bypass AC source’s voltage voltage or frequency Out ECO...
  • Page 226 1. Check the battery constant temperature The battery temperature is equipment. Battery Under too low or the batteries are 2. Check if the batteries are abnormal or not. Temperature abnormal. If yes, please contact service personnel for assistance. Ultron HPH Series 10-4...
  • Page 227 Troubleshooting Alarm Possible Cause Solution Message Output The connected loads Overload Please decrease the loads. exceed the rated value. Warning 1. After overload shutdown, the connected loads will be supplied by the bypass. Please Output The connected loads decrease the loads to let the system re-start Overload exceed the rated value for automatically.
  • Page 228 Please contact service personnel for Abnormal - loose or the circuit board assistance. Physical has abnormalities. The system’s internal MONCAN communication cable is Please contact service personnel for Abnormal - loose or the circuit board assistance. Physical has abnormalities. Ultron HPH Series 10-6...
  • Page 229 Troubleshooting Alarm Possible Cause Solution Message PFC #n The circuit board has Please contact service personnel for MONCAN abnormalities. assistance. Comm Loss The system’s internal Parallel IO communication cable is Please contact service personnel for Abnormal loose or the circuit board assistance.
  • Page 230 Please contact service personnel for Open abnormal. assistance. INV #N The #n power module is Please contact service personnel for Output Fuse abnormal. assistance. Open Output Relay The #n power module is Please contact service personnel for Fault abnormal. assistance. Ultron HPH Series 10-8...
  • Page 231 Troubleshooting Alarm Possible Cause Solution Message 1. Please turn on the #n power module’s switch. PM Repair The #n power module’s 2. If the alarm message still exists after Switch Open switch is in the OFF status. the solution mentioned above has been executed, please contact service personnel.
  • Page 232 The fans are abnormal. or not. If yes, remove the foreign matter. Shutdown 2. Contact service personnel for assistance. NOTE: If the alarm still exists after the above possible causes are eliminated, please contact your dealer or customer service. Ultron HPH Series 10-10...
  • Page 233 Appendix 1 Technical A1-1...
  • Page 234 96.5% Efficiency ECO Mode Nominal Voltage ± 240 Vdc Charge Voltage ± 272 Vdc (adjustable from 204 Vdc to 312 Vdc) Battery Q’ty Battery 30 ~ 46 PCS (default: 40 PCS) Protection of Battery Deep Discharge Ultron HPH Series A1-2...
  • Page 235 Appendix 1 Model UPS Capacity 160kVA* / 150kW 200kVA/ 200kW Operating Altitude 1000 meters (without derating) Operating Temperature 0 ~ 40°C Environment Relative Humidity 95% (non-condensing) Audible Noise < 70 dBA * IP Degree of Protection IP 20 Parallel Redundancy Yes (up to 8 units) Remote Emergency Others...
  • Page 237: Appendix 2 : Warranty

    Appendix 2 Warranty Warranty A2-1...
  • Page 238 The User Manual must be carefully followed. Seller makes no representation No. 501326390000 Version : V 0.0 Release Date : 2018_06_13 Ultron HPH Series A2-2...