Table of Contents 4.1.8 Parallel Ports --------------------------------------------------------------------4-12 4.1.9 SMART Slot ---------------------------------------------------------------------4-13 4.1.10 USB Port & RS-232 Port -----------------------------------------------------4-13 4.1.11 Auxiliary Power Cards --------------------------------------------------------4-13 4.1.12 Battery Start Buttons ----------------------------------------------------------4-14 Communication Interfaces at the Rear of the Touch Panel --------------------4-14 Installation and Wiring ------------------------------------------------------- 5-1 Before Installation and Wiring ---------------------------------------------------------- 5-2 Installation Environment ---------------------------------------------------------------- 5-2 UPS Transportation ---------------------------------------------------------------------- 5-4...
Page 6
Power Flow & Summary & System Status -----------------------------------------7-17 Check System Readings ---------------------------------------------------------------7-19 7.9.1 Main Input ------------------------------------------------------------------------7-19 7.9.2 Bypass Input --------------------------------------------------------------------7-20 7.9.3 Inverter Output ------------------------------------------------------------------7-20 7.9.4 Power Module Summary -----------------------------------------------------7-21 7.9.5 UPS Output ----------------------------------------------------------------------7-21 7.9.6 Battery Status -------------------------------------------------------------------7-22 Ultron HPH Series...
Leave adequate space around all sides of the UPS for proper ventilation and mainte- nance. Please refer to 5.2 Installation Environment. Only authorized Delta engineers or service personnel can perform installation and maintenance. If you want to install the UPS by yourself, please install it under the su- pervision of authorized Delta engineers or service personnel.
(that have serious surge current) to the UPS, it needs to be de-rated according to on-site applications. For such special applications, please contact Delta service personnel for the accurate UPS sizing. The UPS is not suitable for connecting with any asymmetrical loads.
Page 12
Do not open or remove the covers or panels of the UPS to avoid high voltage electric shock. Only authorized Delta engineers or service personnel can do so for installation or maintenance. If you want to open or remove the covers or panels, do it only under the supervision of authorized Delta engineers or service personnel.
Important Safety Instructions Storage Warnings Use the original packing material to pack the UPS to prevent any possible damage from rodents. If the UPS needs to be stored prior to installation, it should be placed in a dry indoor area. The allowable storage temperature is below 70°C and relative humidity is below 95%.
Introduction Introduction General Overview Package Inspection Functions & Features Exterior and Dimensions Front View Internal View Rear View Tri-color LED Indicator & Buzzer...
Internal 1. Check the rating label attached to the UPS and make sure the device No. and capacity match what you ordered. 2. Examine if any parts are loose or damaged. Ultron HPH Series...
Page 17
Introduction 3. The UPS package contains the following items. Please check if any items are missing. The power behind competitiveness Delta UPS - Ultron Family HPH Series, Three Phase 160/ 200 kVA User Manual www.deltapowersolutions.com ×18 ×2 ×2 Item Q'ty...
±15% & frequency ±3Hz). If yes, the UPS will stop supplying power to the critical loads to protect your electronic equipment. Supports ECO mode: when input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, the UPS will transfer to bypass mode; other- Ultron HPH Series...
Page 19
Introduction Both auxiliary power and control circuit adopt redundancy design, which doubly en- hances UPS reliability. Suitable for top and bottom wiring. Suitable for top and front maintenance for power modules and system components. Generator compatible Single input and dual input functions. Supports external switch/ breaker status detection.
Moreover, fan failure detection circuit is established. State-of-the-art microprocessor technology performs self-detection and monitors fan speed in real time, which provides complete and detailed operating status of the UPS. Exterior and Dimensions 1600 1100 (Figure 2-1: Exterior & Dimensions) Ultron HPH Series...
Introduction Front View 10” Color Tri-color Touch Screen LED Indicator Door Switch Casters Leveling Feet (Figure 2-2: UPS Front View) On the front of the UPS, there are a 10” color touch screen, a tri-color LED indicator, a door switch, four casters and four leveling feet. Please see Figure 2-2. 1.
(Figure 2-3: How to Open the UPS Front Door) Internal View WARNING: Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
Page 23
Introduction Internal View (Front View with Door Open) Communication Interfaces GND B A GND B A MODBUS BMS DISPLAY BATT. START EXT. BATT TEMP. EXT.SWITCH STATUS CONTACT O/P DRY CONTACT I/P DRY BT1 BT2 REPO BATT. START BT3 BT4 PARALLEL RS-232 Power Modules (160kVA: 3 Power Modules)
Page 24
Switch (Q2) Switch (Q3) (Figure 2-5: Location of the Four Switches) Figure 2-6. Turn on the Switch : Turn off the Switch : (ON) (OFF) (ON) (OFF) ON I ON I ON I ON I 90° 90° Ultron HPH Series 2-10...
Introduction Rear View WARNING: Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
Page 26
Bypass Input (Figure 2-9: Wiring Terminals_ AC Input & Bypass Input ) (Rear View after Rear Panel Removal) Battery Input T T E IN P UPS Output (Figure 2-10: Wiring Terminals_ Battery Input & UPS Output) Ultron HPH Series 2-12...
Introduction (Rear View after Rear Panel Removal) Grounding Terminals for Top Wiring & Grounding Terminals for Bottom Wiring & (Figure 2-11: Wiring Terminals_ Grounding ) Tri-color LED Indicator & Buzzer Please see Figure 2-12 for the location of the tri-color LED Indicator. For information about the tri-color LED indicator, please refer to Table 2-1.
Page 28
A GND GND B RESET MODBUS Buzzer IT C IT C IT C IT C (Figure 2-13: Buzzer Location ) Please refer to the table below for the status of the tri-color LED indicator and the buzzer. Ultron HPH Series 2-14...
Page 29
Introduction Table 2-1: Tri-color LED Indicator & Buzzer Tri-color Green Yellow Indicator Status ‘Bypass’ ‘On-Line’ ‘Battery’ Operation ‘ECO’ Mode & ‘Standby’ ‘Frequency Conversion’ Screen ‘Softstart’ ‘Green’ Display* ‘Energy Recycle’ Warning Minor Medium Major Level* The buzzer The buzzer beeps 0.5 Buzzer beeps 0.5 second for...
Operation Modes Operation Modes 3.1 Single Input 3.2 Dual Input 3.3 Hot Standby Redundancy (Only For Dual Input & At Least Two UPSs) 3.4 Common Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s))
Page 32
2. Up to eight UPS units can be paralleled for redundancy and capacity expansion. Only UPSs with the same capacity, voltage and frequency can be paralleled. Please only use the provided parallel cable to parallel the UPS units. Otherwise, parallel functions will fail. Ultron HPH Series...
Operation Modes Single Input 3.1.1 Online Mode_ Single Input_ Single Unit In online mode, the main AC source supplies AC power via the Input Switch (Q1) to the to the inverter. In the meantime, the rectifier provides charging power to the batteries. After receiving the DC power, the inverter converts it into clean and stable AC power to the connected critical loads via the Output Switch (Q4).
During bypass mode, the UPS’s tri-color LED illuminates yellow and the text ‘Bypass’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-3: Bypass Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
Operation Modes 3.1.4 Manual Bypass Mode_ Single Input_ Single Unit When the UPS needs maintenance, you can manually switch the UPS to manual bypass mode. To let the UPS run in manual bypass mode, please follow the procedures below: Press the LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’...
During ECO mode, the UPS’s tri-color LED illuminates green and the text ‘ECO’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-5: ECO Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
Operation Modes 3.1.6 Frequency Conversion Mode_ Single Input_ Single Unit To activate frequency conversion mode, please refer to 6.2.6 Frequency Conversion Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. After the UPS is manually set in frequency conversion mode, the inverter will automatically the system will automatically disable the bypass function.
UPS. For the green mode diagram, please see Figure 3-7. During green mode, the UPS’s tri-color LED illuminates green and the text ‘Green’ appears in the upper right corner of the screen. Static Switch Rectifier Inverter MAIN LOAD Batteries (Figure 3-7: Green Mode Diagram_ Single Input Single Unit) Ultron HPH Series...
Operation Modes 3.1.8 Energy Recycle Mode_ Single Input_ Single Unit NOTE: Energy recycle mode is only applicable to single input and single unit application. Energy recycle mode is only applicable to UPS self-test only. Without connection of any critical loads, the UPS can execute current test under full load condition. Before you activate energy recycle mode, please make sure that the Manual Bypass Switch (Q3), Output Switch (Q4) and each external battery cabinet’s battery breaker (Q5) are in the OFF status.
UPS’s LCD shows the text ‘On-Line’ in the upper right corner. Please refer to Figure 3-9 for the path of electrical power through the parallel UPSs in online mode. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-9: Online Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-10...
Operation Modes 3.1.10 Battery Mode_ Single Input_ Parallel Units If the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs, all parallel UPSs will automatically transfer from online mode to battery mode. During the conversion process, output voltage remains the same, and during battery mode, each UPS’s tri-color LED illuminates yellow and each UPS’s LCD shows the text ‘Battery’...
‘Bypass’ in the upper right corner. Please refer to Figure 3-11 for the path of electrical power through the parallel UPSs in bypass mode. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-11: Bypass Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-12...
Operation Modes 3.1.12 Manual Bypass Mode_ Single Input_ Parallel Units please follow the procedures below to manually switch each of the parallel UPSs to manual bypass mode. Press each LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’ screen will YES’.
Page 44
Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-12: Manual Bypass Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-14...
Operation Modes 3.1.13 ECO Mode_ Single Input_ Parallel Units To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode (parallel), when each UPS’s bypass input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, each UPS works in bypass mode;...
During frequency conversion mode (parallel), once all of the UPSs’ inverters shut down, there is no bypass output. Static Switch Rectifier Inverter MAIN Batteries LOAD Static Switch Rectifier Inverter MAIN Batteries (Figure 3-14: Frequency Conversion Mode Diagram_ Single Input Parallel Units) Ultron HPH Series 3-16...
Operation Modes 3.1.15 Green Mode_ Single Input_ Parallel Units To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. each system will automatically detect its UPS’s output status (i.e. total load capacity %) to higher efficiency of the UPS.
During online mode, the UPS’s tri-color LED illuminates green and the text ‘On-Line’ appears in the upper right corner of the screen. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-16: Online Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-18...
Operation Modes 3.2.2 Battery Mode_ Dual Input_ Single Unit The UPS transfers to battery mode automatically if the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs. In battery mode, the batteries provide DC power and the UPS converts it into AC power and supplies it to the connected critical loads via the Output Switch (Q4).
Do not touch the wiring terminals and the Manual Bypass Switch (Q3) during UPS maintenance process to avoid electric shock. the connected critical loads are not protected. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-19: Manual Bypass Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-20...
Operation Modes 3.2.5 ECO Mode_ Dual Input_ Single Unit To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode, when the bypass AC source’s input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, the UPS works in bypass mode;...
‘Frequency Conversion’ appears in the upper right corner of the screen. NOTE: During frequency conversion mode, once the inverter shuts down, there is no bypass output. Static Switch BYPA. Rectifier Inverter MAIN LOAD Batteries (Figure 3-21: Frequency Conversion Mode Diagram_ Dual Input Single Unit) Ultron HPH Series 3-22...
Operation Modes 3.2.7 Green Mode_ Dual Input_ Single Unit To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. Green mode is the same as online mode, but the difference is that the system will the UPS.
Operation Modes 3.2.9 Battery Mode_ Dual Input_ Parallel Units If the main AC source cannot supply power, for example, when unstable voltage or a power outage occurs, all parallel UPSs will automatically transfer from online mode to battery mode. During the conversion process, output voltage remains the same, and during battery mode, each UPS’s tri-color LED illuminates yellow and each UPS’s LCD shows the text ‘Battery’...
‘Bypass’ in the upper right corner. Please see Figure 3-25 for the path of electrical power through the parallel UPSs in bypass mode. Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-25: Bypass Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-26...
Operation Modes 3.2.11 Manual Bypass Mode_ Dual Input_ Parallel Units please follow the procedures below to manually switch each of the parallel UPSs to manual bypass mode. Press each LCD’s ON/ OFF button ( ) once and the ‘POWER OFF?’ screen will YES’.
Operation Modes 3.2.12 ECO Mode_ Dual Input_ Parallel Units To activate ECO mode, please refer to 6.2.5 ECO Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. In ECO mode (parallel), when each UPS’s bypass input voltage and frequency are within the range of rating voltage ±10% and rating frequency ±3Hz, each UPS works in bypass mode;...
During frequency conversion mode (parallel), once all of the UPSs’ inverters shut down, there is no bypass output. Static Switch BYPA. Rectifier Inverter MAIN Batteries LOAD Static Switch BYPA. Rectifier Inverter MAIN Batteries (Figure 3-28: Frequency Conversion Mode Diagram_ Dual Input Parallel Units) Ultron HPH Series 3-30...
Operation Modes 3.2.14 Green Mode_ Dual Input_ Parallel Units To activate green mode, please refer to 6.2.7 Green Mode Start-up Procedures, 7.6 Main Screen and 7.10.2 Mode Setting. each system will automatically detect its UPS’s output status (i.e. total load capacity %) to higher efficiency of the UPS.
UPS 1 tri-color LED illuminates green and the UPS 2 tri-color LED illuminates yellow. Static Switch BYPA. Rectifier Inverter MAIN Batteries Static Switch BYPA. Rectifier Inverter LOAD MAIN Batteries (Figure 3-30: Hot Standby Redundancy Diagram (only for Dual Input & at Least Two UPSs)) Ultron HPH Series 3-32...
Operation Modes Common Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s)) To save on your costs and installation space, the parallel UPSs can share their connected external battery cabinet(s). For common battery application, please install an isolated switch between each parallel UPS and its connected external battery cabinet(s).
Page 64
Static Switch BYPA. Rectifier Inverter MAIN LOAD Static Switch BYPA. Batteries Rectifier Inverter MAIN (Figure 3-31: Common Battery Diagram_ only for Parallel UPSs Connecting to the Same External Battery Cabinet(s)) Ultron HPH Series 3-34...
Communication Interfaces Communication Interfaces 4.1 Communication Interfaces on the Front of the UPS with Front Door Open 4.2 Communication Interfaces at the Rear of the Touch Panel...
START O/P DRY I/P DRY EXT. BATT EXT.SWITCH CONTACT CONTACT TEMP. STATUS BT1 BT2 REPO BATT. NC NO START BT3 BT4 PARALLEL RS-232 (Figure 4-2: Communication Interfaces_ on the Front of the UPS with Front Door Open) Ultron HPH Series...
Power Contacts Contacts Contacts Card’s LED Card Card’s LED Indicator Indicator (Figure 4-3: Functions of Communication Interfaces) 4.1.1 Display Port Before shipment, the display port has been connected to the 10” touch panel with the designated cable in Delta factory.
Communication Interfaces Jump CNR3 Dry Contact Card (Figure 4-6: Jump CNR3 Location) 4.1.3 External Battery Temperature Dry Contacts You can use the external battery temperature dry contacts (BT1, BT2, BT3 and BT4) to detect at maximum four external battery cabinets’ temperature. You need to purchase the battery cabinet temperature sensor cable (optional).
Communication Interfaces Event Description External input switch or breaker Detect the external input switch or breaker’s detection. status (default: S1). External bypass switch or Detect the external bypass switch or breaker’s breaker detection. status (default: S2). External output switch or Detect the external output switch or breaker’s breaker detection.
Page 73
Communication Interfaces Event Description None No set-up. Load On Inverter The UPS works in online mode. Load On Bypass The UPS works in bypass mode. When the main AC source fails, the batteries supply Load On Battery power to the critical loads. When the UPS runs in battery mode, battery voltage Battery Low is lower than the setup limit (default: 220Vdc).
Communication Interfaces Event Description None No set-up. Generator Status Generator status detection. Battery Ground Fail Battery leakage detection. External Battery Breaker Status detection of the external battery cabinet’s Detection breaker or switch. 4.1.7 Parallel Communication Card The UPS has one parallel communication card and the card includes two parallel ports and one LED indicator.
Parallel Ports (Figure 4-14: Location of Parallel Ports) WARNING: The provided parallel cable is placed in the accessory package. Using other types of cables to connect the parallel UPSs may cause parallel failure, malfunctions and accidents. Ultron HPH Series 4-12...
Communication Interfaces 4.1.9 SMART Slot You can install the optional Relay I/O card (for dry contact expansion) into the SMART slot shown in Figure 4-15. For relevant installation and application information, please contact Delta customer service. SMART Slot DISPLAY BATT.
R E S E T BM S A GND GND B RESET M OD BU MODBUS IT C IT C IT C IT C (Figure 4-18: Communication Interfaces _ at the Rear of the Touch Panel) Ultron HPH Series 4-14...
Page 79
(Built-in MODUBS card) 2. Connects to a user-supplied monitoring system. Connects to a user-supplied battery management system or Delta battery management system (optional). 1. Connects to the display port shown in Figure 4-3. 2. Before shipment, the display port has been connect- DISPLAY ed to the 10”...
& cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel. If you use a forklift or other equipment to move Table 5-1.
Page 83
Installation and Wiring The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Ensure that the installation area is big enough for maintenance and ventilation. Since the UPS adopts the design of air inlet at the front and air outlet at the rear, we suggest that you: 1.
UPS, one person hold the other lateral side of the UPS with their hands, and one person use their hands to push the UPS either from the front side or from the backside to move the unit to the installation area and avoid tipping the UPS. Ultron HPH Series...
Installation and Wiring If you need to move the UPS over a long distance, please use appropriate equipment like a forklift. Do not use the UPS casters to move the unit over a long distance. Fixing the UPS Please follow the steps below: information, please refer to Table 5-1.
1. Before wiring, please ensure that you have followed 5.4 Fixing the UPS 2. Before wiring, please read 5.5 Wiring thoroughly. 3. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
Page 87
Installation and Wiring Before wiring or making any electrical connection, make sure that the power supplied to The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Check that the size, diameter, phase, polarity are correct for each cable that needs con- necting to the UPS and external battery cabinet(s).
Page 88
VNG of the UPS should be zero, we suggest that you install an isolation transformer in front of the input side of the UPS, and connect the isolation trans- former’s secondary neutral (N) and the ground ( ) to the nearest place of the trans- former. Ultron HPH Series...
Page 89
UPS is powered on. WARNING: Only authorized Delta engineers or service personnel can modify single input/ dual input setup. The UPS default setting is single input. If you want to modify it into dual input, please follow the procedures below.
Page 90
(Figure 5-6: Rear Panel & Screw Location) (Rear View after Rear Panel Removal) IN P AC Input AC Input or Bypass Input IN P AC Input or Bypass Input (Figure 5-7: Wiring Terminals_ AC Input & Bypass Input ) Ultron HPH Series 5-10...
Page 91
Installation and Wiring Unscrew the six screw nuts and remove the three copper bars. Please refer to Figure 5-8. (Rear View after Rear Panel Removal) INPUT IN P Different Angle BYPASS INPUT IN P Three Three Copper Bars Screw Nuts Copper Bars Screw Nuts (Figure 5-8: Remove the Six Screw Nuts and Three Copper Bars )
5.5.3 Single Unit Wiring NOTE: 1. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
Page 93
Installation and Wiring Single Input (Single Unit) When there is only one AC power source, single unit wiring procedures are as follows. The UPS adopts top and bottom wiring. Please leave adequate space on the top and at the bottom of the UPS to allow cable entry. Remove the rear panel’s six screws (Figure 5-9 ~ Figure 5-10) to see the wiring terminals (Figure 5-11 ~ Figure 5-13).
Page 94
Bypass Input (Figure 5-11: Wiring Terminals_ AC Input & Bypass Input ) (Rear View after Rear Panel Removal) Battery Input T T E IN P UPS Output (Figure 5-12: Wiring Terminals_ Battery Input & UPS Output ) Ultron HPH Series 5-14...
Page 95
Installation and Wiring (Rear View after Rear Panel Removal) Grounding Terminals for Top Wiring & Grounding Terminals for Bottom Wiring & (Figure 5-13: Wiring Terminals_ Grounding ) For top wiring, please remove the top cover (there are 6 crews) shown in Figure 5-14. (Rear View after Rear Panel Removal) Top Cover...
Page 96
Battery Input Connect to the external battery Include +/ -/ N terminals. Terminals cabinet. Includes one grounding For the UPS’s protective earthing. terminal. Includes three For the external battery cabinet grounding terminals. and critical loads’ grounding. Ultron HPH Series 5-16...
Page 97
Installation and Wiring Make sure the Input Switch (Q1), Bypass Switch (Q2), Manual Bypass Switch (Q3) and Output Switch (Q4) are in the OFF position. Please see Figure 2-5 for switch location. Make sure each external battery cabinet’s breaker is in the OFF position. Follow Table 5-2 to select proper input, output and battery cables.
Page 98
Rear Panel Removal) IN P IN P For the External For the UPS’s Battery Cabinet Protective and Critical Earthing Connect the Loads’ grounding Main AC Source (Figure 5-18: Single Unit Single Input Bottom Wiring Diagram_ Step 1) Ultron HPH Series 5-18...
Page 99
Installation and Wiring Single Input_ Bottom Wiring_ Step 2 (Rear View after Rear Panel Removal) BA TT ER Y INP UT UP S OU TP UT R S T Connect the External Connect the Battery Cabinet Critical Loads (Figure 5-19: Single Unit Single Input Bottom Wiring Diagram_ Step 2) NOTE: The UPS will not work normally if the main AC source’s neutral (N) is not Follow Figure 5-20 to ground the UPS, external battery cabinet(s) and connected...
Page 100
Protective Connect the Connect the and Critical Earthing Bypass Source Main AC Source Loads’ grounding (Rear View after Rear Panel Removal) IN P IN P (Figure 5-21: Single Unit Dual Input Top Wiring Diagram_ Step 1) Ultron HPH Series 5-20...
Page 101
Installation and Wiring Dual Input_ Top Wiring_ Step 2 Connect the External Connect the Battery Cabinet Critical Loads (Rear View after Rear Panel Removal) R S T T T E IN P (Figure 5-22: Single Unit Dual Input Top Wiring Diagram_ Step 2) Dual Input_ Bottom Wiring_ Step 1 (Rear View after Rear Panel Removal)
Page 102
(Figure 5-24: Single Unit Dual Input Bottom Wiring Diagram_ Step 2) NOTE: The UPS will not work normally if the main AC source and bypass Input neutral (N). Follow Figure 5-20 to ground the UPS, external battery cabinet(s) and connected critical loads. Ultron HPH Series 5-22...
5.5.4 Parallel Unit Wiring NOTE: 1. Only authorized Delta engineers or service personnel can perform installation, wiring, panel & cover removal, maintenance and operation. If you want to execute any action mentioned above by yourself, the action must be under the supervision of authorized Delta engineers or service personnel.
Page 105
Installation and Wiring WARNING: UPS’s ‘Parallel Group ID’ (1 or 2) and ‘Parallel ID’ (1~8) through the LCD. Otherwise, the parallel UPSs cannot be started. Please refer to 7.10.5 Parallel Setting. Dual Input (Parallel Units) When there are two AC power sources, parallel units’ wiring procedures are as follows. Follow to modify the UPS from single input to dual input.
UPS is powered on, the UPS will automatically charge the batteries. WARNING: You can connect the critical loads to the UPS only after the batteries are power to the critical loads connected when a power failure occurs. Ultron HPH Series 5-26...
Page 107
Installation and Wiring Battery Parameters Item Description Float charge voltage: ±272Vdc (default) Charge Voltage Equalized charge voltage: ±280Vdc (default) Default: ±5A (per power module) Minimum: ±6A Charge Current Maximum: ±45A (160kVA)/ ±60A (200 kVA) (per power module’s Max. current: 15A) Low Battery Shutdown ±200~±220Vdc (default: 210Vdc) Voltage...
Page 108
Table 5-3: External Battery Cabinet’s Protective Device (Default Battery Q’ty: 40 PCS) Power Protective Module UPS Rating Device’s Protective Device’s Voltage Q’ty Current 160kVA/ 150kW 450A (1) 4-pole DC breaker (per pole (2) 3-pole DC breaker (per pole 200kVA/ 200kW 600A Ultron HPH Series 5-28...
Page 109
Please note that only authorized Delta engineers or service personnel can perform wir- ing or you can perform wiring only under the supervision of authorized Delta engineers or service personnel. To connect the external battery cabinet(s) to the UPS, please refer to:...
Page 110
(Figure 5-29: Installation of an Isolated Switch Connected in Series with a DC Fuse) 2. Option 2: A DC circuit breaker External Battery Cabinet 4-Pole DC Circuit Breaker (Figure 5-30: Installation of a 4-Pole DC Circuit Breaker) Ultron HPH Series 5-30...
Page 111
Installation and Wiring External Battery Cabinet 3-Pole DC Circuit Breaker (Figure 5-31: Installation of a 3-Pole DC Circuit Breaker) To save on your costs and installation space, parallel UPSs (at maximum 8 units) can share external battery cabinet(s). For relevant information, please refer to 3.4 Com- mon Battery (Only for Parallel UPSs connecting to the Same External Battery Cabinet(s)).
Long beep. Battery Life Time Expired Sounds 50ms every 3 seconds STS Module The hot swappable STS module has been installed inside the UPS in the Delta factory before shipment. Please see Figure 5-32 for its location. 160kVA 200kVA GND B...
(Figure 5-33: STS Module) 5.7.1 STS Module Installation The hot swappable STS module has been installed inside the UPS in the Delta factory before shipment. If the STS module is removed for some reasons and you want to re-install it, please follow the steps below.
Page 114
IT C IT C (Figure 5-35: Insert the STS Module into the UPS) Re-install the four screws (removed during the STS module removal process) to IT C (Figure 5-36: Fix the STS Module on the UPS) Ultron HPH Series 5-34...
Installation and Wiring Turn the STS module’s switch to the upper position ( (Figure 5-37: Turn the STS Module’s Switch to the Upper Position) 5.7.2 STS Module Removal NOTE: procedures. 2. The STS module is heavy (> 21kg). At least two people are required for handling.
Page 116
5-41) on the left side of the STS module in order to continuously pull out the mo- dule from the UPS cabinet. GND B A GND RESET MODBUS IT C IT C IT C IT C (Figure 5-40: Remove the STS Module) Ultron HPH Series 5-36...
Installation and Wiring Press the Lock (Figure 5-41: Press the Lock of the STS Module) 5.7.3 STS Module’s LED Indicator LED Indicator (Figure 5-42: STS Module’s LED Indicator ) The STS module’s LED indicator shows its operation status. Please refer to the following table.
M AN M AN L BY L BY IT CH IT CH (Figure 5-43: Power Module Location) For power module illustration, please refer to Figure 5-44. LED Indicator Handle Switch Fans Handle (Figure 5-44: Power Module ) Ultron HPH Series 5-38...
Installation and Wiring 5.8.1 Power Module Installation The power modules have been installed inside the UPS in the Delta factory before shipment. If any power module is removed for some reasons and you want to re-install it, please follow the steps below.
Page 120
RESET MODBUS IT C IT C IT C IT C (Figure 5-46: Insert the Power Module into the UPS) the UPS cabinet. Please refer to Figure 5-47. (Figure 5-47: Fix the Power Module on the UPS) Ultron HPH Series 5-40...
Installation and Wiring Turn the power module’s switch to the upper position ( (Figure 5-48: Turn the Power Module’s Switch to the Upper Position) 5.8.2 Power Module Removal NOTE: 1. Only after the UPS is manually set in the manual bypass mode, can the following power module removal procedures be executed.
Page 122
Figure 5-52) on the left side of the power module in order to continuously pull out the module from the UPS cabinet. GND B A GND RESET MODBUS IT C IT C IT C IT C (Figure 5-51: Remove the Power Module) Ultron HPH Series 5-42...
Installation and Wiring Press the Lock (Figure 5-52: Press the Lock of the Power Module) 5.8.3 Power Module’s LED Indicator LED Indicator (Figure 5-53: Power Module’s LED Indicator ) The power module’s LED indicator shows its operation status. Please refer to the following table.
Page 124
In online mode, if you turn the power module’s switch to the lower position ( the power module will shut down its output and discharge the DC BUS voltage until the voltage reaches to a safety level. After that, the power module's LED indicator Ultron HPH Series 5-44...
UPS Operation UPS Operation 6.1 Pre Start-up & Pre Turn- and Parallel Units 6.2 Start-up Procedures...
Page 126
UPS’s requirements. 4. Check if all power modules are properly installed and every power module’s switch is in the upper position ( ). Please refer to 5.8 Power Module for more information. Ultron HPH Series...
Page 127
UPS Operation If you perform turn-off procedures for single unit, all power will be completely cut off. Please make sure the critical loads connected to the UPS have already been safely shut Parallel Units Pre Start-up Warnings for Parallel Units 1.
LED indicator will illuminate yellow. For more information, please refer to 4.1.7 Parallel Communication Card. For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. Ultron HPH Series...
Page 129
UPS Operation Auxiliary Auxiliary Power Power Card Card’s LED Indicator DISPLAY BATT. START O/P DRY I/P DRY EXT. BATT EXT.SWITCH CONTACT CONTACT TEMP. STATUS BT1 BT2 REPO BATT. NC NO START BT3 BT4 PARALLEL RS-232 Parallel Communication Parallel Auxiliary Auxiliary Power Card’s LED Indicator Communication Card Power Card...
Page 130
EVENT LOG Bypass Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-3: Main Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series...
Page 131
UPS Operation Press the ON/ OFF button ( ) once and the following screen will pop up to ask you if you want to power on the UPS’s inverter. Please select ‘YES’. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Standby Power Flow...
For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. The LCD initial screen (see Figure 6-6) will appear within 40 seconds after each auxiliary power card’s LED indicator illuminates green. Ultron HPH Series...
Page 133
UPS Operation (Figure 6-6: LCD Initial Screen) After 20 seconds of LCD initialization, the LCD will enter the Main Screen shown in Figure 6-7 and the tri-color LED indicator will illuminate yellow. For the location of the tri-color LED indicator, please refer to Figure 2-12. User Login 09:30 May 10,2018...
Page 134
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Battery Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-9: Battery Mode Screen) Ultron HPH Series 6-10...
UPS Operation 6.2.3 Bypass Mode Start-up Procedures WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. Ensure that the Manual Bypass Switch (Q3) is in the OFF position. Switch ON every external battery cabinet’s breaker (Q5).
Page 136
WARNING Bypass Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins ( Figure 6-11: Main Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series 6-12...
Page 137
UPS Operation For parallel application, please check each parallel UPS’s parallel settings. Please input, output and battery settings must be the same. For parallel application, press the icon ( ) located in the upper left corner of the UPS-1.1 screen and check if the total number of the parallel UPSs is correct. The UPS with the Figure 6-12.
Power Flow User ON/ OFF POWER FLOW Button Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-14: Online Mode Screen_ User Login & ON/ OFF Button Location) Ultron HPH Series 6-14...
Page 139
UPS Operation Check if the bypass voltage and STS module are normal or not. If normal, press the ON/ OFF button ( ) once and the following screen will pop 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow User...
Page 140
For the locations of parallel communication card, auxiliary power cards, power mo- dules and associated LED indicators, please refer to Figure 6-1. The LCD initial screen (see Figure 6-17) will appear within 40 seconds after the Input Switch (Q1) and Bypass Switch (Q2) are turned on. Ultron HPH Series 6-16...
Page 141
UPS Operation (Figure 6-17: LCD Initial Screen) After 20 seconds of LCD initialization, the LCD will enter the Main Screen. For the Main Screen information, please refer to 7.6 Main Screen. Now, each power module keeps running and its LED indicator remains green. After each power module finishes establishing DC BUS voltage, the charger will start to charge the batteries.
Page 142
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-20: Online Mode Screen) Ultron HPH Series 6-18...
UPS Operation 6.2.5 ECO Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
Page 144
MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-22: Main Screen_ User Login) Ultron HPH Series 6-20...
Page 145
UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-23). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
Page 146
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-26: ECO Mode Screen) Ultron HPH Series 6-22...
UPS Operation 6.2.6 Frequency Conversion Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
Page 148
MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-28: Main Screen_ User Login) Ultron HPH Series 6-24...
Page 149
UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-29). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
Page 150
UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Conversion Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-32: Frequency Conversion Mode Screen) Ultron HPH Series 6-26...
UPS Operation 6.2.7 Green Mode Start-up Procedures WARNING: 1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures normally run, follow the following procedures step by step. 2. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs.
Page 152
MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-34: Main Screen_ User Login) Ultron HPH Series 6-28...
Page 153
UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-35). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow...
Page 154
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Green Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 6-38: Green Mode Screen) Ultron HPH Series 6-30...
UPS Operation 6.2.8 Energy Recycle Mode Start-up Procedures WARNING: Energy recycle mode is only applicable to single input and single unit application. Ensure that the Manual Bypass Switch (Q3), Output Switch (Q4) and every external battery cabinet’s breaker (Q5) are in the OFF position. Switch ON the Input Switch (Q1) and Bypass Switch (Q2).
Page 156
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins ( Figure 6-40: Main Screen_ User Login) Ultron HPH Series 6-32...
Page 157
UPS Operation Please log in as an Administrator. For the Administrator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-41). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow...
Page 158
LED indicator location, please refer to Figure 2-12. 09:30 May 10,2018 Energy UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Recycle Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 0 mins (Figure 6-44: Energy Recycle Mode Screen) Ultron HPH Series 6-34...
Page 159
UPS Operation WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. In online mode, the LCD shows the following screen (Figure 6-45) and the tri-color LED indicator illuminates green.
Page 160
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. Ultron HPH Series 6-36...
Page 161
UPS Operation In battery mode, the LCD shows the following screen (Figure 6-48) and the tri-color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Battery Power Flow...
Page 162
UPSs. parallel ones, please contact service personnel. In bypass mode, the LCD shows the following screen (Figure 6-51) and the tri-color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12. Ultron HPH Series 6-38...
Page 163
UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins ( Figure 6-51: Bypass Mode Screen) Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
Page 164
System Status 90 % 5 mins ( Figure 6-52: ECO Mode Screen & ON/ OFF Button Location) Press the ON/ OFF button ( ) once and the following screen will pop up to ask you YES’. Ultron HPH Series 6-40...
Page 165
UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Power Flow User POWER OFF ? Transfer to Bypass without Protection! After selection of ‘YES’, the UPS will shut down the inverter, terminate each power module’s output and let the bypass AC source supply power. If the bypass AC source is abnormal, there is a risk of output interruption and the connected critical loads won’t be protected.
Page 166
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). Ultron HPH Series 6-42...
Page 167
UPS Operation WARNING: 1. For parallel units, ensure that every operation procedure mentioned below is synchronized to all parallel UPSs. parallel ones, please contact service personnel. In frequency conversion mode, the LCD shows the following screen (Figure 6-57) and the tri-color LED indicator illuminates green. For the tri-color LED indicator location, please refer to Figure 2-12.
Page 168
09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Standby Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 90 % 5 mins (Figure 6-59: Standby Mode Screen) Ultron HPH Series 6-44...
Page 169
UPS Operation Switch OFF the Output Switch (Q4) and log in as an Administrator. For the Admini- strator password, please contact service personnel. After login, ensure that you are in the Administrator login status (see Figure 6-60). Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT...
Page 170
System Status 90 % 5 mins ( Figure 6-62: Green Mode Screen & ON/ OFF Button Location) Press the ON/ OFF button ( ) once and the following screen will pop up to ask you YES’. Ultron HPH Series 6-46...
Page 171
UPS Operation 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Green Power Flow User POWER OFF ? Transfer to Bypass without Protection! After selection of ‘YES’, the UPS will shut down each power module’s output and let the bypass AC source supply power.
Page 172
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED Switch OFF every external battery cabinet’s breaker (Q5). Ultron HPH Series 6-48...
Page 173
UPS Operation WARNING: Energy recycle mode is only applicable to single input and single unit application. In energy recycle mode, the LCD shows the following screen (Figure 6-67) and the tri- color LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to Figure 2-12.
Page 174
Administrator Login 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN WARNING Bypass Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary Mains System Status 0 mins (Figure 6-70: Bypass Mode Screen_ Administrator Login) Ultron HPH Series 6-50...
Page 175
UPS Operation Click SETUP Mode Setting On-Line. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Mode Setting Administrator MODE SETTING Select to change system mode Energy Frequency On-Line Green Recycle Conversion (Figure 6-71: Select Online Mode) Switch OFF the Input Switch (Q1) and Bypass Switch (Q2).
LCD Display & Settings LCD Display & Settings 7.1 LCD Display Hierarchy 7.2 How to Turn on the LCD 7.3 ON/ OFF Button 7.4 Introduction of Touch Panel and Function Keys 7.5 Password Entry 7.6 Main Screen 7.7 Main Menu 7.8 Power Flow &...
DHCP Client/ IP Address/ Subnet Mask/ Gateway IP/ DNS 1 IP/ DNS 2 IP/ Search Domain Host Name (Level 2) Control Buzzer Force Equalized Charge/ Force Bypass to Inverter/ Reset Module/ Reset System (Figure 7-1: LCD Display Hierarchy) Ultron HPH Series...
LCD Display & Settings NOTE: 1. * means that the ADMINISTRATOR password is needed. For password information, please refer to 7.5 Password Entry. 2. The information on the LCD screen presented in 7. LCD Display & Settings, including UPS operation mode, machine number, date, time, total number of alarms, load %, battery remaining time, user login or administrator login, are for reference only.
Page 180
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Power Flow User POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins (Figure 7-4: Main Screen_ User Login) Ultron HPH Series...
LCD Display & Settings ON/ OFF Button After the touch panel is turned on in accordance with the steps stated in 7.2 How to Turn on the LCD, the main screen will appear in the User login status and the ON/ OFF Button ) shown in Figure 7-5 will appear.
On-Line Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins 13 14 15 16 17 18 (Figure 7-8: Introduction of Touch Panel and Function Keys) Ultron HPH Series...
Page 183
LCD Display & Settings Button Text/ Symbol Function Digital Display No. Icon/ Text Description (Yes or Display (Yes or (Yes or No) Back to the main screen. The UPS-1.1 shown below the symbol indicates the group ID and parallel ID of the UPS. NOTE: For the parallel UPSs (at ma- ximum eight), if you press...
Page 184
Energy Recycle Bypass operation status). Battery Standby Softstart Press the button to check the operation mode and status of the UPS. For more information, please refer to 7.8 Power Power Flow Flow & Summary & System Status. Ultron HPH Series...
Page 185
LCD Display & Settings Button Text/ Symbol Function Digital Display No. Icon/ Text Description (Yes or Display (Yes or (Yes or No) Shortcut button for summary information. Press the button to check the input, output, and battery status of the UPS. For more information, please refer to 7.8 Summary Power Flow &...
Page 186
Other symbols which will appear during the operation of the touch panel are shown in the table below. Symbol Function Goes to the top page. Goes to the last page. Moves up. Moves down. Increases number. Decreases number. Indicates the page No. Deletes number/ word. Ultron HPH Series 7-10...
LCD Display & Settings Symbol Function Capital Space NOTE: the Main Screen. For information about the Main Screen, please refer to 7.6 Main Screen. 2. The sleep time for the back light can be adjusted. Please refer to 7.10.7 General Setting. 3.
POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in bypass mode and the inverter is not turned on. Ultron HPH Series 7-12...
Page 189
LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in online mode and the loads are supplied by the inverter.
Page 190
For energy recycle mode settings, please refer to 7.10.2 Mode Setting and 6.2.8 Energy Recycle Mode Start-up Procedures. Ultron HPH Series 7-14...
Page 191
LCD Display & Settings 09:30 May 10,2018 Frequency UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Conversion Power Flow Administrator POWER FLOW Maintenance Power Flow Bypass Bypass Load Summary 30 % Mains System Status 90 % 5 mins The screen above indicates that the UPS is in frequency conversion mode and the bypass output is restricted.
LCD Display & Settings Main Menu Description Button Press the button to go to the Maintenance Menu. In the menu, you can (1) check the warning events/ historical events/ statistics/ relevant test, (3) clear the statistics/ historical event/ battery test result, and (4) In the Maintenance Menu, it includes the following items.
Page 194
-0 A 50.0 kW 50.0 kW 50.0 kW Press the button to check the status of the STS module, power modules, parallel System Status communication card, system control card and auxiliary power cards. Please refer to the Ultron HPH Series 7-18...
LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line System Status Administrator SYSTEM STATUS Power Flow Summary System Status STS Module Status System Control Card Status Power Module Status Auxiliary Power Card Status Parallel Communication Card Status Check System Readings 7.9.1 Main Input...
LCD Display & Settings 7.9.4 Power Module Summary Path: Power Module Summary MEASUREMENT After entering the POWER MODULE SUMMARY user can inquire about each power module’s Phase Voltage, Current, DC BUS Voltage, PM A/D and PM D/D readings. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Battery Status Administrator PAGE PAGE BATTERY STATUS Power Module# Charge Voltage 272.0 272.0 272.0 272.0 of PM# 272.0 272.0 272.0 272.0 Charge Current of PM# Ultron HPH Series 7-22...
After entering the BYPASS SETTING screen (shown in the figure below), the user can set up the Bypass Frequency Range, Bypass Voltage (Max.), Bypass Voltage (Min.) and ECO Voltage Range. If the range is exceeded, the system will issue an alarm. Only Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
UPS system mode, of which there are 5 options: On-Line Mode, Green Mode, ECO Mode, Energy Recycle Mode and Frequency Conversion Mode. These settings must be performed by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
In the BATTERY & CHARGING SETTING screen (shown in the figure below), the user can set up the following items. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1...
Page 203
LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Battery & Charging Setting Administrator PAGE PAGE PAGE PAGE BATTERY & CHARGING SETTING Battery Test Fail Voltage Battery Test Duration Auto Battery Test Interal None 09:30 May 10,2018...
Set up the battery replacement date. 7.10.5 Parallel Setting Path: SETUP After entering the PARALLEL SETTING items can be set up. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
In the DRY CONTACT SETTING open) or NC (normally closed) for each of the input and output dry contacts can be set up. These settings must be carried out by qualified service personnel. Please contact Delta customer service for assistance.
Page 206
13. Battery over temperature 14. Output voltage abnormal 15. Battery need replacement 16. Bypass over temperature 17. Bypass static switch fault 18. UPS over temperature 19. Battery breaker shunt trip 20. Backfeed protection 21. UPS general alarm Ultron HPH Series 7-30...
LCD Display & Settings 7.10.7 General Setting Path: SETUP After entering the GENERAL SETTING items can be set up. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass General Setting Administrator GENERAL SETTING DATE/ DUST SCREEN USER TIME FILTER Date Format...
Page 208
Set up the LCD backlight sleep time (default: 1 Screen Sleep (after) minute). Language Set up the display language (default: English). USER MODBUS ID Set up the MODBUS ID. Admin Password Set up the administrator password (4 digits). Ultron HPH Series 7-32...
Only when you select ‘Enable’ for ‘Dust Filter Installation’ can you set up the ‘Dust Filter Installation Date’. 7.10.8 IP Setting Path: SETUP After entering the IP SETTING Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE...
Set up the DNS server 2 IP address. Search Domain Set up the search domain. Host Name Set up the host name. 7.10.9 Control Path: SETUP After entering the CONTROL Delta customer service for assistance. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG...
LCD Display & Settings Item Description Reset the power modules or not. In bypass mode, when you press the ON/ OFF button ( ) to start up the UPS but the UPS does not respond, please select Reset Module ‘Reset’ to reset the power modules. After the power modules are reset, please press the ON/ OFF button ( ) to start up the UPS.
Mains Input Volt Out Range 08:10:06 2017-10-15 501F-01 UPS Soft Start 07:58:15 2017-10-15 5005-01 No Output 07:48:22 2017-10-15 480A-01 COM Card #2 Absent 07:35:10 2017-10-15 0100-01 Mains Input Volt Out Range 07:25:25 2017-10-15 3200-01 About Emergency PWR Off 07:15:02 Ultron HPH Series 7-36...
LCD Display & Settings 7.11.3 Statistics Path: MAINTENANCE After entering the STATISTICS the following statistics. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Statistics Administrator STATISTICS In Battery Mode times Battery Mode Duration hours In Bypass Mode times Bypass Mode Duration hours...
After entering the CLEAR statistics, historical event and battery test result. 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG On-Line Clear Administrator CLEAR Clear Statistics Clear Historical Event Clear Clear Clear Battery Test Result Clear Ultron HPH Series 7-38...
LCD Display & Settings Item Description After selecting ‘Clear’ Clear Statistics all records of the statistics will be cleared. The clear action requires the Administrator password. After selecting ‘Clear’ and confirming clearance of historical Clear Historical event logs, all historical event logs will be cleared. The clear Event action requires the Administrator password.
UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Version & S/N Administrator VERSION & S/N MAIN System Power Module 1 EA017700017W0 Power Module 2 EA017700018W0 Touch Panel Power Module 3 EA017700019W0 Power Module 4 EA017700020W0 Ultron HPH Series 7-40...
Page 217
LCD Display & Settings 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP MAINTENANCE LOG IN EVENT LOG Bypass Version & S/N Administrator VERSION & S/N MAIN FPGA COM #1 0H0017AR00.00.01 4A0000AD00.00.01 Choose File System 0H0033AD00.01.00 4A0002AD00.00.01 Touch Panel 00.92 UPGRADE 09:30 May 10,2018 UPS-1.1 MEASUREMENT SETUP...
Page 218
Touch Panel _ MCU/ Check and update the touch panel’s MCU or FPGA Check and update the MCU or FPGA firmware PM #_ MCU/ FPGA Check and update the MCU or FPGA firmware PM #_ MCU/ FPGA Ultron HPH Series 7-42...
Page 220
Quick Guide, User Guide, or Installation & Operation Guide included in the package of the relevant optional accessory. 2. If you want to buy any accessory mentioned above, please contact your local dealer or customer service. Ultron HPH Series...
Page 222
UPS. If not, replace the fans. NOTE: Please ask your local dealer or customer service for more maintenance information. Do not perform maintenance if you are not trained for it. Ultron HPH Series...
Page 224
When you see the following alarm messages appear on the LCD, please follow the solutions shown below. If you see other alarm messages that are not listed in the table below, please contact Delta service personnel for assistance. Do not perform troubleshooting if you are not trained for it.
Page 225
Troubleshooting Alarm Possible Cause Solution Message Bypass Input Please check the wiring and phase sequence Volt Phase The wiring is incorrect. of the bypass AC source, and contact service Seq Abnormal personnel for assistance. The bypass AC source’s Bypass Volt Please check the bypass AC source’s voltage voltage or frequency Out ECO...
Page 226
1. Check the battery constant temperature The battery temperature is equipment. Battery Under too low or the batteries are 2. Check if the batteries are abnormal or not. Temperature abnormal. If yes, please contact service personnel for assistance. Ultron HPH Series 10-4...
Page 227
Troubleshooting Alarm Possible Cause Solution Message Output The connected loads Overload Please decrease the loads. exceed the rated value. Warning 1. After overload shutdown, the connected loads will be supplied by the bypass. Please Output The connected loads decrease the loads to let the system re-start Overload exceed the rated value for automatically.
Page 228
Please contact service personnel for Abnormal - loose or the circuit board assistance. Physical has abnormalities. The system’s internal MONCAN communication cable is Please contact service personnel for Abnormal - loose or the circuit board assistance. Physical has abnormalities. Ultron HPH Series 10-6...
Page 229
Troubleshooting Alarm Possible Cause Solution Message PFC #n The circuit board has Please contact service personnel for MONCAN abnormalities. assistance. Comm Loss The system’s internal Parallel IO communication cable is Please contact service personnel for Abnormal loose or the circuit board assistance.
Page 230
Please contact service personnel for Open abnormal. assistance. INV #N The #n power module is Please contact service personnel for Output Fuse abnormal. assistance. Open Output Relay The #n power module is Please contact service personnel for Fault abnormal. assistance. Ultron HPH Series 10-8...
Page 231
Troubleshooting Alarm Possible Cause Solution Message 1. Please turn on the #n power module’s switch. PM Repair The #n power module’s 2. If the alarm message still exists after Switch Open switch is in the OFF status. the solution mentioned above has been executed, please contact service personnel.
Page 232
The fans are abnormal. or not. If yes, remove the foreign matter. Shutdown 2. Contact service personnel for assistance. NOTE: If the alarm still exists after the above possible causes are eliminated, please contact your dealer or customer service. Ultron HPH Series 10-10...