Details On The Control Circuit Terminals (Ethernet Model) - Mitsubishi Electric 800 Series Instruction Manual

Connection
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.6.2
Details on the control circuit terminals (Ethernet
model)
 Input signal
Termi
Ty
nal
Common
pe
symbo
l
*1
DI0
SD
(sink
(negative common))
PC
(source
*1
DI1
(positive common))
10
5
2
5
4
5
*1
The terminal function can be selected by Pr.178 or Pr.179 (Input terminal function selection). (Refer to the FR-E800 Instruction Manual
(Function).)
*2
Refer to the FR-E800 Instruction Manual (Function).
 Output signal
Termin
Ty
Comm
al
pe
on
symbol
A,
B,
*1
C
*1
The terminal function can be selected by Pr.192 (Output terminal function selection). (Refer to the FR-E800 Instruction Manual (Function).)
*2
Refer to the FR-E800 Instruction Manual (Function).
56
2. Installation and Wiring
2.6 Control circuit
Terminal name
Forward rotation start
Reverse rotation start
Frequency setting
power supply
Frequency setting
(voltage)
Frequency setting
(current)
Terminal name
1 changeover contact output that indicates that an
inverter's protective function has been activated and the
Relay output (fault
outputs are stopped.
output)
Fault: discontinuity across B and C (continuity across A
and C), Normal: continuity across B and C (discontinuity
across A and C)
Terminal function description
Turn ON the STF signal to
start forward rotation and turn
it OFF to stop.
Turn ON the STR signal to
start reverse rotation and turn
it OFF to stop.
When connecting the frequency setting
potentiometer at an initial status, connect it to
terminal 10.
Inputting 0 to 5 VDC (or 0 to 10 VDC) provides
the maximum output frequency at 5 V (or 10 V)
and makes input and output proportional. Use
Pr.73 to switch among input 0 to 5 VDC (initial
setting), 0 to 10 VDC, and 0 to 20 mA.
* The initial setting varies depending on the
specification.
Set the voltage/current input switch to the "I"
position to select current input (0 to 20 mA).
Inputting 4 to 20 mADC (or 0 to 5 VDC, 0 to 10
VDC) provides the maximum output frequency
at 20 mA and makes input and output
proportional. This input signal is valid only when
the AU signal is ON (terminal 2 input is invalid).
To use the terminal 4 (current input at initial
setting), assign "4" to Pr.178 or Pr.179 (Input
terminal function selection) before turning ON
the AU signal.
* The initial setting varies depending on the
specification. Use Pr.267 to switch among input
4 to 20 mA (initial setting), 0 to 5 VDC, and 0 to
10 VDC. Set the voltage/current input switch to
the "V" position to select voltage input (0 to 5 V /
0 to 10 V).
Terminal function description
Rated
specification
Input resistance: 4.7
When the STF
kΩ,
and STR signals
voltage when
are turned ON
contacts are open:
simultaneously,
21 to 27 VDC,
the stop
current when
command is
contacts are short-
given.
circuited: 4 to 6
mADC
5 VDC ±0.5 V,
permissible load
current: 10 mA
For voltage input,
input resistance:
10±1 kΩ, maximum
permissible voltage:
20 VDC.
For current input,
input resistance:
245 ±5 Ω, maximum
permissible current:
30 mA.
Voltage/current
input switch
V
I
Rated specification
Contact capacity: 240
VAC 2 A
(power factor = 0.4),
30 VDC 1 A
Refer
to page
*2
*2
*2
*2
2
4
Refer
to page
*2