 Common terminal
Termi
nal
Common
Terminal name
symb
ol
Contact input
common (sink
(negative common))
External transistor
SD
common (source
(positive common))
24 VDC power supply
common
External transistor
common (sink
(negative common))
Safety stop input
PC
terminal common
Contact input
common (source
(positive common))
SD
24 VDC power supply Can be used as a 24 VDC 0.1 A power supply.
Frequency setting
5
common
Open collector output
SE
common
Safety monitor output
SOC
terminal common
*1
Refer to the FR-E800 Instruction Manual (Function).
 Communication
Terminal
Type
Terminal name
symbol
PU connector
USB B connector
*1
USB bus power connection is available. The maximum SCCR is 500 mA. A PU connector cannot be used during USB bus power connection.
Terminal function description
Common terminal for the contact input terminal (sink logic),
terminal FM.
Connect this terminal to the power supply common terminal
of a transistor output (open collector output) device, such as
a programmable controller, in the source logic to avoid
malfunction by undesirable current.
Common terminal for the 24 VDC power supply (terminal
PC).
Isolated from terminals 5 and SE.
Connect this terminal to the power supply common terminal
of a transistor output (open collector output) device, such as
a programmable controller, in the sink logic to avoid
malfunction by undesirable current.
Common terminal for safety stop input terminals
Common terminal for contact input terminal (source logic).
Common terminal for the frequency setting signal (terminal
2 or 4). Do not earth (ground).
Common terminal for terminals RUN and FU.
Common terminal for terminal SO.
Terminal function description
RS-485 communication can be made through the PU connector
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 300 to 115200 bps
Wiring length: 500 m
Mini B connector (receptacle).
By connecting the inverter to a personal computer via this connector, FR
Configurator2 installed on the computer can be used for setting the inverter, or
*1
monitoring or testing the inverter operation.
Interface: conforms to USB 1.1 (USB 2.0 full-speed compatible)
Transmission speed: 12 Mbps
Power supply: 5 V, 100 mA (500 mA maximum)
Refer
Rated specification
to
page
Power supply voltage
range:
22 to 26.5 VDC,
permissible load current:
100 mA
*1
66
Refer
to page
77
80