Controller
ER Code
Alarm
11
Makeup quantity
12
Filling time
13
Filling volume
15
Makeup valve
16
Power failure
19
Stop > 4 h
20
Max. Makeup volume
21
Maintenance
recommended
24
Softening
30
I/O module fault
31
EEPROM defective
36 — English
Group
Causes
message
Set value of the water meter
has been exceeded.
•
Leakage in the system.
•
Water quantity per
contact incorrectly set
in the Service menu.
Set value for the maximum
filling time has been
exceeded.
•
System volume too
large (≤ 3000Liter).
•
System volume too
large (≤ 3000Liter).
•
Water quantity per
contact incorrectly set
in the Service menu.
Makeup without demand
•
"WV" makeup valve
leaking
No power.
The device is in Stop mode
for more than 4 hours.
Set value for the makeup
quantity has been exceeded.
Set value exceeded.
•
Set value for the water
capacity has been
reached.
•
Time interval for
replacement of the
softening cartridge has
been reached.
•
I/O module defective.
•
Connection between
option card and
controller faulty.
•
Option card defective.
YES
•
EEPROM defective.
•
Internal calculation
error.
Fillcontrol Plus — 06.07.2016 - Rev. B
Remedy
•
Check the system for leaks.
•
Check the set value.
•
Restart the filling process
•
If necessary, restart the filling
process
•
Set the water quantity per
contact in the Service menu.
•
Replace the "WV" makeup
valve
Check power supply.
Select Automatic mode.
Reset the "Makeup quantity"
meter in the Customer menu.
Carry out maintenance.
Replace the softening cartridge.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Alarm reset
"Quit"
"Quit"
"Quit"
–
–
"Quit"
"Quit"
"Quit"
"Quit"