Malfunctions

8 Malfunctions
Note
Contact SAMSON's After-sales Service department for malfunctions not listed in Table 1 (see
section 10.1).
Table 1: Troubleshooting
Malfunction
Possible reasons
Pilot supply
Entire
pressure at the
solenoid
pneumatic
valve island
connection
no longer
module is outside
functions.
the permissible
range.
Incorrect nominal
signal at the
solenoid pilot
Single
valve
solenoid
valve no
longer
functions.
Incorrect
pneumatic output
signal at the
solenoid pilot
valve
46
Recommended action
For pneumatic connection module with pressure reducer:
− Unscrew the screw plug out of the pressure reducer.
− Screw in a quick connector with M4 male thread (order no.
0230-1679).
− Connect a pressure gauge with a 2x1 mm hose.
The output pressure of the pressure reducer must be between 1.8
and 2.0 bar (pilot supply pressure between 2.2 and 6.0 bar)
For pneumatic connection module without pressure reducer:
Connect a pressure gauge using a tee at the pilot supply port 8.
The pilot supply pressure must be 2.2 bar ±10 %.
Solenoid pilot valve with electric status indication:
When a nominal electric signal is connected, the yellow LED is
constantly illuminated when the circuit is not interrupted.
Solenoid pilot valve without electric status indication:
Measure the nominal voltage U
tacts of the connector (single connector or multi-pole connector)
or at the terminals (common cable).
Refer to the table below for the nominal voltage U
switch the solenoid pilot valve on and off:
Nominal voltage U
N
Switching
ON U
 +80 °C
point
OFF U
 –25 °C
Remove the solenoid pilot valve and install a new one, if neces-
sary (see section 7.1).
using a voltmeter at the con-
N
6 V DC
12 V DC
24 V DC
≥4.8 V
≥9.6 V
≥18.0 V
≤1.0 V
≤2.4 V
≤4.7 V
required to
N
24 V AC
≥19.0 V
≤4.5 V
EB 3965 EN