Table 3.1: Configuration of the switch for the analog input and output signals selection
Input/
S1 Switch
Signal
Output
Settings
Voltage
S1.2 = OFF
AI1
Current
S1.2 = ON
Voltage
S1.1 = OFF
AI2
Current
S1.1 = ON
AI3
Current
Voltage
S1.3 = ON
AO1
Current
S1.3 = OFF
Voltage
S1.4 = ON
AO2
Current
S1.4 = OFF
(*) Factory setting.
NOTE!
Settings of the S2 switch:
S2.1 = ON and S2.2 = ON: RS-485 is ON.
S2.1 = OFF and S2.2 = OFF: RS-485 is OFF.
The factory default for the S2.1 and S2.2 switches are OFF.
Other combinations of switch S2 are not allowed.
Follow instructions below for the proper installation of the control wiring:
1. Wire gauge: 0.5 mm
2. Maximum tightening torque: 0.50 N.m (4.50 lbf.in).
3. Use shielded cables for the connections in XC1 and run the cables separated from the
remaining circuits (power, 110 V / 220 Vac control, etc.), according to
on page
22. If control wiring must cross other cables (power cables for instance), make
it cross perpendicular to the wiring and provide a minimum separation of 5 cm (1.9 in) at the
crossing point.
Refer to
Item 3.2.6 Cable Distances on page
Signal
Range
0...10 V
P0233 = 0 (direct reference) or 2 (reverse reference).
(*)
(*)
-10...10 V
P0233 = 4
0...20 mA
P0233 = 0 (direct reference) or 2 (reverse reference).
4...20 mA
P0233 = 1 (direct reference) or 3 (reverse reference).
0...10 V
P0238 = 0 (direct reference) or 2 (reverse reference).
(*)
(*)
-10...10 V
P0238 = 4
0...20 mA
P0238 = 0 (direct reference) or 2 (reverse reference).
4...20 mA
P0238 = 1 (direct reference) or 3 (reverse reference).
-
0...20 mA
P0243 = 0 (direct reference) or 2 (reverse reference).
-
4...20 mA
P0243 = 1 (direct reference) or 3 (reverse reference).
0...10 V
P0253 = 0 (direct reference) or 2 (reverse reference).
(*)
(*)
0...20 mA
P0253 = 0 (direct reference) or 2 (reverse reference).
4...20 mA
P0253 = 1 (direct reference) or 3 (reverse reference).
0...10 V
P0256 = 0 (direct reference) or 2 (reverse reference).
(*)
(*)
0...20 mA
P0256 = 0 (direct reference) or 2 (reverse reference).
4...20 mA
P0256 = 1 (direct reference) or 3 (reverse reference).
(20 AWG) to 1.5 mm² (14 AWG).
²
22, for the proper cable distances.
Installation and Connection
Parameter Settings
Item 3.2.6 Cable Distances
CFW701 | 21