ACC Precision Air Conditioner Controller
User Manual
Menu
Home
Screen >
Settings >
System
Settings >
System
Control
Issue 02 (2016-11-30)
Parameter
Description
Delay
Sets the delay time for
reporting alarms.
Threshold
Sets the alarm threshold for a
certain alarm.
Monitoring mode
Sets the mode in which the
host computer software
monitors the precision air
conditioners.
Unit startup
Sets the time delay for starting
delay
or re-powering on a precision
air conditioner, avoiding large
electric shocks when the
precision air conditioner is
started with other devices.
Energy-saving
Sets the fans to rotate at a low
mode
speed when there is no
requirement.
Alternate work
Sets the alternative working
duration
duration for the two modules
in a dual-module unit when the
cooling requirement is small.
Alternate work
mode
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
related protection actions.
Block: New alarms are not
reported to the EMS. The
EMS can still detect the
alarms that are generated
before the block. The LCD
displays active alarms and
the system implements
related protection actions.
Disallow: Alarms are not
reported and no protection
actions are implemented.
Alternate work: When
cooling is required, system
1 and system 2 take priority
to work in turn. When the
dual-system cooling time
difference reaches the
value of Alternate work
duration, the system with
shorter working time
begins to work first.
No.1 system first: When
cooling is required, system
1 starts first. After the
cooling requirement
A Parameter Description
Default Value
Not displayed
Not displayed
Single mode
10s
Off
100 h
Alternate work
62