ACC Precision Air Conditioner Controller
User Manual
Figure 5-7 Teamwork control information screen
----End
5.10 Which Parameters Are Restored to Default Values
After Default Settings Are Operated
After choosing Settings > Restore Defaults > Yes, the following parameters are displayed:
To prevent loss of important data, record all parameter values before restoring default settings.
After restoring default settings, change the parameter values to the recorded values.
Issue 02 (2016-11-30)
Master/Slave and Active/Standby indicate the information of this single unit. Other information is
about the teamwork control information of the group.
Required cooling capacity: indicates the total cooling/heating requirements of the group and is used
as a reference for enabling the cooling/heating mode by the master device. If the cascade function is
enabled, the capacity is used as a reference for determining whether to start a standby unit.
Required humidity: indicates the total dehumidification and humidification requirements of the
group and is used as a reference for enabling the dehumidification and humidification mode by the
master device.
All parameters displayed on Settings > System Settings.
All parameters displayed on Settings > Alarm Settings.
All parameters displayed on Settings > Comm Settings.
Date format and time zone settings displayed on Settings > User Settings.
All parameters displayed on Maint > Sensor Adjust.
After default settings are restored, all communication addresses are changed to 1 and the communication
between all devices and the EMS is disconnected. The communication addresses must be reset to
recover the communication.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.