Huawei NetCol5000-A User Manual page 21

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual
Figure 3-7 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Step 3 Set Read Community and Write Community.
1.
2.
Issue 02 (2016-11-30)
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read Community and
Write Community. Read Community and Write Community are respectively set to
sread and swrite by default. You can modify the settings by following instructions
provided in
Step
3.
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing
Step
4.
Tap the text box after Read Community, as shown in
as planned, tap
, and then tap Submit.
Figure 3-8 Setting read community
Tap the text box after Write Community, as shown in
Community as planned, tap
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
Figure
, and then tap Submit.
3 Power-on Commissioning
3-8. Set Read Community
3-9. Set Write
15