Installation
SLCP-30 Connections
B.2.3 IFC-1010 & IFC-2020 (JLIB-200A or JLIB-400)
DTK-2LVLP-F Connections
Optional Four-wire
Return Loop
Style 6 (Class A)
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
Optional Four-wire
Return Loop
Style 6 (Class A)
NOTE: Use 12 AWG (3.31 mm
connect the unit's ground terminal to equipment ground. Wire length must be minimized to
provide best protection. Do not connect shield (if present) to surge protector or fire panel.
Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009
IN
SLC Loop
+
–
IN
–
+
SLC Loop
–
+
IN
PLP-42N
SLC Loop
2
) to 18 AWG (0.82 mm
SLCP-30
Optional Four-wire Return Loop
Style 6 (Class A)
OUT
SLC Terminal Block
SLCP-30
OUT
2LVLP-F
OUT
2
) wire with crimp-on connectors to
SLC Surge Suppression
SLC Terminal Block
SLC Terminal Block
61