Devices
1.6.4 Relay Modules
This addressable module provides the control panel with a dry-contact output for activating a
variety of auxiliary devices.
•
M300RJ Relay Module; FlashScan or CLIP mode.
•
XP6-R Controls six Form-C relays; FlashScan or CLIP mode.
1.6.5 Transponders
•
XPIQ An integrated, multiple channel audio amplification and distribution subsystem
remotely controlled by the FACP. It can direct up to four low level audio signals from risers to
up to four audio amplifiers, which are then directed to up to four integrated, continuously
supervised speaker circuits. The XPIQ is FlashScan capable (only).
•
XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with an efficient multiplex
subsystem capability. It communicates with the FACP and functions as a data-gathering panel
for alarm Initiating Device Circuits and as a remote switching center for Notification
Appliance Circuits (NAC), telephone circuits or relays. Not FlashScan capable.
For information on connecting these transponders to the SLC, refer to the XP Transponder Manual
or the XPIQ Manual.
1.6.6 Plug-in Detector Bases
Plug-in detector bases provide a connection between the SLC and a variety of intelligent detectors
which are snapped into place. Standard and isolator bases are used depending upon which NFPA
SLC style is required. Sounder and relay bases are similar to standard bases, but have sound or
relay capabilities.
•
Standard Base - Models B501J (4 inch standard small diameter base, commonly used in
European installations) and B210LPJ (6 inch standard large diameter base, commonly used in
US installations)
•
HARSH™ Base - Model B501B-FTXJ
•
Isolator Base - Model B224BI isolator base.
•
Sounder Base - Models B501BH (standard sounder base), and B501BHT(base with temporal
sounder)
•
Relay Base - Model B224RB relay base
1.6.7 Intelligent Detectors
FSB-200S Addressable, intelligent, single-ended beam smoke detector with built-in sensitivity
testing. The FSB-200 is the same except that it does not provide sensitivity testing. Both models
support FlashScan and CLIP mode.
2951TMJ (Acclimate ™) Addressable, intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection (135°F / 57.2°C). FlashScan capable. (An earlier
version named 2351TMJ was also FlashScan capable. The model named 3251J was discontinued
as of December 1, 2001.)
2951J-COPTIR Intelligent Photoelectric Multi-Criteria Smoke Sensor. Plug-in type smoke sensor
that is a photoelectric sensing chamber combined with Carbon Monoxide (CO), thermal, and infra-
red (IR) sensors to help reduce false alarms. The 2951J-COPTIR adds thermal sensors that will
alarm at a fixed temperature of 135° F (57.2° C) and alarm sensitivity options with built-in alarm
and pre-alarm time delay. JCI panels offer different feature sets across different models. Certain
features of the 2951J-COPTIR may not be available on some panels. The 2951J-COPTIR
supports both FlashScan and CLIP modes. Read Status limitations may apply in CLIP mode.
Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009