Introduction

1.6 Devices

1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
M300MJ Monitor Module; FlashScan or CLIP mode. (An earlier module named M500MJ
was CLIP mode only.)
M300DJ Dual Monitor Module; FlashScan or CLIP mode.
M301MJ Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module
named M501MJ was CLIP mode only.)
M300MJ-4-20 Four-to-Twenty Milli-Amp Monitor Module; FlashScan mode only. CLIP
mode operation will generate a trouble message at the panel. This module is only compatible
with the IFC2-3030.
M302MJ Zone Interface Module; FlashScan or CLIP mode. (An earlier module named
M502MJ was CLIP mode only).
XP5-M Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. Supports FlashScan or CLIP mode. This module is
capable of participating in degraded mode where supported by the FACP. (See the XP5 Series
Manual)
XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire
detectors; FlashScan or CLIP mode.
XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of
participating in degraded mode where supported by the FACP.
1.6.2 Control Modules
Through these addressable modules, the control panel can selectively activate Notification
Appliance Circuits (NAC).
M300CJ Control Module; FlashScan or CLIP mode. (Earlier monitor modules named CMX-1
and M510CJ were CLIP mode only.)
M300CJ-REL Control Module; FlashScan mode only. CLIP mode operation will generate a
trouble message at the panel.
XP5-C Acts as a NAC or a speaker/telephone circuit (Class B only) or a Form-C relay.
FlashScan capable. (See the XP5 Series Manual.)
XP6-C Controls six NAC or speaker/telephone circuits; FlashScan or CLIP mode.
M500FPJ Firefighter's Telephone Module; FlashScan-only device for use with Fire Fighters
Telephone on IFC-320, IFC2-640, IFC-640, IFC-3030, and IFC2-3030. (See the Voice Alarm
System Manual, the DVC Manual, or the DAA Manual.)
1.6.3 Isolator Modules
Isolator Modules permit a short-circuited section of the SLC to be fault isolated from the remainder
of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator
modules are required to meet the requirements of an NFPA Style 7 circuit.
M500XJ Loop Fault Isolator Module; FlashScan or CLIP mode.
12
Johnson Controls, Inc. SLC Wiring Manual — P/N 51870:G 04/23/2009