VICTRIX PRO 35 1 I - 55 1 I

15 KIT SIZES AND CONNECTIONS (OPTIONAL) WITH VICTRIX PRO 35 1 I - 55 1 I BOILERS

IN CASCADE CONFIGURATION (UP TO A MAXIMUM OF FIVE APPLIANCES)

Reference
2 boilers
X
2120 mm
Y
1917 mm
Z
58 mm
Ø
160 mm
N.B.: In case of installation outside, the safety devices kit must be
protected using the IPX4D protection box kit for safety devices for
boilers in cascade configuration, code 3.024038.
Immergas declines all liability whenever the installer does not use
original Immergas devices and kits, or uses them improperly.
The sensitive elements of the safety devices must be set up as
described in the installation instructions, in compliance with the
provisions cascade forth in the ''R'' collection.
For design purposes, by installing the Immergas safety kit, the
following devices are included: Manometer-holder cock, ma-
nometer, thermometer, manual reset thermostat, manual reset
maximum pressure switch, and manual reset minimum pressure
switch (the boiler is already equipped as per standard with 4-bar
safety valve and standard draining funnel).
3 boilers
4 boilers
2920 mm
3720 mm
1959 mm
2001 mm
100 mm
142 mm
160 mm
160 mm
5 boilers
4520 mm
2043 mm
184 mm
160 mm
There is a fitting for an expansion vessel on the flow and return
stub pipes.
The modular boilers, i.e. installed in cascade (battery) with an Im-
mergas original hydraulic manifold kit, must be considered a unique
appliance, which assumes the serial number (factory number) of
the boiler nearest to the safety devices. It is therefore possible to
set up up to 5 (five) modules side-by-side, with a single safety kit.
The hydraulic manifolds (optional) are equipped with non-return
valve positioned on the flow pipe and with system interception cocks
positioned on the flow and return pipes of every boiler (2-way on
return and 3-way on flow).
19