Victrix Pro 35 1 I-55 1 I Specifications - Immergas VICTRIX PRO 1 I Series Technical Sheet

Wall-hung modular condensing boilers for high power
Table of Contents

Advertisement

VICTRIX PRO 35 1 I - 55 1 I
1
Wall-hung, open-chamber and fan-assisted pre-mixed con-
densing boilers, high efficiency with forced circulation, with a
maximum heat output for 50/30°C of:
VICTRIX PRO 35 1 I = 37.3 kW (32.155 kcal/h)
VICTRIX PRO 55 1 I = 54.8 kW (47.097 kcal/h)
Type-approved for installation in heating control unit and
outside the building without any additional protection (in the
open), it can be used in two configurations:
Open chamber and fan assisted (appliance type B
B
) - No additional kit is required for this factory-supplied
53p
configuration.
Sealed chamber and fan assisted (appliance type C
- Only using the vertical or horizontal concentric kits.
The boiler is made up from:
• total pre-mixing combustion system with steel multigas cylin-
drical burner, complete with ignition electrodes and ionisation
control;
• pneumatic gas valve with double shutter;
• primary gas/water heat exchanger with casing in composite
material with air vent valve and internal stainless steel coil,
composed of 9 elements (6+3 on flue side);
• combustion chamber in stainless steel internally isolated with
ceramic panels;
• fan for flue evacuation with electronically variable speed;
• circuit for disposal of condensate including trap and flexible
drain hose;
• hydraulic unit comprised of flow manifold, circulation pump
and automatic air vent valve;
• 4 bar safety valve and standard draining funnel;
• system flow rate meter (flow switch);
• water overheating safety thermostat, heat exchanger safety
thermofuse and flue control probe;
• control panel supplied with P.C.B. with microprocessor with
continuous flame modulation on heating with P.I.D. control,
modulation field referring to 50/30 °C between:
3.7 and 37.3 kW (between 3.208 and 32.155 kcal/h) for
VICTRIX PRO 35 1 I;
5.5 and 54.8 kW (between 4.701 and 47.097 kcal/h) for
VICTRIX PRO 55 1 I;
• system flow regulation probe;
• system return regulation probe;
• heating flow temperature with factory setting between 25 and
85°C;
• ignition delay device in central heating phase, antifreeze
protection, pump anti-blocking function, chimney sweep
function;
• control panel composed of main switch, C.H. system pressure
gauge, multifunction back-lit display and 7-key push button
panel with protective sliding door;
• setting and adjusting boiler operation parameters through
the following keys: C.H. temperature adjustment buttons,
D.W.H. temperature adjustment buttons, summer / winter
mode button, reset button, info, parameter confirmation and
multi-function button (anomaly records, D.W.H. exclusion);
• self-diagnosis system with digital display of the temperature,

VICTRIX PRO 35 1 I-55 1 I SPECIFICATIONS

/ B
23p
/C
/C
13
33
functioning status and error codes;
• IPX5D electrical insulation level, with possibility of installation
outside without any additional protection (in the open);
• antifreeze protection to -5 °C as per standard (-15 °C with
relevant kit optional);
• set-up for the connection of the cascade and zone regulator
and of the external probe;
• set-up for connection to an external 3-way valve with 230 Vac
/
power supply, for coupling to a separate storage tank unit for
33
the production of D.W.H.;
• set-up for functioning in cascade configuration (up to 5 boilers
)
with a unique safety devices kit);
63
• set-up for the installation of the safety stub pipes, both in single
and cascade configuration (up to 5 boilers);
• possibility of installation with the supporting frame kit in "free
standing" mode, which can be used to install one or more
VICTRIX PRO 1 I without having to mount the boilers directly
on the wall. The frame is also suitable for outdoor installation,
in the open;
• possibility of connecting (in combination with a cascade and
zone regulator) to a remote management system for remote
management of the system (optional);
• it can be combined with the system by Ø 80 mm flexible duct-
ing (single installation).
Supplied with sample points for combustion analysis, bottom
protective metal-sheet plate grid and gas interception cock.
Category II appliance
2H3P
CE Marking.
It is available in the model:
• VICTRIX PRO 35 1 I
• VICTRIX PRO 55 1 I
NOTA BENE: for correct installation of the boiler the Immergas
"Green Range" air intake/fumes exhaust kit must be used and
however, dedicated for the VICTRIX PRO 1 I boiler, whether in
single or cascade configuration (battery).
, operates with natural gas and L.P.G.
code 3.024488
code 3.024489
5