VICTRIX PRO 1 I
11 THREE-WAY VALVE KIT FOR COMBINATION WITH SEPARATE STORAGE TANK UNIT
(CODE 3.023950) FOR VICTRIX PRO 35 1 I - 55 1 I - 80 1 I - 100 1 I - 120 1 I
The kit is sized for single boiler operation or in combination
with a separate boiler for D.W.H. production. The output of the
boiler in domestic hot water operation must be set based on the
heat exchange output of the coil supplied with the storage tank.
The diverter valve (which is powered by 230 Vac) comes installed
on the flow pipe in combination with a blind manifold (3), re-
ducing the overall installation footprint.
The standard kit comes with a NTC probe which needs to be
applied to the external storage tank unit and connected to the
boiler card (see electrical diagram provided below), removing
Flow rate coefficient Kv of the three-way valve = 7.7
KEY:
1
- Gasket 44 x 34 x 2
2
- Return section from the insulated boiler unit
3
- Flow section to the insulated boiler unit
3-way brass valve
4
-
Valve drive motor
5
-
Fitting pipe
6
-
Gasket 30 x 22 x 2
7
-
M - System flow
R
- System return
MU - Flow to boiler unit
RU - Return from boiler unit
KEY:
B2 - Domestic hot water probe
M30 - Three-way valve
6
7
7
MU
5
4
7
G1"
any pre-installed temperature probe from the storage tank unit.
Kit installation requires the use of an ON-OFF chrono-thermo-
stat for boiler management.
Note: The boiler has an IPX5D electric insulation rating and
can also be installed outdoors without additional protections.
However, if installed outdoors, the outdoor piping should be
insulated and the kit protected from the elements based on its
electric protection rating.
R
M
1
2
RU
3
G1"
1 1
G1"1/2
1
G1"1/2
15